3. Compressor Control

W-2WAY ECO-i SYSTEM Control Functions

(2)Current Protection

Inverter compressor current control is composed of primary current control and secondary current control. Current protection control for the inverter compressor is performed by self-protection in the inverter circuit, and does not increase or decrease the compressor capacity.

 

 

 

Primary current

 

Secondary current

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

-

 

75.0A or (302°F)

 

 

 

Inverter compressors stop (HIC auto. protection)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter compressors stop (When 100ms is detected,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16.0A~

 

16.5A

 

 

 

 

 

 

 

 

current protection works.)

 

 

 

14.5A~

 

 

 

 

 

Hz decrease in the inverter compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13.5A

 

 

 

 

 

 

 

 

 

 

 

 

13.5A~

 

 

 

 

 

 

 

 

 

 

 

13.0A

 

 

 

 

 

12.5A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Prohibit Hz increase in the inverter compressor

 

 

 

 

 

 

 

 

 

 

 

12.0A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Permit Hz increase in the inverter compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80Hz 90Hz

 

 

 

 

3-6-4. Roadmap Control after Trip

When restarting after the trip stop occurs, the horsepower may increase slowly depending on the trip counter value.

(1)If trip counter =1, the horsepower increases at a speed that is 1/2 of ordinary roadmap control.

(2)If trip counter =2, the horsepower increases at a speed that is 1/3 of ordinary roadmap control.

The trip counter will be cleared if no trip occurs within 10 minutes after operation starts.