HP Performance Optimized Data Center (POD) 20cp manual POD Shut Down Required

Page 65

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

POD SHUT DOWN REQUIRED

Annually

Licensed electrician

 

Conduct torque checks on the

 

 

 

following:

 

 

 

Main/House Power Feeds

 

 

 

Electrical panels, breakers,

 

 

 

 

and disconnects

 

 

 

Busway End Feeds and Drop

 

 

 

 

Box locking mechanism (bolt)

 

 

 

 

 

 

Grounding

Grounding system residence test

Every 2 years

Licensed electrician

 

using the DUCTOR method

 

 

POD SHUT DOWN REQUIRED

Every 2 years

Licensed electrician

 

Ground and grounding

 

 

 

connection/lug located internal to

 

 

 

each electrical panel torque test.

 

 

 

Clean and re-tighten as necessary.

 

 

Service entrance grounding

Every 2 years

Licensed electrician

 

ground-rod/ground well and

 

 

 

grounding connection/lug located

 

 

 

external to the POD torque test.

 

 

 

Clean and re-tighten as necessary.

 

 

POD SHUT DOWN REQUIRED

Every 2 years

Licensed electrician

 

Service entrance ground

 

 

 

connection/lug located on the

 

 

 

switchboard (or landing location)

 

 

 

torque test. Clean and re-tighten as

 

 

 

necessary.

 

 

Grounding system bonding

Every 2 years

Licensed electrician

 

jumpers that connect racks to the

 

 

 

POD structure and rack to rack

 

 

 

torque test. Clean and re-tighten as

 

 

 

necessary.

 

 

Circuit breakers

Panel breaker operational test

Annually

Licensed

 

(open and shut).

 

electrician/Qualified

 

 

 

 

personnel

 

 

 

 

LLS inspection of breakers,

Quarterly

Licensed

 

disconnects, motor starters, and

 

electrician/Qualified

 

fuse holders (physical).

 

personnel

 

 

 

 

Breaker fault testing for all

Every 3 years

Third party testing

 

breakers ≥ 250AF

 

facility

 

 

 

 

Sensors

Verify proper operation of:

Annually

Qualified personnel

 

Internal POD temperature

 

 

 

 

sensors (thermometer)

 

 

 

Relative humidity sensors (RH

 

 

 

 

meter)

 

 

 

(Investigate discrepancies, trouble

 

 

 

shoot, and replace as necessary.)

 

 

Periodic maintenance 65

Image 65
Contents Abstract Page Contents Contacting HP Structural component identification Illustrated parts catalogComponent Description Life safety component identificationFront view shown Component Description Electrical power component identificationAccessed only by authorized personnel Control cabinet component identification Electrical safety label DescriptionCold aisle clearance HP POD 20c racksAisle clearances Hot aisle clearance Replaceable components for China modelsSpare part number Description Overview Installation considerations Optional Fire suppression systemButtons Removal and replacement proceduresEPO button Removing the EPO buttonRemoving the control relay module DIN rail componentsControl relay module Replacing the control relay module Differential pressure sensorReplacing the differential pressure sensor Removing the differential pressure sensorMagnetic contacts Door position devicesRemoving the magnetic contacts Replacing the magnetic contactsRemoving the busway drop box ElectricalBusway drop box Removal and replacement procedures Replacing the busway drop box IT cooling fan FansRemoving the IT cooling fan Replacing the IT cooling fan Ventilation fanReplacing the Rittal SK 3326 ventilation fan Removing the Rittal SK 3326 ventilation fanHeat exchanger air filters FiltersRemoving the heat exchanger air filter Replacing the heat exchanger air filterRemoving the Vesda filter Vesda filterReplacing the Vesda filter Rittal SK 3326 ventilation fan filterReplacing the Rittal SK 3326 ventilation fan filter Removing the Rittal SK 3326 ventilation fan filterECS touchscreen and EPO indicators IndicatorsReplacing the ECS EPO LED indicators Removing the ECS EPO LED indicatorsLED light LightsRemoving the LED light Replacing the LED lightRemoving the drain pan sensor SensorsHeat exchanger condensate drain pan sensors Replacing the drain pan sensor Chilled water supply and return header drain pan sensorsRemoving the humidistat HumidistatReplacing the humidistat Humidity sensor Replacing the humidity sensor Removing the humidity sensorRemoving temperature sensor from the chilled water system Chilled water system temperature sensorReplacing the temperature sensor in the chilled water system Chilled water temperature sensor internal componentsReplace the chilled water temperature sensor circuit board Removal and replacement procedures Replacing the cold aisle temperature sensor Temperature sensor cold aisleRemoving the cold aisle temperature sensor Removing the hot aisle temperature sensor Temperature sensors hot aisleChilled water supply and return header pressure sensors Replacing the hot aisle temperature sensorFluid system components You need a wrench to remove and replace the pressure sensors Replacing the chilled water flow sensor Chilled water flow sensorRemoving the chilled water flow sensor Chilled water system temperature sensor Chilled water temperature sensor internal components Replace the chilled water temperature sensor circuit board Heat exchanger Removing the humidifier HumidifierRemoval and replacement procedures Replacing the humidifier Removal and replacement procedures Humidistat if installed Replacing the humidistat Removing the external chilled water isolation valve ValvesExternal chilled water isolation valve Removing the external pressure gauge isolation valve External pressure gauge isolation valveReplacing the external chilled water isolation valve Replacing the external pressure gauge isolation valve Periodic maintenance overview Periodic maintenanceQualified personnel Cooling systemLeak isolation Leak detectionHumidifier if installed ECS POD Shut Down Required HP POD 20c structure Fire alarm and suppression systemEPO Functional Test Life safetyThird-party components Access controlElectrical specifications SpecificationsGeneral HP POD 20c specifications Environmental specifications Rack specificationsWater specifications Thermal and air flow performanceOptional features specifications HP contact information Contacting HPBefore you contact HP HP POD 20c regulatory compliance Safety and NEC complianceRegulatory information Regulatory requirements for Exit signs With Council, Inc Regulatory information Branch circuit GlossarySOW Documentation feedback Index HP POD 20c structure Temperature sensors, cold aisle