Sanyo CHDXR07263, CHDXR09663, CHDX09663, CHDX07263 2WAY ECO-i Alarm Codes, Alarm code Alarm meaning

Models: CHDXR07263 CHDXR09663 CHDX07263 CHDX09663

1 142
Download 142 pages 31.63 Kb
Page 116
Image 116

4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

With type 96, the INV compressor is compressor 1, and the constant-speed compressor is compressor 2.

With type 72, the INV compressor is compressor 1.

Alarm code

Alarm meaning

Page

 

 

 

 

 

 

 

E06

Outdoor unit failed to receive serial communication signals from indoor unit.

5-9

 

 

E12

Automatic address setting start is prohibited.

5-9

 

 

E15

Automatic address setting alarm (too few units)

5-9

 

 

E16

Automatic address setting alarm (too many units)

5-10

 

 

E20

No indoor units at automatic address setting.

5-10

 

 

E24

Outdoor unit (INV) failed to receive communications from another outdoor

5-10

 

 

 

unit (constant-speed).

 

 

 

E25

Outdoor unit address setting failure (duplication)

5-11

 

 

E26

Mismatch in outdoor unit quantity

5-11

 

 

E29

Outdoor unit failed to receive communication from outdoor unit (main)

5-11

 

 

 

 

 

 

 

F04

Compressor 1 discharge temperature sensor trouble

5-12

 

 

F05

Compressor 2 discharge temperature sensor trouble

5-12

 

 

F06

Gas temperature sensor trouble at outdoor heat exchanger 1 (In)

5-13

 

 

F07

Liquid temperature sensor trouble at outdoor heat exchanger 1 (Out)

5-13

 

 

F08

Outdoor air temperature sensor trouble

5-14

 

 

F12

Compressor intake temperature sensor trouble

5-14

 

 

F16

High-pressure sensor trouble

5-15

 

 

F17

Low-pressure sensor trouble

5-16

 

 

F23

Gas temperature sensor trouble at outdoor heat exchanger 2 (In)

5-13

 

 

F24

Liquid temperature sensor trouble at outdoor heat exchanger 2 (Out)

5-13

 

 

F31

Outdoor unit non-volatile memory (EEPROM) trouble

5-16

 

 

 

 

 

 

 

H11

Constant speed compressor 2 overcurrent alarm

5-17

 

 

H12

Constant speed compressor 2 lock current alarm

5-17

 

 

H03

Compressor 1 CT sensor disconnected or short-circuit

5-18

 

 

H06

Low-pressure switch activated

5-19

 

 

H07

No-oil alarm

5-20

 

5

H08

Compressor 1 oil detection sensor (connection) trouble

5-21

 

 

 

H13

Compressor 2 CT sensor disconnected or short-circuit

5-18

 

 

H15

Compressor 2 discharge temperature sensor disconnected

5-18

 

 

H27

Compressor 2 oil detection sensor (connection) trouble

5-21

 

 

H31

HIC trouble alarm

5-21

 

 

 

 

 

 

 

L04

Outdoor system address duplication

5-22

 

 

L10

Outdoor unit capacity not set

5-22

 

 

L17

Outdoor unit model mismatch

5-22

 

 

L18

4-way valve operation failure

5-22

 

 

5 - 7

Page 116
Image 116
Sanyo CHDXR07263, CHDXR09663, CHDX09663, CHDX07263 service manual 2WAY ECO-i Alarm Codes, Alarm code Alarm meaning