HP Performance Optimized Data Center (POD) 20cp manual Life safety, EPO Functional Test

Page 67

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

Inspect the door operation and

Annually

Qualified personnel

 

inspect the door gaskets for water

 

 

 

and air leaks.

 

 

Visually inspect the paint. Perform

Annually

Qualified personnel

 

prep and touch-up as necessary.

 

 

Life safety

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

Manual EPO shunt trip

EPO FUNCTIONAL TEST

Annually

Qualified personnel

 

Manually initiate EPO with the

 

 

 

internal and external push buttons

 

 

 

(if installed) in succession. (Verify

 

 

 

all shunt-trips on all panels trip.)

 

 

Thermal EPO shunt trip

EPO FUNCTIONAL TEST

Annually

Qualified personnel

 

Initiate a thermal (automatic) EPO

 

 

 

shutdown via the EPO

 

 

 

temperature switches located in

 

 

 

the hot aisle. (Verify all shunt-trips

 

 

 

on all panels trip.)

 

 

EPO System Test

EPO NON-FUNCTIONAL TEST

Annually

Qualified personnel

 

Mode Key Switch Test - rotate

 

 

 

keyed switch through all modes.

 

 

 

ARMED MODE - Verify:

 

 

 

Power Indicator - White

 

 

 

Armed Light - White

 

 

 

BYPASS MODE - Verify

 

 

 

Bypass Light - Green

 

 

 

TEST MODE - Verify:

 

 

 

Test Light - Amber

 

 

 

Press EPO button (each in

 

 

 

succession) and thermal trip to

 

 

 

verify:

 

 

 

Reset Light - White

 

 

 

Audible alarm

 

 

 

Visual lamp indicator

 

 

 

Replace light upon failure

 

 

Emergency Lighting

Verify emergency lighting is

Every 2 years

Qualified personnel

 

visible when all lighting is off and

 

 

 

the POD doors are shut.

 

 

Exit signs

Visually inspect Tritium exit signs

Every 2 years

Qualified personnel

 

for operation or damage.

 

 

 

Replace as necessary.

 

 

Emergency egress

Personnel door emergency egress

Bi-annually

Qualified personnel

 

panic bars. (Visual and

 

 

 

operational inspection.)

 

 

Periodic maintenance 67

Image 67
Contents Abstract Page Contents Contacting HP Structural component identification Illustrated parts catalogComponent Description Life safety component identificationFront view shown Component Description Electrical power component identificationAccessed only by authorized personnel Control cabinet component identification Electrical safety label DescriptionAisle clearances HP POD 20c racksCold aisle clearance Hot aisle clearance Replaceable components for China modelsSpare part number Description Overview Installation considerations Optional Fire suppression systemRemoving the EPO button Removal and replacement proceduresButtons EPO buttonControl relay module DIN rail componentsRemoving the control relay module Replacing the control relay module Differential pressure sensorReplacing the differential pressure sensor Removing the differential pressure sensorReplacing the magnetic contacts Door position devicesMagnetic contacts Removing the magnetic contactsBusway drop box ElectricalRemoving the busway drop box Removal and replacement procedures Replacing the busway drop box IT cooling fan FansRemoving the IT cooling fan Replacing the IT cooling fan Ventilation fanReplacing the Rittal SK 3326 ventilation fan Removing the Rittal SK 3326 ventilation fanReplacing the heat exchanger air filter FiltersHeat exchanger air filters Removing the heat exchanger air filterRemoving the Vesda filter Vesda filterReplacing the Vesda filter Rittal SK 3326 ventilation fan filterReplacing the Rittal SK 3326 ventilation fan filter Removing the Rittal SK 3326 ventilation fan filterECS touchscreen and EPO indicators IndicatorsReplacing the ECS EPO LED indicators Removing the ECS EPO LED indicatorsReplacing the LED light LightsLED light Removing the LED lightHeat exchanger condensate drain pan sensors SensorsRemoving the drain pan sensor Replacing the drain pan sensor Chilled water supply and return header drain pan sensorsRemoving the humidistat HumidistatReplacing the humidistat Humidity sensor Replacing the humidity sensor Removing the humidity sensorRemoving temperature sensor from the chilled water system Chilled water system temperature sensorReplacing the temperature sensor in the chilled water system Chilled water temperature sensor internal componentsReplace the chilled water temperature sensor circuit board Removal and replacement procedures Removing the cold aisle temperature sensor Temperature sensor cold aisleReplacing the cold aisle temperature sensor Removing the hot aisle temperature sensor Temperature sensors hot aisleFluid system components Replacing the hot aisle temperature sensorChilled water supply and return header pressure sensors You need a wrench to remove and replace the pressure sensors Removing the chilled water flow sensor Chilled water flow sensorReplacing the chilled water flow sensor Chilled water system temperature sensor Chilled water temperature sensor internal components Replace the chilled water temperature sensor circuit board Heat exchanger Removing the humidifier HumidifierRemoval and replacement procedures Replacing the humidifier Removal and replacement procedures Humidistat if installed Replacing the humidistat External chilled water isolation valve ValvesRemoving the external chilled water isolation valve Replacing the external chilled water isolation valve External pressure gauge isolation valveRemoving the external pressure gauge isolation valve Replacing the external pressure gauge isolation valve Cooling system Periodic maintenancePeriodic maintenance overview Qualified personnelLeak isolation Leak detectionHumidifier if installed ECS POD Shut Down Required HP POD 20c structure Fire alarm and suppression systemEPO Functional Test Life safetyThird-party components Access controlGeneral HP POD 20c specifications SpecificationsElectrical specifications Thermal and air flow performance Rack specificationsEnvironmental specifications Water specificationsOptional features specifications Before you contact HP Contacting HPHP contact information Regulatory information Safety and NEC complianceHP POD 20c regulatory compliance Regulatory requirements for Exit signs With Council, Inc Regulatory information Branch circuit GlossarySOW Documentation feedback Index HP POD 20c structure Temperature sensors, cold aisle