W-2WAY ECO-i SYSTEM

2. Detailed Settings Function

Remote Controller Functions

 

 

 

 

 

 

Item code

Item

 

Setting data

No.

Description

 

 

 

 

(1B)

Forced thermostat ON time

0000

5 minutes

0001

4 minutes

 

 

 

 

 

 

 

 

–010

–20°F

 

Cooling discharge

–009

–18°F

 

–008

–16°F

 

temperature shift

 

 

 

 

 

 

 

 

 

 

 

 

0010

20°F

 

 

 

 

–010

–20°F

 

 

 

 

–009

–18°F

 

Heating discharge

–008

–16°F

 

temperature shift

 

 

 

 

 

 

 

 

 

 

 

 

0010

20°F

 

 

 

 

0001

±2°F

 

Temperature shift for

0002

±4°F

 

0003

±6°F

 

cooling/heating change in

 

 

 

 

auto heat/cool mode

 

 

 

 

 

 

 

 

 

 

 

 

0007

±14°F

 

 

 

 

0018

64°F (Lower limit at shipment)

(Upper limit)

 

 

Cooling

0019

66°F

 

 

 

 

 

 

 

 

 

 

 

(Lower limit)

 

 

 

0029

84°F

 

 

 

0030

86°F (Upper limit at shipment)

 

 

 

 

0016

60°F (Lower limit at shipment)

(Upper limit)

 

 

Heating

0017

62°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Lower limit)

Change to remote

 

0029

84°F

 

0030

86°F (Upper limit at shipment)

 

control temperature

 

 

 

 

 

0018

64°F (Lower limit at shipment)

 

setting range

 

 

 

 

 

(Upper limit)

Drying

0019

66°F

 

 

 

 

 

 

 

 

 

 

 

 

 

(Lower limit)

 

 

 

0029

84°F

 

 

 

0030

86°F (Upper limit at shipment)

 

 

 

 

 

 

 

heat/cool

0017

62°F (Lower limit at shipment)

(Upper limit)

 

 

0018

64°F

 

 

 

 

 

Auto

 

 

 

 

 

 

 

(Lower limit)

 

 

0026

78°F

 

 

0027

80°F (Upper limit at shipment)

 

Humidifier operation

0000

Normal

 

0001

Ignore heat exchanger temperature conditions.

 

 

 

 

 

 

 

 

0000

Filter input (differential pressure switch input)

 

Filter (CN70) input

0001

Alarm input (for trouble input about air cleaner or similar device)

 

switching

0002

Humidifier input (Operates linked with drain pump when humidifier is

 

 

 

 

ON.)

 

 

 

 

 

 

Indoor unit electronic

0000

Present (Setting at shipment)

 

control valve

0002

None

 

 

 

 

0000

Normal (Used as optional relay PCB or JEMA standard HA terminal.)

 

T10 terminal switching

0001

Used for OFF reminder

 

 

 

 

0002

Fire prevention input

4 - 6