HP Performance Optimized Data Center (POD) 20cp manual Electrical power component identification

Page 7

Electrical power component identification

Front view shown

Item

Component

Description

 

 

 

1

Demarcation box*

Customer communication connection point for the following

 

 

components:

 

 

ECS

 

 

Security

 

 

Phone

 

 

 

2

Fire box*

Connection location for fire emergency and VESDAnet signals

3

380-415 VAC Y, 3-phase,

Feed A and B power for IT critical loads busways and house power

 

400 A

 

 

*The demarcation box and the fire box are communication data points that are provided on the POD by HP. Connecting these data points is the responsibility of the customer, unless an approved Statement of Work is initiated.

Main breaker locations

Side view shown

Illustrated parts catalog 7

Image 7
Contents Abstract Page Contents Contacting HP Structural component identification Illustrated parts catalogComponent Description Life safety component identificationFront view shown Component Description Electrical power component identificationAccessed only by authorized personnel Control cabinet component identification Electrical safety label DescriptionAisle clearances HP POD 20c racksCold aisle clearance Hot aisle clearance Replaceable components for China modelsSpare part number Description Overview Installation considerations Optional Fire suppression systemRemoving the EPO button Removal and replacement proceduresButtons EPO buttonControl relay module DIN rail componentsRemoving the control relay module Replacing the control relay module Differential pressure sensorReplacing the differential pressure sensor Removing the differential pressure sensorReplacing the magnetic contacts Door position devicesMagnetic contacts Removing the magnetic contactsBusway drop box ElectricalRemoving the busway drop box Removal and replacement procedures Replacing the busway drop box IT cooling fan FansRemoving the IT cooling fan Replacing the IT cooling fan Ventilation fanReplacing the Rittal SK 3326 ventilation fan Removing the Rittal SK 3326 ventilation fanReplacing the heat exchanger air filter FiltersHeat exchanger air filters Removing the heat exchanger air filterRemoving the Vesda filter Vesda filterReplacing the Vesda filter Rittal SK 3326 ventilation fan filterReplacing the Rittal SK 3326 ventilation fan filter Removing the Rittal SK 3326 ventilation fan filterECS touchscreen and EPO indicators IndicatorsReplacing the ECS EPO LED indicators Removing the ECS EPO LED indicatorsReplacing the LED light LightsLED light Removing the LED lightHeat exchanger condensate drain pan sensors SensorsRemoving the drain pan sensor Replacing the drain pan sensor Chilled water supply and return header drain pan sensorsRemoving the humidistat HumidistatReplacing the humidistat Humidity sensor Replacing the humidity sensor Removing the humidity sensorRemoving temperature sensor from the chilled water system Chilled water system temperature sensorReplacing the temperature sensor in the chilled water system Chilled water temperature sensor internal componentsReplace the chilled water temperature sensor circuit board Removal and replacement procedures Removing the cold aisle temperature sensor Temperature sensor cold aisleReplacing the cold aisle temperature sensor Removing the hot aisle temperature sensor Temperature sensors hot aisleFluid system components Replacing the hot aisle temperature sensorChilled water supply and return header pressure sensors You need a wrench to remove and replace the pressure sensors Removing the chilled water flow sensor Chilled water flow sensorReplacing the chilled water flow sensor Chilled water system temperature sensor Chilled water temperature sensor internal components Replace the chilled water temperature sensor circuit board Heat exchanger Removing the humidifier HumidifierRemoval and replacement procedures Replacing the humidifier Removal and replacement procedures Humidistat if installed Replacing the humidistat External chilled water isolation valve ValvesRemoving the external chilled water isolation valve Replacing the external chilled water isolation valve External pressure gauge isolation valveRemoving the external pressure gauge isolation valve Replacing the external pressure gauge isolation valve Cooling system Periodic maintenancePeriodic maintenance overview Qualified personnelLeak isolation Leak detectionHumidifier if installed ECS POD Shut Down Required HP POD 20c structure Fire alarm and suppression systemEPO Functional Test Life safetyThird-party components Access controlGeneral HP POD 20c specifications SpecificationsElectrical specifications Thermal and air flow performance Rack specificationsEnvironmental specifications Water specificationsOptional features specifications Before you contact HP Contacting HPHP contact information Regulatory information Safety and NEC complianceHP POD 20c regulatory compliance Regulatory requirements for Exit signs With Council, Inc Regulatory information Branch circuit GlossarySOW Documentation feedback Index HP POD 20c structure Temperature sensors, cold aisle
Related manuals
Manual 86 pages 43.14 Kb Manual 22 pages 15.98 Kb Manual 37 pages 24.34 Kb Manual 38 pages 28.4 Kb