4. W-2WAY ECO-i Alarm Codes
F04, F05 Alarm
|
| Alarm code | F04, F05 |
|
|
|
|
| |
|
| Alarm meaning | Compressor 1 discharge temperature sensor trouble, compressor 2 discharge temperature | |
|
|
| sensor trouble. |
|
|
| Alarm conditions | (1) Discharge temp. of 212°F or higher was detected 20 minutes or more after that compressor | |
|
|
| stopped operating. |
|
|
|
| (2) Discharge temp. of 158°F or higher was detected after all compressors had been stopped for | |
|
|
| 60 minutes or longer. |
|
|
|
| (3) A/D step is 10 steps or less (short circuit). | |
|
| Probable cause | (1) Sensor malfunction |
|
|
|
| • Sensor element malfunction |
|
|
|
| • Sensor wiring is partially disconnected, resulting in increased electrical resistance. | |
|
|
| This alarm does not occur when the wiring is cut or when the connector is not connected to | |
|
|
| the outdoor unit PCB. |
|
|
|
| (2) Crossed wiring or installation error | |
|
|
| • The discharge temperature sensor of that compressor is connected to the discharge tube | |
|
|
| of the other compressor. |
|
|
|
| • The connector for the discharge temperature sensor of the problem compressor is | |
|
|
| connected to the outdoor unit PCB connector for the other compressor. | |
|
|
| (3) Outdoor unit PCB failure |
|
|
|
| (4) The check valve on the discharge tube for that compressor is wet. | |
|
|
| (5) An air short blockage in the area around the outdoor unit has increased the outdoor unit | |
|
|
| ambient temperature, reducing the cooling effects after the compressor stops. | |
|
|
| (6) There is a cause that results in P03, P17, or P02 alarm. | |
|
|
| (7) Electrical noise |
|
|
| Check | (1) Sensor malfunction and outdoor unit PCB failure | |
|
|
| Trouble: • Constantly indicates a high temperature. | |
|
|
| • When monitoring software or other means are used for monitoring, the discharge | |
|
|
| temperature at times fluctuates suddenly and wildly. | |
|
|
| • In some cases, the precise temperature may not be known, even when monitoring | |
|
|
| software is used. |
|
|
|
| Check: • Wiggle the sensor and check whether the trouble continues. | |
|
|
| • Check whether the connector is partially disconnected from the PCB. | |
|
|
| An F04 alarm will not result if the connector is completely disconnected (circuit is | |
|
|
| open). |
|
|
|
| • If the cause is still uncertain, check the following to determine whether a sensor or | |
|
|
| ||
|
|
| PCB failure has occurred. | |
|
|
| Step 1: Connect the other compressor discharge sensor, or a discharge sensor where | |
5 |
|
| the F04 alarm has not occurred, to the connector for this compressor on the | |
|
| PCB. Measure the temperature at the same point (a location where temperature | ||
|
|
| fluctuations are small), and check whether there is a temperature difference. | |
|
|
| Difference ¡ | A PCB or sensor failure is possible. |
|
|
| No difference ¡ PCB and sensor are normal. | |
|
|
| Step 2: If an abnormality was found at Step 1, connect the problem compressor | |
|
|
| ||
|
|
| sensor to the other compressor connector on the PCB, or to the PCB | |
|
|
| connector of a device where the F04 alarm has not occurred. Measure the | |
|
|
| temperature at the same point (a location where temperature fluctuations are | |
|
|
| small), and check whether there is a temperature difference. | |
|
|
| Difference ¡ | Sensor failure. |
|
|
| No difference ¡ PCB failure. | |
|
|
| It is convenient at this time to have a discharge temperature sensor on hand. | |
|
|
| (2) Crossed wiring or installation error | |
|
|
| Trouble: Although the other compressor is operating and this compressor is stopped, the | |
|
|
| discharge temperature of the other compressor does not increase and the discharge | |
|
|
| temperature of this compressor rises. | |
|
|
| * The discharge temperature remains high immediately after the compressor stops. Wait | |
|
|
| for some time after the compressor stops and observe. | |
|
|
| Check: Check for crossed wiring and installation errors. | |
|
|
|
| Continued |
5 - 12