4. W-2WAY ECO-i Alarm Codes
H11, H12 Alarm
Alarm code | H11, H12 | |
|
| |
Alarm meaning | H11: Constant speed compressor 2 overcurrent alarm | |
| H12: Constant speed compressor 2 lock current alarm | |
Alarm conditions | H11: During operation, the compressor current value exceeded 20 A for 30 seconds or longer. | |
|
| However this alarm is not detected for 4 seconds after the compressor starts. |
| H12: During operation, the compressor current value exceeded 29 A for 4 seconds or longer. | |
|
| However this alarm is not detected for 2 seconds after the compressor starts. |
Probable cause | (1) Compressor failure (locked or partially locked) | |
| (2) | CT circuit failure (including cut wiring) |
| (3) | Missing power phase |
| (4) | Low power voltage |
| (5) | PCB failure |
Check | (1) Compressor failure (partially locked) | |
|
| Trouble: Current value during operation greatly exceeds the value shown above. |
|
| Check: When the current for each phase is measured with a clamp meter or similar |
|
| instrument, check that the current value for all phases is not high. If MG was forced |
|
| ON (use caution), check that compressor noise will not occur or the compressor will |
|
| not run with a groaning sound. |
| (2) | CT circuit failure, PCB failure |
|
| Trouble: |
|
| Check: • Check for poor connector contact. |
|
| • Check the continuity of the CT circuit. |
|
| • Install a normal CT in place of this CT and check. If current is detected, then the |
|
| PCB can be jedged OK. |
|
| →CT circuit failure |
|
| • Check that current is flowing in the phase where the CT circuit is connected. |
|
| →Check voltage and current. |
| (3) | Missing power phase |
|
| Trouble: This alarm primarily occurs when the |
|
| |
|
| be true in the case of a missing phase caused by magnet SW trouble. |
|
| Check: There is the possiblility of a magnet SW failure. Therefore, check the phase voltage at |
|
| a location that is as close to the compressor as possible. |
| (4) | Low power voltage |
|
| Trouble: In most cases, this occurs when another |
|
| compressors in other units) or other dvice starts. It also occurs when the power |
|
| wiring is extremely long. |
|
| Check: Check the voltage between each of the phases. However if this troube occors when |
|
| other devices or compressors start, then an oscilloscope is required. |
| (5) | PCB failure |
|
| Trouble: |
|
| Check: Check that the current value measured with the clamp meter is not lower than the |
|
| value measured with the PC or remote controller. |
| (6) | If the cause is still unknown after checking the above, then it is possible that noise is the |
|
| cause of the trouble. It is necessary to connect a PC or other instrument. |
Correction | (1) Replace the compressor. | |
| (2) | Replace the CT circuit. |
| (3) | Repair the power circuit. |
| (4) | Adjust the |
| (5) | Replace the outdoor unit PCB. |
| (6) | Correct the trouble. |
|
| * In the case of a compressor failure, it is likely that steps must be taken to correct the cause |
|
| of the compressor failure (such as liquid |
|
| check that there is no cause which may resuit in compressor locking. |
Example | — |
|
5
5 - 17