4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

H08, H27 Alarm

Alarm code

H08, H27

 

 

Alarm meaning

Trouble (open circuit) with the oil sensor (connection) at compressor 1, compressor 2

Alarm conditions

This alarm occurs when a connector connection (pins 1 and 2 for compressor 1, pins 4

 

and 5 for compressor 2) is open.

Probable cause

Disconnected connector

Check

Check that the connector is securely connected.

Correction

(1) Connect the connector.

 

(2) Correct the connection at connector pins 4 and 5.

Example

Notes

 

H31 Alarm

Alarm code

H31

 

 

 

 

Alarm meaning

HIC trouble alarm

 

Alarm conditions

This alarm occurs when the microcomputer identifies a trouble signal (indicating abnormal HIC

 

temperature or other trouble) from the HIC.

 

 

The HIC judges the current and temperature, and outputs the trouble signal. In general this

 

indicates trouble with the HIC itself.

 

Probable cause

Overcurrent in HIC circuit, and the resultant abnormal heating, caused by HIC failure

Check

Check the power wiring and connector wiring. If the wiring and connectors are normal, use a

 

tester to measure the resistance between the compressor HIC power (HIC+) and ground (HIC–).

 

If there is a short circuit, there is an HIC malfunction.

 

 

HIC -

HIC +

 

HIC PCB

 

 

Correction

If an HIC failure is found, replace the PCB.

Example

Notes

Turn OFF the power, and check the continuity of HIC+ and HIC– on the HIC PCB.

5

5 - 21

Page 130
Image 130
Sanyo CHDX09663, CHDXR07263, CHDXR09663, CHDX07263 service manual H08, H27 Alarm Alarm code, H31 Alarm Alarm code