Thermo Products OH5-85DXE Venting Rotation of Front Flue Elbow, Trim Collar, Unit DIA. Hole

Page 5

All installations and services must be performed by qualified service personnel.

A. VENTING:

NOTE: On the OH5-85DXE*** it is possible to rotate the flue elbow (which is factory installed for vertical discharge) 90° counterclockwise from the vertical position to adapt to various venting systems.

cCAUTION MUST BE TAKEN NOT TO EXCEED 90° ROTATION (OF THE FLUE ELBOW) COUNTERCLOCKWISE OR RIGHT FROM THE VERTICAL POSITION.

ROTATION OF FRONT FLUE ELBOW

When an installation requires that the flue exit out the left hand side casing on a front flue unit, remove screw securing the 90 deg. elbow and rotate it 90° counterclockwise. Then, by following the dimensions listed below, locate the center point for the exit of the flue. Once the center has been located, use a scribe to mark the hole size. Cut hole and extend flue through side casing.

A trim collar may be ordered from Thermo Products to hide the gap around the flue pipe. This trim collar, however, is not required for operation. Trim collar/gasket part numbers(s) 14121 / 330073.

TABLE 1: Suggested size and position of flue pipe opening on left hand side of casing.

 

 

 

 

 

TRIM COLLAR/

UNIT

DIA. HOLE

“X” DIM.

“Y” DIM.

FLUE DIA.

GASKET PART #

OH5-85DXE

6-1/2”

4-3/4”

33-1/16”

6”

14131/330005

*FRONT FLUE MODELS ONLY

“X” DIMENSION IS MEASURED FROM SEPARATOR PANEL.

“Y” DIMENSION IS MEASURED FROM THE BLOWER PAN ON “H” MODELS AND FROM THE BASE ON “L” AND “C” MODELS.

Fig 1: Recommended location for drilling hole to connect vent pipe to the furnace through the left hand side casing.

NOTE: ROTATION OF FLUE PIPE IS ONLY ALLOWED FOR LEFT HAND SIDE VENTING APPLICATIONS.

The OH5-85DXE*** may be vented through a standard correctly sized chimney.

B. DRAFT REGULATORS:

A draft regulator is supplied with the furnace and should be installed according to the regulator manufacturers recommendations. With the burner operating, use a draft gauge to adjust the regulator to the proper setting. (refer to the instructions enclosed with draft regulator to adjust to the proper setting). When the burner air supply and draft are properly adjusted, the overfire draft should be a negative (-).01" to (-).02" WC 1, as measured at the 5/16" overfire air tap (See Fig. 8). This tap is provided in the upper burner mounting plate. To measure the flue draft, punch a small hole in the vent connector pipe as close to the furnace as possible and always before the draft regulator.

2

Image 5
Contents OH5-85DXE OIL Fired FurnaceSafety Section Table of Contents Section Beginning Combustible Material II. General Instructions Read Before Start of InstallationNON-COMBUSTIBLE Material From Rear FLUE/VENTTrim Collar Venting Rotation of Front Flue ElbowUnit DIA. Hole Flue DIA Gasket OH5-85DXEFilters Mounted External to Furnace Duct WORK/AIR ConditioningCutaway view of fan section of a typical highboy furnace Riello Mounting Plate Burner InstallationLimit Position and Location Top view Burner insertion illustration Heating Nozzle Size Input Rate EffectiveBTU/HR Capacity High Fire LOW FireHeat Exchanger Cleaning Instructions Starting the Burner III. Users Information SectionInspection Areas Location of the air filter on the typical highboy furnace Filter Cleaning and LocationCustomer APPENDIX-A Replacement Parts List APPENDIX-B Wiring Diagram