Component to be inspected | Task | Frequency | Capable Party |
|
|
|
|
— | Inspect the door operation and | Annually | Qualified personnel |
| inspect the door gaskets for water |
|
|
| and air leaks. |
|
|
— | Visually inspect the paint. Perform | Annually | Qualified personnel |
| prep and |
|
|
Life safety
Component to be inspected | Task | Frequency | Capable Party | |
|
|
|
| |
Manual EPO shunt trip | EPO FUNCTIONAL TEST | Annually | Qualified personnel | |
| Manually initiate EPO with the |
|
| |
| internal and external push buttons |
|
| |
| (if installed) in succession. (Verify |
|
| |
| all |
|
| |
Thermal EPO shunt trip | EPO FUNCTIONAL TEST | Annually | Qualified personnel | |
| Initiate a thermal (automatic) EPO |
|
| |
| shutdown via the EPO |
|
| |
| temperature switches located in |
|
| |
| the hot aisle. (Verify all |
|
| |
| on all panels trip.) |
|
| |
EPO System Test | EPO | Annually | Qualified personnel | |
| Mode Key Switch Test - rotate |
|
| |
| keyed switch through all modes. |
|
| |
| ARMED MODE - Verify: |
|
| |
| • Power Indicator - White |
|
| |
| • Armed Light - White |
|
| |
| BYPASS MODE - Verify |
|
| |
| • Bypass Light - Green |
|
| |
| TEST MODE - Verify: |
|
| |
| • Test Light - Amber |
|
| |
| Press EPO button (each in |
|
| |
| succession) and thermal trip to |
|
| |
| verify: |
|
| |
| • Reset Light - White |
|
| |
| • | Audible alarm |
|
|
| • | Visual lamp indicator |
|
|
| Replace light upon failure |
|
| |
Emergency Lighting | Verify emergency lighting is | Every 2 years | Qualified personnel | |
| visible when all lighting is off and |
|
| |
| the POD doors are shut. |
|
| |
Exit signs | Visually inspect Tritium exit signs | Every 2 years | Qualified personnel | |
| for operation or damage. |
|
| |
| Replace as necessary. |
|
| |
Emergency egress | Personnel door emergency egress | Qualified personnel | ||
| panic bars. (Visual and |
|
| |
| operational inspection.) |
|
|
Periodic maintenance 67