Sanyo CHDXR09663, CHDXR07263, CHDX09663, CHDX07263 F17 Alarm Alarm code, F31 Alarm Alarm code

Models: CHDXR07263 CHDXR09663 CHDX07263 CHDX09663

1 142
Download 142 pages 31.63 Kb
Page 125
Image 125

4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

 

 

Correction

(1)

Replace the high-pressure sensor.

 

 

 

 

Caution: Because the high-pressure sensor connection employs a Schrader-type valve, it can

 

 

 

 

be removed and replaced. However, the high-pressure sensor can be easily

 

 

 

 

damaged by high voltage; therefore use sufficient caution with regard to static

 

 

 

 

electricity.

 

 

 

(2)

Replace the PCB.

 

 

 

(3)

Correct the locations of problems in the refrigeration cycle.

 

 

 

 

• Correct locations where clogging or leakage has occurred.

 

 

 

 

• In the case of over-charging, recover refrigerant. (Adjust the amount of refrigerant).

 

 

 

 

∗ Guide for over-charging

 

 

 

 

Be sure to connect the gauge to the high-pressure outlet when checking for over-charging.

 

 

 

 

During cooling: The following does not apply when outdoor air temperature is low or when fan

 

 

 

 

speed is controlled. When both compressor 1 and compressor 2 are

 

 

 

 

operating, and the fan mode is 14 (maximum fan speed), then the high

 

 

 

 

pressure saturation temperature should be approximately 30°F above the

 

 

 

 

outdoor air temperature. If it is 10°F or more above this level, then it is

 

 

 

 

possible that over-charging may have occurred.

 

 

 

 

During heating: There is an indoor unit where refrigerant flow is poor (E1 temperature and

 

 

 

 

discharge temperature are low), and the mechanical valve of that unit is

 

 

 

 

opened to 300 pulses or more, and the E1 temperature is close to room

 

 

 

 

temperature. However be aware that this kind of data results often when

 

 

 

 

there is a height difference between indoor units. Reducing the amount of

 

 

 

 

refrigerant will improve the refrigerant flow, however reducing it too much will

 

 

 

 

increase the likelihood of alarms related to low oil level (scroll-side), the low

 

 

 

 

pressure SW, and discharge temperature. Use caution.

 

 

Example

This alarm may result when the service valve is closed or when valve leakage (particularly from

 

 

 

the mechanical valve) occurs.

 

F17 Alarm

 

 

 

 

 

 

 

 

Alarm code

F17

 

 

 

 

 

 

Alarm meaning

Low-pressure sensor trouble

 

 

Alarm conditions

(1)

Sensor short circuit

 

 

 

(2)

Sensor open circuit

 

 

Probable cause

(1)

Sensor malfunction (including connector)

 

 

 

 

(2)

PCB malfunction

 

 

Check

(1)

Measure the sensor resistance. Check that the sensor is operating normally.

5

 

 

(2)

Use a remote monitor or a PC monitor to check the temperature that is recognized

 

 

 

by the microcomputer.

 

 

Correction

 

 

 

Example

 

 

 

Notes

 

 

 

 

 

 

 

F31 Alarm

 

 

 

 

 

 

 

 

Alarm code

F31

 

 

 

 

 

 

Alarm meaning

Outdoor unit non-volatile memory (EEPROM) trouble

 

 

Alarm conditions

(1)

Non-volatile memory is not present when power initialization occurs.

 

 

 

(2)

Read values do not match after writing to non-volatile memory is complete.

 

 

Probable cause

(1)

Memory was not inserted after the PCB was replaced.

 

 

 

(2) The lifetime of the non-volatile memory has been reached.

 

 

 

(3)

Non-volatile memory is installed incorrectly (wrong direction, bent pins, etc.).

 

 

Check

(1)

Check the non-volatile memory on the PCB.

 

 

Correction

 

 

 

Example

 

 

 

Notes

 

5 - 16

Page 125
Image 125
Sanyo CHDXR09663, CHDXR07263, CHDX09663, CHDX07263 service manual F17 Alarm Alarm code, F31 Alarm Alarm code