1. Contents of Remote Controller Switch Alarm Display
5
|
|
| ON: Blinking: |
|
|
| OFF: | |||||||||||||||||
|
|
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Wired |
|
|
|
|
|
|
| Wireless | |||||||||||||
|
|
| remote |
|
|
|
|
|
|
| ||||||||||||||
|
|
| remote controller | |||||||||||||||||||||
|
|
| control | |||||||||||||||||||||
|
|
| receiver display | |||||||||||||||||||||
|
|
| display | |||||||||||||||||||||
| Possible cause of malfunction |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| Operation | Timer | Standby for heating | ||||||||||||||||
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Serial | Remote controller is detecting | Error in receiving serial communication signal. (Signal from |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
communication | error signal from indoor unit. | main indoor unit in case of group control) Outdoor system |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Operating lamp |
|
|
|
|
|
|
| ||||||||||
errors |
| address, indoor unit address, or indoor unit address | <E01> |
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
| blinking |
|
|
|
|
|
|
|
| |||||||||
| independent/main/sub unit setting has not been made. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| (Auto address is not completed.) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Error in transmitting serial communication signal. | <E02> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Indoor unit is detecting error signal from remote controller and system controller. | <<E03>> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Indoor unit is detecting error | • Error in receiving serial communication signal. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| signal from outdoor unit. | • When turning on the power supply, the number of |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| connected indoor units does not correspond to the number |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| E04 |
|
|
|
| Heating ready lamp |
|
|
|
|
| ||||||||||||
|
| set. (Except R.C. address is “0.”) |
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
| blinking |
|
|
|
|
|
|
|
|
|
|
| |||||||
|
| • Group wiring failure of indoor units in the refrigerant system |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| (occurring when remote controller is operated immediately |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| after automatic address setting) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Outdoor unit is detecting error | • Error in receiving serial communication signal. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| signal from indoor unit. | • There is an indoor unit which does not send signals when | E06 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| the power is ON. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Improper setting | • Indoor unit address setting is duplicated. | <<E08>> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| • Duplicated remote controller “main” setting. | <<E09>> |
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
| Operating lamp | ||||||||||||||||
| Improper setting | Automatic address setting start is prohibited. |
|
|
|
|
|
|
| blinking |
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| AP pin was | E12 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| setting was started. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Indoor unit communication | Error of main indoor unit in receiving serial communication | E18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| error of group control wiring. | signal from sub indoor units. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| During auto. address setting, | Number of connected indoor units is less than the number set. | E15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| number of connected units | Number of connected indoor units is more than the number set. | E16 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| does not correspond to number | No indoor unit is connected during auto. address setting. | E20 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Heating ready lamp |
|
|
|
|
| ||||||||||||||
| set. |
|
|
|
|
|
|
|
|
|
| |||||||||||||
| Main outdoor unit is detecting error signal from sub outdoor unit. | E24 | ||||||||||||||||||||||
|
|
|
|
| blinking |
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
| Duplicated outdoor unit address. | E25 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Mismatch in “No. of outdoor units” setting. | E26 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Error of sub outdoor unit in receiving serial communication | E29 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| signal from main outdoor unit. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| Improper setting | Connected indoor unit is not a multi unit. | <<L02>> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Duplication of main indoor unit address setting in group control. | <L03> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Duplicated indoor unit priority (priority indoor unit). | L05 |
|
|
|
|
|
|
| ||||||||||||||
|
|
| Operating and heating | |||||||||||||||||||||
|
| Duplicated indoor unit priority | L06 |
| ready lamps blinking |
|
| |||||||||||||||||
|
| outdoor unit. |
| simultaneously |
|
|
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Group control wiring is connected to individual control indoor unit. | L07 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Indoor unit address is not set. | L08 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Capacity code of indoor unit is not set. | <<L09>> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Mismatch of outdoor unit type. | L17 |
|
|
|
|
|
| |||||||||||||||
|
|
| Operating and heating | |||||||||||||||||||||
|
| Duplication of outdoor R.C. address setting. | L04 |
| ready lamps blinking |
| ||||||||||||||||||
|
|
|
|
| simultaneously |
|
|
|
|
|
|
|
| |||||||||||
|
| Capacity code of outdoor unit is not set. | L10 |
|
|
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| L18 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Thermistor | Indoor unit | Indoor coil temp. sensor (E1) | <<F01>> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Operating and |
|
|
|
|
|
|
|
| |||||||||||||
fault |
| Indoor coil temp. sensor (E3) | <<F03>> |
|
|
| timer lamps blinking |
| ||||||||||||||||
|
| Indoor suction air (room) temp. sensor | <<F10>> |
|
|
| alternately |
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Indoor discharge air temp. sensor | <<F11>> |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Thermistor fault | Outdoor unit | Compressor 1 (INV) discharge temp. sensor | F04 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Compressor 2 (constant speed) discharge temp. sensor | F05 |
|
|
| Operating and timer |
| ||||||||||||||||
|
|
|
|
| lamps blinking |
|
|
|
|
|
|
|
| |||||||||||
|
| Outdoor air temp. sensor | F08 |
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
| altemately |
|
|
|
|
|
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Heat exchanger 1 liquid temp. sensor | F07 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| Heat exchanger 1 gas temp. sensor | F06 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Continued