SECTION 14: CONVERSION BETWEEN GASES

SECTION 14: CONVERSION BETWEEN GASES 14.1 General

Conversion between gasses will require a change of burner injectors and the gas valve re-commissioning to the new conditions.

14.2 Burner Conversion

Conversion of the burner assembly from one gas to the other is the same for all types of heaters.

1.Remove the burner compartment cover as shown on Page 36, Section 16.2.

2.Remove the connection between the gas valve outlet and the manifold. See Page 35, Section 16.1 for gas valve removal.

3.Remove the manifold from the burner assembly by removing the screws at the top and bottom. See Page 36, Section 16.2.1.

4.Remove the main burner injectors.

5.Replace with the injectors for the new gas ensuring a gas tight seal.

6.Refit all components in reverse order.

14.3 Gas Valves

All gas valves used on the CTU have pressure regulators that may be set to operate on natural gas or LPG.

Conversion is carried out by re-setting the burner pressure to the value in the data table during commissioning. See Page 8, Section 4.4. Ensure that the gas inlet pressure to the heater is correct for the new gas, and that the gas supply has been purged of the old gas.

31

Image 37
Contents Supplier after leaving the building Immediately call your local gasFollow the gas supplier’s Instructions Supplier, call the Fire DepartmentPage Roberts-Gordon, LLC Page Table of Figures Page Product Approval Installer Responsibility Heater SafetyClearances to Combustibles Corrosive ChemicalsCritical Considerations 3.1 Basic Information Minimum Required Installation ClearancesVentilation Gas SupplyInstallation Clearances and Clearances to Combustibles Dimension Data Ctua All Models Specifications 4.1 CtuaTop View End View Rear ViewCTUB, Ctuc and Ctud Dimension Data CTUB, Ctuc and CtudGeneral Technical Data Table Gas rates corrected to standard conditions 1013.25 mbar 15 C Handling Heater Installation 5.1 GeneralType B22 Appliance Flue Installation 6.1 Flue InstallationAir Intake Terminal Cover Vertical and Horizontal Flue Termination Type B22 Appliance AIR Supply Distribution Duct Work for CTUB, Ctuc and Ctud Heaters Optional Heater ConfigurationsCtud Heaters Connections GAS PipingOption a Option BWiring and Electrical Information 50 Hz Ctua Wiring Diagram ModelsSite Wiring CTUB/C Wiring Diagram Models Site Wiring230 V 1 Ø 50 Hz Ignition ModuleRUN For external fan wiring Ctud Wiring Diagram ModelsSite Wiring and Electrical Information Louvres CommissioningElectrical Checks Mechanical ChecksEnd View Automatic Burner Control Box SequenceCheck Gas Rate Combustion TestingTurning Off the Heater Complete the Commissioning External ControlsInstruction to the User Heater Operation Burner Lockout Reset ButtonCommon User Controls Thermostat Limit Thermodisc Lighting Instructions To Turn On HeaterSimple Fault Finding Burner Faults Simple Fault FindingTo Turn the Heater Off 13.3 Fan/Motor Assembly Maintenance Burner MaintenanceHeat Exchanger Maintenance Gas Control Valve MaintenanceBurner Conversion Conversion Between Gases 14.1 GeneralGas Valves Start Conduct Commissioning procedure as shown on Page 24, SectionFor your safety and optimum heater performance Troubleshooting For Automatic Ignition Burner SystemsConduct Commissioning procedure as shown Troubleshooting for Solenoid Valves Troubleshooting for Flame Supervision SystemRemoval and Replacement Parts Burner Injectors Burner CompartmentIgnition Electrode and Flame Probe Remove screws securing outlet flange to the flue adapter RG P/N Pressure SwitchFan Removal and Replacement Ctua Axial Fan/Guard/Motor AssemblyTo Replace the Fan Assembly Ctub & Ctuc Centrifugal Fan/Guard/Motor AssemblyFan Data Centrifugal Fan OrientationPage Page Page Some objects can catch fire or explode when placed

CTU 22 TO 115 specifications

The Roberts Gordon CTU 22 TO 115 is a renowned unit heater designed to deliver efficient heating solutions in commercial and industrial settings. Known for its advanced features and robust design, this unit heater is ideal for applications where warmth and comfort are essential, such as warehouses, manufacturing facilities, and large retail spaces.

One of the main features of the CTU 22 TO 115 is its powerful heating capacity. With a range of output capabilities, it can effectively heat large areas, ensuring that employees and equipment remain comfortable during cold weather. The heater's output is adjustable, allowing for tailored heating solutions based on specific operational needs.

This model integrates several innovative technologies to enhance efficiency and performance. The use of advanced combustion technology ensures optimal fuel efficiency, which translates to lower energy costs and reduced environmental impact. The heater is available in both gas and oil configurations, providing versatility to accommodate different fuel sources depending on availability and preference.

In addition to its energy efficiency, the Roberts Gordon CTU features a compact design, making it suitable for installations in tight spaces. Its lightweight construction allows for easy installation and relocation, ensuring that businesses can quickly adapt to changing layout requirements. The unit is equipped with high-quality materials and a durable finish, contributing to its longevity and low maintenance needs.

Safety is a paramount concern in any heating system, and the CTU 22 TO 115 doesn't disappoint. It comes with various safety features, including over-temperature protection, ensuring that it operates securely under all conditions. With automatic shutoff capabilities, the heater provides peace of mind to operators, allowing for unattended operation in more remote settings.

Moreover, the CTU’s quiet operation is a significant advantage, as it minimizes disruption in the workplace, ensuring a comfortable environment for personnel. Its design also facilitates easy access to components for maintenance, thus ensuring that the unit remains operational with minimal downtime.

Overall, the Roberts Gordon CTU 22 TO 115 combines performance, efficiency, and safety features to create a reliable heating solution for diverse industrial applications. Its adaptability to various fuel types and efficient design makes it a popular choice among facility managers looking for dependable heating solutions.