3. Compressor Control

W-2WAY ECO-i SYSTEM Control Functions

3-1. Compressors Mounted in the Outdoor Units [CHDX07263, CHDX09663]

 

 

 

Capacity

 

72

 

96

 

 

 

 

 

 

 

 

 

 

Installed

Compressor 1

Rotary

DC Inverter

 

DC Inverter

 

 

 

 

 

 

 

 

 

 

 

compressor

 

 

 

 

 

 

 

Compressor 2

Scroll

–––

 

5 hp

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

hp = horsepower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INV

Constant speed INV

Compressor 1

Compressor 2 Compressor 1

Type 72

Type 96

3-2. Compressor Selection Rules

In cooling mode, all inverter compressors in the outdoor units are designed to operate simultaneously. All the inverter compressors will stop at a time when the outdoor is stopped accordingly. Constant-speed compressors run in order of the shortest amount of operating time. In heating mode, the inverter compressor with the shortest amount of operating time runs at first followed by the compressors in order of the shortest amount of operating time including inverter units.

*Immediately after installation, all compressors have an operating time of zero. In this case, the compressors start in the following sequence: Inverter compressor > Constant-speed compressor 1 > Constant-speed com- pressor 2.

Examples of accumulated operating time: ODU=Outdoor Unit

Suppose the following tentative system.

 

ODU 1

ODU 2

Comp 1

100 hrs.

70 hrs.

Comp 2

150 hrs.

160 hrs.

Compressor Selection Sequence in Cooling Mode:

All the inverter compressors are firstly selected simultaneously.

 

ODU 1

ODU 2

Comp 1

1st

1st

Comp 2

3rd

4th

Compressor Selection Sequence in Heating Mode:

First, the inverter compressor with the shortest amount of operating time is selected. And then, the remained other compressors are selected and start in the order of shortest amount of operating time.

 

ODU 1

ODU 2

Comp 1

3rd

1st

Comp 2

4th

2nd

1 - 4

Page 9
Image 9
Sanyo CHDXR09663, CHDXR07263, CHDX09663, CHDX07263 Compressor Control, Compressor Selection Rules, Capacity, Type