Sanyo CHDX09663, CHDXR07263, CHDXR09663, CHDX07263 service manual Test Pin, Output Operation

Models: CHDXR07263 CHDXR09663 CHDX07263 CHDX09663

1 142
Download 142 pages 31.63 Kb
Page 138
Image 138

 

W-2WAY ECO-i SYSTEM

7. Test Pin

Trouble Diagnosis

 

 

When the test pin on the outdoor unit control PCB is short-circuited, each part can be operated individually.

After turning OFF the main unit power, short circuit the test pin (CN022, WHT), then turn the power back ON. Output is performed in the sequence shown in the table below, for 0.5 seconds each.

 

Output

Operation

 

Output

Operation

1

Relay RY024

4-way valve (205)

11

Relay RY012

Save valve (SAVE)

 

 

 

 

 

 

2

12

 

 

 

 

 

 

3

13

Relay RY003

Crank case 2 (CH2)

 

 

 

 

 

 

4

14

Relay RY002

Crank case 1 (CH1)

 

 

 

 

 

 

5

Relay RY005

Bypass valve (BPV)

 

 

 

 

 

 

 

 

 

6

Relay RY007

Recovery valve (ORVR)

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

9

Relay RY017

Refrigerant balance valve (RBV)

 

 

 

 

 

 

 

 

 

10

Relay RY016

Refrigerant adjustment valve (RCV)

 

 

 

 

 

 

 

 

 

5

5 - 29

Page 138
Image 138
Sanyo CHDX09663, CHDXR07263, CHDXR09663, CHDX07263 service manual Test Pin, Output Operation