4. W-2WAY ECO-i Alarm Codes

W-2WAY ECO-i SYSTEM Trouble Diagnosis

 

L04 Alarm

 

 

 

 

 

 

 

Alarm code

L04

 

 

 

 

 

 

Alarm meaning

Outdoor system address duplication

 

 

Alarm conditions

Communication by inter-unit control wiring was received that contained the same address as that

 

 

 

unit 5 times or more within 3 minutes.

 

 

Probable cause

Incorrect outdoor system address settings

 

 

Check

Check the system address settings again.

 

 

Correction

Correct the system address settings.

 

 

Example

 

 

Notes

Recovery from this alarm occurs automatically (when communication that contains the same

 

 

 

address as that unit is not received for 3 minutes after detection).

 

L10 Alarm

 

 

 

 

 

 

 

Alarm code

L10

 

 

 

 

 

 

Alarm meaning

Outdoor unit capacity not set

 

 

Alarm conditions

The outdoor unit capacity has not been set, or the setting is not allowed by the system.

 

 

Probable cause

This alarm occurs because the capacity has not been set.

 

 

Check

Connect the outdoor unit maintenance remote controller. On the outdoor unit EEPROM detailed

 

 

 

setting mode screen, check the value for the outdoor unit capacity (item code 81). Check that it is

 

 

 

not set to “0” or to a capacity that is not allowed.

 

 

Correction

If item code 81 is incorrect, use the outdoor unit maintenance remote controller and set it

 

 

 

correctly.

 

 

 

* After changing the setting, be sure to reset both the indoor and outdoor power.

 

 

Example

 

 

Notes

The outdoor unit maintenance remote controller is required in order to set the capacity in the

 

 

 

outdoor unit EEPROM.

 

L17 Alarm

 

 

 

 

 

 

 

Alarm code

L17

 

 

 

 

 

 

Alarm meaning

Outdoor unit model mismatch

 

 

Alarm conditions

This alarm occurs when a unit other than a R410A refrigerant model is connected.

 

 

Probable cause

(1) A unit that uses R407C refrigerant, or a R22 model unit, was connected by mistake.

 

 

 

 

(2) The connected unit is correct, however the refrigerant type setting in the outdoor unit

 

 

 

EEPROM (item code 80) is incorrect.

5

 

Check

(1) Check the refrigerant type at the connected unit.

 

 

(2) Use the outdoor unit maintenance remote controller and check the item code 80 refrigerant

 

 

 

type. If the setting is incorrect, change it to R410A.

 

 

Correction

 

 

Example

 

 

 

 

 

 

Notes

The outdoor unit maintenance remote controller is required in order to set the refrigerant type in

 

 

 

the outdoor unit EEPROM.

 

L18 Alarm

 

 

 

 

 

 

 

Alarm code

L18

 

 

 

 

 

 

Alarm meaning

4-way valve operation failure

 

 

Alarm conditions

During heating operation (Comp. ON), the highest detected temperature at an outdoor unit

 

 

 

heat exchanger (EXG 1, EXG 2, EXL 1, or EXL 2) was 40°F or more above the outdoor air

 

 

 

temperature (Air Temp.) continuously for 5 minutes or longer, or the detected suction temperature

 

 

 

(SCT) was 40°F or more above the outdoor air temperature continuously for 5 minutes or longer.

 

 

Probable cause

(1) The 4-way valve connector (20S CN060) has become disconnected from the control PCB.

 

 

 

(2) The 4-way valve circuit is locked (malfunctioning).

 

 

Check

(1) Check the 4-way valve connector (20S CN060).

 

 

 

(2) If the connector is normal, check the 4-way valve wiring and the PCB circuit.

 

 

Correction

If the connector is normal, correct or replace the problem locations.

 

 

Example

 

 

Notes

5 - 22