14. Current Protection

(1) Fan motor

Alarm

Description

P22

Occurs when the fan motor detects over current, or when the motor is locked and

 

does not turn.

W-2WAY ECO-i SYSTEM Control Functions

(2) Inverter compressor

1

Alarm

Description

P16

Occurs during ordinary operation when overcurrent (27 A) is detected.

P26

Occurs under the same conditions as P16 when the inverter compressor is operating

 

at or above 80 Hz.

P29

Occurs when missing phase or overcurrent (48 A) is detected at inverter compressor

 

start. (the alarm at frequencies below 25 Hz)

H31

Occurs when HIC detects overcurrent (75 A), or when an abnormal high temperature

 

(302°F) is reached.

 

 

The inverter current includes a primary current and secondary current. The alarm judgment utilizes both cur- rents. Generally, the secondary current is larger that the primary current.

(3)Constant-speed compressor

An alarm occurs when overcurrent or lock current is detected.

List of overcurrent and lock currents

Outdoor unit

Constant-speed

Overload

type

compressor

current [A]

96

Compressor 2

23.1

Lock current [A]

27.3

List of Alarms

Compressor

Compressor 2

No.

 

 

Detected

Overcurrent

Lock

current

current

 

Alarm display

H11

H12

(4) CT circuit detection trouble

 

 

Alarm

Description

Compressor 1

(inverter

H03

Occurs when an open CT circuit is detected in the inverter

compressor)

 

 

compressor.

Compressor 2

(constant-

H13

Occurs when a current value of 1.5 A or less is detected

speed compressor)

 

when the constant-speed compressor is operating.

If the inverter compressor operating frequency is low, the current value is also low. Therefore this alarm is detected only when the compressor is stopped.

The operating current of the constant-speed compressors is always higher than 1.5 A. Therefore, this alarm occurs as the result of an open circuit or failure.