Sanyo CHDX07263, CHDXR07263, CHDXR09663, CHDX09663 F08 Alarm Alarm code, F12 Alarm Alarm code

Models: CHDXR07263 CHDXR09663 CHDX07263 CHDX09663

1 142
Download 142 pages 31.63 Kb
Page 123
Image 123

4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

F08 Alarm

Alarm code

F08

 

 

Alarm meaning

Outdoor air temperature sensor trouble

Alarm conditions

(1)

A/D step is 10 steps or less (short circuit).

 

(2)

A/D step is 1014 steps or more (open circuit)

Probable cause

(1)

Sensor malfunction (including connector)

 

(2)

PCB malfunction

Check

(1)

Measure the sensor resistance. Check that the sensor is operating normally.

 

(2)

Use a remote controller monitor or PC monitor to check the temperature that is recognized by

 

 

the microcomputer.

Correction

 

Example

 

Notes

 

F12 Alarm

 

 

 

 

Alarm code

F12

 

 

Alarm meaning

Compressor intake temperature sensor trouble

Alarm conditions

(1)

A/D step is 10 steps or less (short circuit).

 

(2)

A/D step is 1014 steps or more (open circuit)

Probable cause

(1)

Sensor malfunction (including connector)

 

(2)

PCB malfunction

Check

(1)

Measure the sensor resistance. Check that the sensor is operating normally.

 

(2)

Use a remote controller monitor or PC monitor to check the temperature that is recognized by

 

 

the microcomputer.

Correction

 

Example

 

Notes

 

5