4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

P16 Alarm

Alarm code

P16

 

 

Alarm meaning

Compressor 1 (INV) overcurrent alarm

Alarm conditions

This alarm occurs when current trouble or current detection trouble occur at an inverter frequency

 

of less than 80 Hz after start (when trouble judgment current is detected in the primary or

 

secondary current, or when an instantaneous secondary current of 13.5 A or higher is detected.

Probable cause

There is a strong possibility of a compressor failure.

 

An alarm occurs for current detection trouble when it is judged that no current is flowing after

 

start (DCCT is damaged). In this case, the cause is a DCCT failure.

Check

Check the power wiring and connector wiring.

Correction

It is possible to resolve this trouble by limiting the maximum frequency.

Example

Notes

P22 Alarm

 

 

 

Alarm code

P22

 

 

Alarm meaning

Fan motor trouble

Alarm conditions

Fan motor start failure, fan motor Hall IC input failure

Probable cause

Possible causes are a Hall IC input circuit failure and a fan HIC failure.

Check

Check the fan motor wiring, the Hall IC wiring, and the connector connections. If the wiring and

 

connectors are normal, then check that the capacitor of the Hall IC input circuit is securely

 

soldered on the outdoor unit control PCB. Also use a tester and measure the resistance between

 

fan HIC power (HIC+) and ground (HIC–). If there is a short circuit, there is an HIC malfunction.

(–)

(+)

 

 

 

Fan circuit on the outdoor unit control PCB

 

 

Correction

If the fan does not start, the below corrections may be effective.

 

(1)

If there is a fan HIC failure or circuit failure, replace the PCB.

 

(2)

If the fan motor is locked, replace the fan motor.

Example

 

Notes

Turn OFF the power, and check the continuity of “+” and “–” on the fan circuit PCB.

5

5 - 25

Page 134
Image 134