4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

P26 Alarm

Alarm code

P26

 

 

Alarm meaning

Inverter compressor high-frequency overcurrent alarm

Alarm conditions

This alarm occurs when current trouble or current detection trouble occurs at an inverter

 

frequency of 80 Hz or higher after start (when trouble judgment current is detected in the

 

primary or secondary current, or when an instantaneous secondary current of 13.5 A or higher is

 

detected).

Probable cause

The detection methods are the same as for P16. However the fact that operation up to high

 

frequencies is possible does not necessarily mean that a compressor failure is the cause of the

 

trouble. Start the compressor several times. If alarm P26 occurs every time and alarm P16 does

 

not occur at all, then the possibility of a compressor failure is low.

Check

Check the power wiring and connector wiring.

Correction

It is possible to resolve this trouble by limiting the maximum frequency.

Example

Notes

P29 Alarm

 

 

 

Alarm code

P29

 

 

Alarm meaning

Inverter compressor missing phase or lock alarm

Alarm conditions

This alarm may occur at start, and occurs when missing phase or lock is detected, and when a

 

DCCT failure occurs.

Probable cause

Generally this alarm occurs when the refrigerant pressure balance is uneven at start, or when

 

inverter compressor lock occurs, there is a missing phase in the inverter compressor wiring, or a

 

DCCT failure occurs. This can be judged to be starting trouble which is not caused by HIC.

Check

Check the power wiring and connector wiring.

Correction

DCCT failure (replace PCB) or compressor failure

Example

Notes

Use a tester to measure the voltage between the DCCT output terminal on the rear of the PCB

 

and the ground. If the voltage is not within 2 – 3 V, then the DCCT has malfunctioned.

CAUTION

Currently the blinking inspection display can be displayed only on the wired remote controller and system remote controller.

Blinking inspection display (1) (Automatic backup)

5

Alarm code

(Blinking inspection display)

 

 

Alarm meaning

Automatic backup is in progress. A/C units can be operated.

 

 

 

Status: The compressor at one of the outdoor units where the outdoor unit fan is running should

 

 

be operating.

 

 

* Blinking inspection display also occurs when seizing of the compressor magnet SW

 

 

is detected. Because this may also be the case, refer to “Blinking inspection display

 

 

(compressor magnet SW seizing detection).”

 

Alarm conditions

When alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, correcting the control device

 

 

(remote controller, etc.) input engages this mode.

 

Probable cause

Because alarm P16, P22, P26, P29, Hx1, Hx2, or H31 has occurred, check the alarm history

 

 

then refer to the corresponding items.

 

Correction

Follow the instructions in the corresponding items to correct the trouble.

 

Recovery

After repairing the malfunctioning locations, reset the power for the system (all outdoor units).

 

 

Caution: Automatic backup mode will not be canceled until the power is reset.

 

Notes

Automatic backup mode is not engaged in cases of alarms other than those listed above.

 

 

Reasons: • There is no need for automatic backup if recovery is possible by correcting the

 

 

remote controller input.

 

 

• With alarms for which automatic recovery is possible (such as sensor alarms), the

 

 

presence of electrical noise may result in a new alarm. However, it is believed that

 

 

this occurs for a comparatively short time only. In these cases, a mode (automatic

 

 

backup mode) that limits operation may be engaged.

 

 

• Control is not possible when a communications system alarm has occurred.

 

 

Automatic backup mode is not engaged in order to avoid causing secondary

 

 

damage.

5 - 26

Page 135
Image 135
Sanyo CHDX07263, CHDXR07263 Blinking inspection display 1 Automatic backup, P26 Alarm Alarm code, P29 Alarm Alarm code