10. Indoor Unit Control of the Electronic Control Valve

W-2WAY ECO-i SYSTEM Control Functions

10-1. Normal Control

(1) Cooling operation

 

 

 

Position of electronic control valve

 

 

 

Outdoor unit operating

Outdoor unit

 

 

 

stopped

 

 

 

 

 

Stopped

20

20

 

 

Fan

20

20

 

 

Thermostat

20

20

 

 

OFF

Cooling

 

 

 

 

Thermostat

Performs SH control in the range of 55 – 480

 

 

 

 

ON

pulses.

 

1

*The SH target value is controlled so that the E3 - E1 becomes between 2°F to 6°F, depending on the operating conditions.

However, a decline in the required level may cause the SH target value to increase. Be aware that in this case, the electronic control valve closes slightly. This can be easily identified incorrectly as insufficient gas.

(2)Heating operation

(A)Except Type D

 

 

 

Position of electronic control valve

 

 

 

 

Outdoor unit operating

Outdoor unit

 

 

 

stopped

 

 

 

 

 

Stopped

Liquid refrigerant is gradually returned to the outdoor unit

85

 

at pulses ranging from 55 to 80.

 

 

 

 

 

 

Fan

Liquid refrigerant is gradually returned to the outdoor unit

85

 

 

at pulses ranging from 55 to 80.

 

 

 

 

 

 

Thermostat

Liquid refrigerant is gradually returned to the outdoor unit

85

 

 

OFF

at pulses ranging from 55 to 80.

Heating

 

 

 

Thermostat

Performs SC distribution control within the range of 55–

 

 

 

 

ON

480 pulses.

 

 

 

*The SC target value is controlled so that the high pressure saturated temp. - E1 becomes between 10°F to 40°F , depending on the operating conditions.

(B) Type D

 

 

Position of electronic control valve

 

 

Outdoor unit operating

 

 

 

Stopped

20

 

Fan

20

 

Thermostat

20

 

OFF

Heating

 

Thermostat

Performs SC distribution control within the range of 55 –

 

 

ON

480 pulses.

Outdoor unit

stopped

20

20

20

*The SC target value is controlled so that the high pressure saturated temp. - E1 becomes between 10°F to 40°F, depending on the operating conditions.

However, if installation is combined with except Type D, the high pressure saturated temp. - E1 may be controlled between 10°F to 80°F.

1 - 21

Page 26
Image 26
Sanyo CHDX09663 Indoor Unit Control of the Electronic Control Valve, Normal Control, Cooling operation, Heating operation