Sanyo CHDX09663, CHDXR07263, CHDXR09663, CHDX07263 Cooling or dry Heating Fan Fan not changed

Models: CHDXR07263 CHDXR09663 CHDX07263 CHDX09663

1 142
Download 142 pages 31.63 Kb
Page 102
Image 102

2. Detailed Settings Function

W-2WAY ECO-i SYSTEM Remote Controller Functions

When the operating mode at the priority remote controller is changed, the operating modes of other remote controllers change as shown below.

Mode change at priority remote controller

Operating modes at other remote controllers

Current mode

New mode

Current mode

New mode

 

 

 

 

Cooling or dry

Heating

Cooling or dry

Heating

Fan

Fan (not changed)

 

 

 

 

 

 

Heating

Cooling

Heating

Cooling

Fan

Fan (not changed)

 

 

 

 

 

 

Cooling

Dry

Cooling

Cooling (not changed)

Dry

Dry (not changed)

 

 

 

 

 

 

Heating

Dry

Heating

Cooling

Fan

Fan (not changed)

 

 

 

 

 

 

 

 

Cooling

Cooling (not changed)

Cooling or dry

Fan

Dry

Dry (not changed)

 

 

Fan

Fan (not changed)

 

 

 

 

Heating

Fan

Heating

Heating (not changed)

Fan

Fan (not changed)

 

 

 

 

 

 

Item code

Item

Description

 

 

 

 

 

 

 

05

Fan speed setting when

Changes the fan speed setting when the heating thermostat is OFF.

 

 

heating thermostat is OFF

 

 

 

 

 

 

 

 

 

 

 

06

Heating intake temperature

Shifts the intake temperature during heating.

 

 

 

shift

Can be set when the body thermostat is used.

 

 

 

 

 

 

 

 

 

 

 

 

Set when cost distribution is performed using an AMY central control system

 

4

07

Electric heater installation

or similar system, and when an optional electric heater is installed.

 

 

 

 

 

(This is unrelated to control of the electric heater.)

 

 

 

 

 

 

 

 

 

Normally humidifying does not occur when the thermostat is OFF during

 

 

 

Humidifying when heater

heating operation. However, this setting can be changed in order to increase

 

 

08

the amount of humidifying.

 

 

thermostat is OFF

 

 

 

Caution: In order to avoid water leakage and damage to the fan, do not use

 

 

 

 

 

 

 

 

this setting unless a vaporizing humidifier is used.

 

 

 

 

 

 

 

 

Permit/prohibit automatic

This setting can be used to prevent the automatic heating/cooling display on

 

 

0D

the remote control if the unit configuration permits automatic heating/cooling

 

 

heating/cooling

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

 

0F

Cooling-only

This setting allows a heat pump indoor unit to be operated as a cooling-only

 

 

unit.

 

 

 

 

 

 

 

 

 

 

 

4 - 11