HP Performance Optimized Data Center (POD) 20cp manual Fire alarm and suppression system

Page 66

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

Compare the following with site

Annually

Qualified personnel

 

indications (if available):

 

 

 

CWS/CWR temperature

 

 

 

CWS/CWR pressure

 

 

 

Flow rate (if possible)

 

 

 

(Investigate discrepancies, trouble

 

 

 

shoot, and replace as necessary.)

 

 

POD SHUT DOWN REQUIRED

Annually

Qualified personnel

 

Calibrate (zero out) POD

 

 

 

differential pressure sensors.

 

 

 

(Investigate discrepancies, trouble

 

 

 

shoot, and replace as necessary.)

 

 

Lighting

Visual inspection of lighting

As needed or

Licensed electrician/

 

fixtures and lamps. Replace

Quarterly

Qualified personnel

 

components upon failure.

 

 

Fire alarm and suppression system

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

Full system functional check

Inspect and perform a functional

As required by

Authorized technician

 

check of the system.

local code

 

Fire panel

Inspect and test fire panel

Bi-annually

Authorized technician

 

battery backup system.

 

 

VESDA

Inspect and test VESDA power

Quarterly

Authorized technician

 

supply.

 

 

Inspect the VESDA pipe

Bi-annually

Authorized technician

 

network.

 

 

Inspect the VESDA filter.

Annually

Authorized technician

 

Replace as necessary.

 

 

Conduct a VESDA pipe integrity

Annually

Authorized technician

 

smoke test.

 

 

Check the VESDA pipe flow.

Annually

Authorized technician

Clean the VESDA sampling

Every 2 years

Authorized technician

 

points.

 

 

Flush the VESDA pipe network.

Every 2 years

Authorized technician

VESDA system air

As required by

Authorized technician

 

sampling/smoke test

local code

 

Suppression system

Suppression system test

As required by

Authorized technician

 

 

local code

 

Fire-pull visual and operational

As required by

Authorized technician

 

inspection

local code

 

Fire strobe and horn visual and

As required by

Authorized technician

 

operational inspection

local code

 

HP POD 20c structure

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

 

 

Complete structure

Visually inspect the structural

Annually

Qualified personnel

 

 

integrity.

 

 

 

 

 

 

Periodic maintenance 66

Image 66
Contents Abstract Page Contents Contacting HP Illustrated parts catalog Structural component identificationLife safety component identification Component DescriptionElectrical power component identification Front view shown Component DescriptionAccessed only by authorized personnel Electrical safety label Description Control cabinet component identificationHP POD 20c racks Aisle clearancesCold aisle clearance Replaceable components for China models Hot aisle clearanceSpare part number Description Installation considerations Optional Fire suppression system OverviewEPO button Removal and replacement proceduresButtons Removing the EPO buttonDIN rail components Control relay moduleRemoving the control relay module Differential pressure sensor Replacing the control relay moduleRemoving the differential pressure sensor Replacing the differential pressure sensorRemoving the magnetic contacts Door position devicesMagnetic contacts Replacing the magnetic contactsElectrical Busway drop boxRemoving the busway drop box Removal and replacement procedures Replacing the busway drop box Fans IT cooling fanRemoving the IT cooling fan Ventilation fan Replacing the IT cooling fanRemoving the Rittal SK 3326 ventilation fan Replacing the Rittal SK 3326 ventilation fanRemoving the heat exchanger air filter FiltersHeat exchanger air filters Replacing the heat exchanger air filterVesda filter Removing the Vesda filterRittal SK 3326 ventilation fan filter Replacing the Vesda filterRemoving the Rittal SK 3326 ventilation fan filter Replacing the Rittal SK 3326 ventilation fan filterIndicators ECS touchscreen and EPO indicatorsRemoving the ECS EPO LED indicators Replacing the ECS EPO LED indicatorsRemoving the LED light LightsLED light Replacing the LED lightSensors Heat exchanger condensate drain pan sensorsRemoving the drain pan sensor Chilled water supply and return header drain pan sensors Replacing the drain pan sensorHumidistat Removing the humidistatReplacing the humidistat Humidity sensor Removing the humidity sensor Replacing the humidity sensorChilled water system temperature sensor Removing temperature sensor from the chilled water systemChilled water temperature sensor internal components Replacing the temperature sensor in the chilled water systemReplace the chilled water temperature sensor circuit board Removal and replacement procedures Temperature sensor cold aisle Removing the cold aisle temperature sensorReplacing the cold aisle temperature sensor Temperature sensors hot aisle Removing the hot aisle temperature sensorReplacing the hot aisle temperature sensor Fluid system componentsChilled water supply and return header pressure sensors You need a wrench to remove and replace the pressure sensors Chilled water flow sensor Removing the chilled water flow sensorReplacing the chilled water flow sensor Chilled water system temperature sensor Chilled water temperature sensor internal components Replace the chilled water temperature sensor circuit board Heat exchanger Humidifier Removing the humidifierRemoval and replacement procedures Replacing the humidifier Removal and replacement procedures Humidistat if installed Replacing the humidistat Valves External chilled water isolation valveRemoving the external chilled water isolation valve External pressure gauge isolation valve Replacing the external chilled water isolation valveRemoving the external pressure gauge isolation valve Replacing the external pressure gauge isolation valve Qualified personnel Periodic maintenancePeriodic maintenance overview Cooling systemLeak detection Leak isolationHumidifier if installed ECS POD Shut Down Required Fire alarm and suppression system HP POD 20c structureLife safety EPO Functional TestAccess control Third-party componentsSpecifications General HP POD 20c specificationsElectrical specifications Water specifications Rack specificationsEnvironmental specifications Thermal and air flow performanceOptional features specifications Contacting HP Before you contact HPHP contact information Safety and NEC compliance Regulatory informationHP POD 20c regulatory compliance Regulatory requirements for Exit signs With Council, Inc Regulatory information Glossary Branch circuitSOW Documentation feedback Index HP POD 20c structure Temperature sensors, cold aisle