HP Performance Optimized Data Center (POD) 20cp Specifications, General HP POD 20c specifications

Page 69

Specifications

General HP POD 20c specifications

Features

Specifications

 

 

Overall dimensions

Height—3.05 m (10 ft)

 

Length—6.10 m (20 ft)

 

Width—2.43 m (7.97 ft)

 

 

Weight1

Empty—7,711 kg (17,000 lb)

 

Maximum fully loaded—22,680 kg (50,000 lb)

 

 

Maximum power2

288 kW

Power input voltage

480 V, 3-phase, 4-wire

Power input current

2 x 320 A 3-phase, 3-wire feeders

Maximum rack quantity

10 racks

Rack Units (RU) per rack

50 RU

Rack Units (RU) total

500 RU

Average capacity per rack (kW)

30 kW

Peak rack capacity

69 kW

 

 

Voltage to rack

200-240 VAC

Minimum quantity of PDUs per HP POD 20c

10 (one per rack)

Maximum quantity of PDUs per HP POD 20c

20 (two per rack)

Maximum power per PDU

30A = 17 kW; 60A = 34 kW

Network supported

Bulk cable pass-through-fiber

 

Bulk cable pass-through-copper

 

External rated DEMARC box

 

 

1The empty weight includes the HP POD 20c structure, empty racks, PDUs, and drop boxes. It does not include IT equipment.

2The maximum power depends on the exact installation and power configuration in your POD. The HP POD 20c is electrically limited to 288 kW.

Electrical specifications

Electrical busway system information

Feature

Specification

 

 

Number of busways

2

Frequency

60 Hz

Amps (per busway)

200 A

Voltage (per busway)

380-415 Y

Grounding

Copper

Busway configuration

3-phase + neutral + equipment ground

Specifications 69

Image 69
Contents Abstract Page Contents Contacting HP Structural component identification Illustrated parts catalogComponent Description Life safety component identificationFront view shown Component Description Electrical power component identificationAccessed only by authorized personnel Control cabinet component identification Electrical safety label DescriptionHP POD 20c racks Aisle clearancesCold aisle clearance Hot aisle clearance Replaceable components for China modelsSpare part number Description Overview Installation considerations Optional Fire suppression systemButtons Removal and replacement proceduresEPO button Removing the EPO buttonDIN rail components Control relay moduleRemoving the control relay module Replacing the control relay module Differential pressure sensorReplacing the differential pressure sensor Removing the differential pressure sensorMagnetic contacts Door position devicesRemoving the magnetic contacts Replacing the magnetic contactsElectrical Busway drop boxRemoving the busway drop box Removal and replacement procedures Replacing the busway drop box IT cooling fan FansRemoving the IT cooling fan Replacing the IT cooling fan Ventilation fanReplacing the Rittal SK 3326 ventilation fan Removing the Rittal SK 3326 ventilation fanHeat exchanger air filters FiltersRemoving the heat exchanger air filter Replacing the heat exchanger air filterRemoving the Vesda filter Vesda filterReplacing the Vesda filter Rittal SK 3326 ventilation fan filterReplacing the Rittal SK 3326 ventilation fan filter Removing the Rittal SK 3326 ventilation fan filterECS touchscreen and EPO indicators IndicatorsReplacing the ECS EPO LED indicators Removing the ECS EPO LED indicatorsLED light LightsRemoving the LED light Replacing the LED lightSensors Heat exchanger condensate drain pan sensorsRemoving the drain pan sensor Replacing the drain pan sensor Chilled water supply and return header drain pan sensorsRemoving the humidistat HumidistatReplacing the humidistat Humidity sensor Replacing the humidity sensor Removing the humidity sensorRemoving temperature sensor from the chilled water system Chilled water system temperature sensorReplacing the temperature sensor in the chilled water system Chilled water temperature sensor internal componentsReplace the chilled water temperature sensor circuit board Removal and replacement procedures Temperature sensor cold aisle Removing the cold aisle temperature sensorReplacing the cold aisle temperature sensor Removing the hot aisle temperature sensor Temperature sensors hot aisleReplacing the hot aisle temperature sensor Fluid system componentsChilled water supply and return header pressure sensors You need a wrench to remove and replace the pressure sensors Chilled water flow sensor Removing the chilled water flow sensorReplacing the chilled water flow sensor Chilled water system temperature sensor Chilled water temperature sensor internal components Replace the chilled water temperature sensor circuit board Heat exchanger Removing the humidifier HumidifierRemoval and replacement procedures Replacing the humidifier Removal and replacement procedures Humidistat if installed Replacing the humidistat Valves External chilled water isolation valveRemoving the external chilled water isolation valve External pressure gauge isolation valve Replacing the external chilled water isolation valveRemoving the external pressure gauge isolation valve Replacing the external pressure gauge isolation valve Periodic maintenance overview Periodic maintenanceQualified personnel Cooling systemLeak isolation Leak detectionHumidifier if installed ECS POD Shut Down Required HP POD 20c structure Fire alarm and suppression systemEPO Functional Test Life safetyThird-party components Access controlSpecifications General HP POD 20c specificationsElectrical specifications Environmental specifications Rack specificationsWater specifications Thermal and air flow performanceOptional features specifications Contacting HP Before you contact HPHP contact information Safety and NEC compliance Regulatory informationHP POD 20c regulatory compliance Regulatory requirements for Exit signs With Council, Inc Regulatory information Branch circuit GlossarySOW Documentation feedback Index HP POD 20c structure Temperature sensors, cold aisle