Sanyo CHDX07263 Overview, NN About the outdoor unit maintenance remote controller, System diagram

Models: CHDXR07263 CHDXR09663 CHDX07263 CHDX09663

1 142
Download 142 pages 31.63 Kb
Page 79
Image 79

1. Overview

W-2WAY ECO-i SYSTEM Outdoor Unit Maintenance Remote Controller

OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER (RCS-TM80BG) for W-2WAY ECO-i

NNAbout the outdoor unit maintenance remote controller

The outdoor unit utilizes nonvolatile memory (EEPROM) on its PCB. This allows EEPROM data to replace the setting switches that were present on previous PCBs. The outdoor unit maintenance remote controller is used to set and change these EEPROM data.

In addition to setting and checking the outdoor unit EEPROM data, this remote controller can also be used to monitor the outdoor unit alarm history, monitor the various indoor and outdoor temperatures, and check the indoor unit connection status (number of units, operating mode, etc.).

[Service Checker Section]

NOTE

 

 

 

RCS-TM80BG

Outdoor unit maintenance remote controller does not function as an

 

ordinary remote controller. It is therefore only used for test runs and during servicing.

 

3

System diagram

Outdoor unit maintenance

 

remote controller

 

 

Special service checker wiring

Outdoor unit

 

(Servicing No.: 6231785082)

 

 

Outdoor unit

 

control PCB

Remote controller Ass’y

 

Inter-unit control wiring

Indoor

 

Indoor

unit

 

unit

 

 

 

 

 

 

 

 

 

 

Operation manual included in package.

Remote

controller

Remote

controller

LThe special service checker wiring is required in order to connect the outdoor unit maintenance remote controller to the outdoor unit PCB.

LOrdinary remote controllers or other controller are still required for the indoor units, even when the outdoor unit maintenance remote controller is connected.

3 - 2

Page 79
Image 79
Sanyo CHDX07263 Overview, NN About the outdoor unit maintenance remote controller, Service Checker Section, System diagram