Sterling 350-2100 CFM installation manual Problem Possible Cause Corrective Action

Page 53

PROBLEM

POSSIBLE CAUSE

CORRECTIVE ACTION

Loss or reduction of

A. Process heaters are

A. Check for open or

process air temperature.

faulty.

shorted heaters. Replace if

 

 

required. Check the fuses.

 

B. Solid-state temperature

B. Replace.

 

controller faulty.

 

 

C. Process temperature

C. Make sure that plant

 

was adjusted in error by

personnel are aware of the

 

plant personnel.

proper temperature

 

 

setpoint. A sign posted next

 

 

to the control would be

 

 

helpful.

 

 

 

Loss or reduction in drying

A. Process heaters are

A. Replace.

capacity.

faulty.

 

 

B. Desiccant beds are

B. Replace desiccant.

 

contaminated.

 

 

C. Material being dried

C. Drying systems are

 

differs from material

designed for the material

 

specified at the time of

which was originally

 

purchase.

specified. Different

 

 

materials may need a

 

 

longer residence time or

 

 

different drying

 

 

temperature.

 

D. Break in flex hose

D. Inspect for air leaks;

 

to/from drying hopper.

replace if necessary.

 

E. Airflow valves sticking

E. Check for proper

 

or failing to shift.

operation of linear valve

 

 

actuator. Check fusing.

 

 

Repair or replace if

 

 

necessary.

 

F. Blower fins filled with

F. Remove blower

 

dust or contaminants.

sideplate, clean baffles,

 

 

replace. Replace filter

 

 

elements.

350-2100 cfm Dryers

Chapter 7: Troubleshooting

53 of 58

Image 53
Contents Large Dehumidifying Dryers SDA Series 350 2100 CFMWrite Down Your Serial Numbers Here For Future Reference Shipping Info Table of Contents Maintenance Safety Symbols Used in this Manual SafetyHow to Use This Manual Dryer Safety Tags Safety Tag InformationWear Safety Glasses and Work Gloves Operator Responsibility ResponsibilityGeneral Responsibility Remember Maintenance ResponsibilityReporting a Safety Defect Optional Features Typical Features and ComponentsFunctional Description Models Covered in This ManualProcess/Regeneration Cycle What is Desiccant?Closed Loop Drying System Cfm Dryers Functional Description TOP View Left Side View Work Rules InstallationElectrical Connections Check For Proper Blower RotationDrying Hopper Air Trap Aftercooler Cooling Water ConnectionTypical Control Panel Control Panel Control Panel Indicator LightsProcess Blower Failure Alarm Valve Position Error Switches and MetersPLC Control Process Air Temperature ControllerProcess Air Temperature Controller Process Value Numeric LED Temperature Controller LED IndicatorsOptional Communications Protocols Temperature Controller Keys See in SectionStartup Startup, Shutdown & OperationPre-Startup Checks Setting the High and Low Temperature Alarms Setting the Process Air TemperatureTo Change the Process Air High Temperature Alarm Setting ShutdownTemperature Controller Internal Switches Temperature Controller Autotune ProcedureTemperature Controller Anti-Tamper Lockout Switch Enabling the Lockout FeatureTo Change the Dewpoint Shift Point Setting the Dewpoint Extend Shift PointChanging the Display from Fahrenheit to Centigrade LL Setpoint Low Regeneration Alarm Setpoint 130F Regeneration Monitoring System Signal ProcessorSetpoint Regeneration Blower Shutdown Temp 160F HH Setpoint Heater Cut Off Temp 300FSeven Day Timer Optional Auxiliary Process Safety System OptionalSetting the start up time Setting the Current Day of the Week, Hour and MinuteSet the days of the week for automatic operation Setting the stop timePut the timer into Run mode Servicing the Process Air Filters Models MaintenanceFilter Cleaning/Replacement Servicing the Process Air Filters Models 850 through Filter Cleaning/ReplacementServicing the Regeneration Filter Dirty Filter Alarm CalibrationTo Clean the Regeneration Filter To check the dewpoint sensor and dewpoint control board Dewpoint Control System ServiceSymptoms of Worn Out Desiccant First AID Desiccant Replacement ProcedureDesiccant Amounts Required Process Heater Replacement ProcedureSpots and lead to premature heater failure Regeneration Heater Replacement ProcedureRestoring a Temperature Controller to the Factory Setup Switch To select a setting 10F Process Temperature Control Error Messages Regeneration Monitor Signal Processor Error Messages Moving Between Levels Regeneration Monitor Advanced ProgrammingInput Shift SetpointsHysteresis Security Protection Display Refresh Cycle Sensor Input TypeScale Indication Problem Possible Cause Corrective Action TroubleshootingProblem Possible Cause Corrective Action Problem Possible Cause Corrective Action Appendix Warranty ReturnsReturned Material Policy Credit ReturnsCfm Dryers Appendix Preventive Maintenance Checklist Dehumidifying Dryers Technical Assistance Service DepartmentParts Department Sales Department

350-2100 CFM specifications

The Sterling 350-2100 CFM is a high-performance ventilation system that effectively addresses the needs of various industrial and commercial applications. This versatile unit is designed to provide optimal air movement, offering flow rates spanning from 350 to 2100 cubic feet per minute (CFM). Its capabilities make it ideal for environments that require robust air circulation, such as warehouses, factories, and workshops.

One of the standout features of the Sterling 350-2100 CFM is its energy-efficient motor. The unit is equipped with a reliable and durable drive system, allowing for lower energy consumption while maintaining high performance. This not only reduces operational costs but also contributes to a greener footprint, making it an attractive option for businesses looking to enhance sustainability.

The ventilation system is designed with an advanced aerodynamic blade technology that maximizes airflow and minimizes noise levels. This allows for a more comfortable working environment by reducing the disruption typically associated with high-velocity air movement. Additionally, the integrated sound-dampening features ensure that it operates quietly, making it suitable for noise-sensitive areas.

The Sterling 350-2100 CFM also incorporates a user-friendly control panel, which allows for easy adjustments and monitoring of airflow levels. This system can be tailored to specific ventilation requirements, ensuring optimal performance in diverse settings. For added convenience, some models come with remote control capabilities, allowing operators to manage airflow from a distance.

Durability is a key characteristic of the Sterling 350-2100 CFM. The unit is constructed with high-grade materials that resist wear and tear, providing long-lasting service even in challenging environments. The weather-resistant design further enhances its suitability for outdoor applications.

Moreover, the system can be easily integrated with existing HVAC setups, providing flexibility and compatibility without extensive modifications. Maintenance is also simplified, with easily accessible components for routine checks and servicing.

In summary, the Sterling 350-2100 CFM ventilation system stands out for its combination of energy efficiency, quiet operation, and robust design. With its innovative technologies and user-friendly features, it meets the demands of modern industrial and commercial spaces while ensuring optimal air quality and comfort for occupants.