Sterling 350-2100 CFM installation manual Process Blower Failure Alarm

Page 21

;The alarm mode and value are factory-set to track 25°F below the process setpoint. The alarm value is a deviation above the process setpoint.

;This alarm is informational. If the alarm light stays lit for an extended period of time, check for blown fuses or possible burnt-out heaters.

;When the temperature at the thermocouple returns within limits, the alarm clears automatically.

;This alarm is delayed on initial start-up to avoid nuisance alarms.

;The alarm range may be altered. See Section 5-5.

PROCESS BLOWER FAILURE ALARM

;This indicator lights if pressure switch 2PS detects a loss of process blower air pressure.

;All heaters are shut-off until the alarm is cleared.

REGEN BLOWER FAILURE ALARM

;This indicator lights if pressure switch 1PS detects a loss of regeneration blower air pressure.

;All heaters are shut-off until the alarm is cleared.

HIGH REGEN AIR TEMPERATURE ALARM

This indicator lights when the thermocouple below the regeneration heater assembly senses an abnormally high temperature.

Note: Do not adjust the factory setpoint of 3CNTL, the 116 DIN panel-mounted temperature controller inside the enclosure.

The regeneration heaters are shut-off until the temperature falls below the alarm point. The regeneration blower will continue to run and cool the heaters and desiccant bed.

The alarm light will clear automatically when the temperature drops below the alarm point, and the heaters will re-energize automatically.

LOW REGEN AIR TEMPERATURE

This indicator lights if the regeneration bleed temperature has not reached the factory setpoint of 150°F within 30 minutes of the start of bed regeneration.

The panel meter (2CNTL) and the PLC monitor the regeneration bleed temperature. This alarm is informational, and does not affect the regeneration process.

This alarm may indicate a very wet desiccant bed or, if the light does not go off within an hour, malfunctioning or burnt out regeneration heaters. For more details on the regeneration monitoring system, see Section 5-7.

CRITICAL ALARM SILENCE

Press this button to turn off the audible alarm and flashing beacon when a critical, operation stopping alarm occurs.

The alarm will repeat every five minutes unless the problem causing the alarm has been resolved.

350-2100 cfm Dryers

Chapter 4: Control Panel

21 of 58

Image 21
Contents Large Dehumidifying Dryers SDA Series 350 2100 CFMWrite Down Your Serial Numbers Here For Future Reference Shipping Info Table of Contents Maintenance Safety How to Use This ManualSafety Symbols Used in this Manual Dryer Safety Tags Safety Tag InformationWear Safety Glasses and Work Gloves Responsibility General ResponsibilityOperator Responsibility Remember Maintenance ResponsibilityReporting a Safety Defect Optional Features Typical Features and ComponentsFunctional Description Models Covered in This ManualWhat is Desiccant? Closed Loop Drying SystemProcess/Regeneration Cycle Cfm Dryers Functional Description TOP View Left Side View Work Rules InstallationElectrical Connections Check For Proper Blower RotationDrying Hopper Air Trap Aftercooler Cooling Water ConnectionTypical Control Panel Control Panel Control Panel Indicator LightsProcess Blower Failure Alarm Valve Position Error Switches and MetersPLC Control Process Air Temperature ControllerProcess Air Temperature Controller Process Value Numeric LED Temperature Controller LED IndicatorsOptional Communications Protocols Temperature Controller Keys See in SectionStartup, Shutdown & Operation Pre-Startup ChecksStartup Setting the High and Low Temperature Alarms Setting the Process Air TemperatureTo Change the Process Air High Temperature Alarm Setting ShutdownTemperature Controller Internal Switches Temperature Controller Autotune ProcedureTemperature Controller Anti-Tamper Lockout Switch Enabling the Lockout FeatureSetting the Dewpoint Extend Shift Point Changing the Display from Fahrenheit to CentigradeTo Change the Dewpoint Shift Point LL Setpoint Low Regeneration Alarm Setpoint 130F Regeneration Monitoring System Signal ProcessorSetpoint Regeneration Blower Shutdown Temp 160F HH Setpoint Heater Cut Off Temp 300FSeven Day Timer Optional Auxiliary Process Safety System OptionalSetting the start up time Setting the Current Day of the Week, Hour and MinuteSetting the stop time Put the timer into Run modeSet the days of the week for automatic operation Maintenance Filter Cleaning/ReplacementServicing the Process Air Filters Models Servicing the Process Air Filters Models 850 through Filter Cleaning/ReplacementDirty Filter Alarm Calibration To Clean the Regeneration FilterServicing the Regeneration Filter Dewpoint Control System Service Symptoms of Worn Out DesiccantTo check the dewpoint sensor and dewpoint control board First AID Desiccant Replacement ProcedureDesiccant Amounts Required Process Heater Replacement ProcedureSpots and lead to premature heater failure Regeneration Heater Replacement ProcedureRestoring a Temperature Controller to the Factory Setup Switch To select a setting 10F Process Temperature Control Error Messages Regeneration Monitor Signal Processor Error Messages Moving Between Levels Regeneration Monitor Advanced ProgrammingSetpoints HysteresisInput Shift Security Protection Sensor Input Type Scale IndicationDisplay Refresh Cycle Problem Possible Cause Corrective Action TroubleshootingProblem Possible Cause Corrective Action Problem Possible Cause Corrective Action Appendix Warranty ReturnsReturned Material Policy Credit ReturnsCfm Dryers Appendix Preventive Maintenance Checklist Dehumidifying Dryers Technical Assistance Service DepartmentParts Department Sales Department

350-2100 CFM specifications

The Sterling 350-2100 CFM is a high-performance ventilation system that effectively addresses the needs of various industrial and commercial applications. This versatile unit is designed to provide optimal air movement, offering flow rates spanning from 350 to 2100 cubic feet per minute (CFM). Its capabilities make it ideal for environments that require robust air circulation, such as warehouses, factories, and workshops.

One of the standout features of the Sterling 350-2100 CFM is its energy-efficient motor. The unit is equipped with a reliable and durable drive system, allowing for lower energy consumption while maintaining high performance. This not only reduces operational costs but also contributes to a greener footprint, making it an attractive option for businesses looking to enhance sustainability.

The ventilation system is designed with an advanced aerodynamic blade technology that maximizes airflow and minimizes noise levels. This allows for a more comfortable working environment by reducing the disruption typically associated with high-velocity air movement. Additionally, the integrated sound-dampening features ensure that it operates quietly, making it suitable for noise-sensitive areas.

The Sterling 350-2100 CFM also incorporates a user-friendly control panel, which allows for easy adjustments and monitoring of airflow levels. This system can be tailored to specific ventilation requirements, ensuring optimal performance in diverse settings. For added convenience, some models come with remote control capabilities, allowing operators to manage airflow from a distance.

Durability is a key characteristic of the Sterling 350-2100 CFM. The unit is constructed with high-grade materials that resist wear and tear, providing long-lasting service even in challenging environments. The weather-resistant design further enhances its suitability for outdoor applications.

Moreover, the system can be easily integrated with existing HVAC setups, providing flexibility and compatibility without extensive modifications. Maintenance is also simplified, with easily accessible components for routine checks and servicing.

In summary, the Sterling 350-2100 CFM ventilation system stands out for its combination of energy efficiency, quiet operation, and robust design. With its innovative technologies and user-friendly features, it meets the demands of modern industrial and commercial spaces while ensuring optimal air quality and comfort for occupants.