Roberts Gorden CTU 22 TO 115 service manual AIR Supply

Page 18

COMBAT® CTU UNIT HEATERS INSTALLATION OPERATION AND SERVICE MANUAL

SECTION 7: AIR SUPPLY

7.1 Room Sealed Installation

When installed as a room sealed heater, the air for combustion is drawn in from outside the building. It is important to ensure that there is adequate ventilation to provide air for the distribution fan/s.

7.2 Open Flued Installation

It is important to ensure that there is adequate air supply at all times for both combustion and heating requirements in accordance with local and national codes. When installed in this mode, the air supply to the heater must also be fitted with a low resistance terminal to prevent the ingress of debris. See Page 11, Figure 5.

7.2.1 Heaters Installed Within the Heated Space

Where the volume of the heated space is greater than 4.7 m3 per kilowatt of total rated heat input and the air change rate is at least 0.5/h, additional high and low level ventilation will not be required.

For a building having an air change rate less than 0.5/h, ventilation will be necessary in accordance with local and national codes. Ventilation direct to outside must be provided as follows:

Heaters up to 70 kW heat input: 5.0 cm2 per kW of rated heat input

Heaters above 70 kW heat input: 350 cm2 + 2.5 cm2 per kW of rated heat input above 70 kW

7.3 Building Ventilation

Where ventilation is required, air must be taken from an outside point where it is not likely to be contaminated or obstructed.

Where natural ventilation is used, suitable ventilation with outside air at low level must be provided in accordance with Section 7.2.1 and local and national codes.

Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the CTU heater.

7.4 Isolated Equipment Rooms

Ventilation must prevent the isolated equipment room temperature from exceeding 32° C as well as prevent any negative air pressure within the room. See Page 12, Figure 7. Any isolated equipment room containing air heaters will require permanent air vents direct to outside air in compliance with local codes.

Where natural ventilation is used, suitable permanent openings at low and high level, communicating directly with the outside air, must be provided.

Where mechanical ventilation is used, extract rate must be 5% - 10% less than the inlet rate. The mechanical ventilation must be interlocked with the burner on the CTU heater.

Figure 7: Heaters Installed in Isolated Equipment Rooms

Duct Distribution

System or

Discharge to Heated Space

 

High Level

Manifold

Ventilation

 

Air Intake

Flue

 

Return Air Duct

from Heated

Space or Fresh

Air from Outside

Max Temperature 32° C

Room Air Pressure Must Not be Negative.

Wall

Low Level

Ventilation

Outside

Wall

12

Image 18
Contents Follow the gas supplier’s Instructions Immediately call your local gasSupplier after leaving the building Supplier, call the Fire DepartmentPage Roberts-Gordon, LLC Page Table of Figures Page Product Approval Clearances to Combustibles Heater SafetyInstaller Responsibility Corrosive ChemicalsVentilation Minimum Required Installation ClearancesCritical Considerations 3.1 Basic Information Gas SupplyInstallation Clearances and Clearances to Combustibles Top View Specifications 4.1 CtuaDimension Data Ctua All Models End View Rear ViewDimension Data CTUB, Ctuc and Ctud CTUB, Ctuc and CtudGeneral Technical Data Table Gas rates corrected to standard conditions 1013.25 mbar 15 C Heater Installation 5.1 General HandlingFlue Installation 6.1 Flue Installation Type B22 ApplianceAir Intake Terminal Cover Vertical and Horizontal Flue Termination Type B22 Appliance AIR Supply Optional Heater Configurations Distribution Duct Work for CTUB, Ctuc and Ctud HeatersCtud Heaters Option a GAS PipingConnections Option BWiring and Electrical Information Ctua Wiring Diagram Models 50 HzSite Wiring Site Wiring CTUB/C Wiring Diagram ModelsIgnition Module 230 V 1 Ø 50 HzRUN Ctud Wiring Diagram Models For external fan wiringSite Wiring and Electrical Information Electrical Checks CommissioningLouvres Mechanical ChecksAutomatic Burner Control Box Sequence End ViewCombustion Testing Check Gas RateTurning Off the Heater External Controls Complete the CommissioningInstruction to the User Common User Controls Thermostat Limit Thermodisc Burner Lockout Reset ButtonHeater Operation Lighting Instructions To Turn On HeaterSimple Fault Finding Simple Fault Finding Burner FaultsTo Turn the Heater Off Heat Exchanger Maintenance Burner Maintenance13.3 Fan/Motor Assembly Maintenance Gas Control Valve MaintenanceConversion Between Gases 14.1 General Burner ConversionGas Valves Conduct Commissioning procedure as shown on Page 24, Section StartTroubleshooting For Automatic Ignition Burner Systems For your safety and optimum heater performanceConduct Commissioning procedure as shown Troubleshooting for Flame Supervision System Troubleshooting for Solenoid ValvesRemoval and Replacement Parts Burner Compartment Burner InjectorsIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter Pressure Switch RG P/NTo Replace the Fan Assembly Ctua Axial Fan/Guard/Motor AssemblyFan Removal and Replacement Ctub & Ctuc Centrifugal Fan/Guard/Motor AssemblyCentrifugal Fan Orientation Fan DataPage Page Page Some objects can catch fire or explode when placed

CTU 22 TO 115 specifications

The Roberts Gordon CTU 22 TO 115 is a renowned unit heater designed to deliver efficient heating solutions in commercial and industrial settings. Known for its advanced features and robust design, this unit heater is ideal for applications where warmth and comfort are essential, such as warehouses, manufacturing facilities, and large retail spaces.

One of the main features of the CTU 22 TO 115 is its powerful heating capacity. With a range of output capabilities, it can effectively heat large areas, ensuring that employees and equipment remain comfortable during cold weather. The heater's output is adjustable, allowing for tailored heating solutions based on specific operational needs.

This model integrates several innovative technologies to enhance efficiency and performance. The use of advanced combustion technology ensures optimal fuel efficiency, which translates to lower energy costs and reduced environmental impact. The heater is available in both gas and oil configurations, providing versatility to accommodate different fuel sources depending on availability and preference.

In addition to its energy efficiency, the Roberts Gordon CTU features a compact design, making it suitable for installations in tight spaces. Its lightweight construction allows for easy installation and relocation, ensuring that businesses can quickly adapt to changing layout requirements. The unit is equipped with high-quality materials and a durable finish, contributing to its longevity and low maintenance needs.

Safety is a paramount concern in any heating system, and the CTU 22 TO 115 doesn't disappoint. It comes with various safety features, including over-temperature protection, ensuring that it operates securely under all conditions. With automatic shutoff capabilities, the heater provides peace of mind to operators, allowing for unattended operation in more remote settings.

Moreover, the CTU’s quiet operation is a significant advantage, as it minimizes disruption in the workplace, ensuring a comfortable environment for personnel. Its design also facilitates easy access to components for maintenance, thus ensuring that the unit remains operational with minimal downtime.

Overall, the Roberts Gordon CTU 22 TO 115 combines performance, efficiency, and safety features to create a reliable heating solution for diverse industrial applications. Its adaptability to various fuel types and efficient design makes it a popular choice among facility managers looking for dependable heating solutions.