HEATING PERFORMANCE - Upflow, Downflow, and Horizontal Furnaces and Coils
UNIT | COIL1 |
|
|
| ARI HEATING2 |
|
|
| ||
MODEL* | MODEL |
| 47F |
|
|
|
| 17F |
| HSPF |
|
| MBH | COP | KW |
| MBH |
| COP | KW | STD |
| FC/MC/PC/UC18 | 17.0 | 3.32 | 1.50 |
| 12.7 |
| 3.00 | 1.24 | 7.70 |
| FC/MC/PC/UC24 | 17.0 | 3.44 | 1.45 |
| 10.4 |
| 2.60 | 1.17 | 7.70 |
YHJD18S41S1 | HC18 | 17.0 | 3.32 | 1.50 |
| 12.7 |
| 3.00 | 1.24 | 7.70 |
| HC30 | 17.0 | 3.38 | 1.47 |
| 10.4 |
| 2.60 | 1.17 | 7.70 |
| HD24 | 16.6 | 3.16 | 1.54 |
| 12.8 |
| 3.00 | 1.25 | 7.70 |
| FC/MC/PC32 | 23.2 | 3.40 | 2.00 |
| 12.6 |
| 2.24 | 1.65 | 7.70 |
| FC/MC/PC35 | 23.2 | 3.40 | 2.00 |
| 12.6 |
| 2.24 | 1.65 | 7.70 |
YHJD24S41S1 | HC30 | 23.0 | 3.40 | 1.98 |
| 12.6 |
| 2.24 | 1.65 | 7.70 |
| HC36 | 23.2 | 3.40 | 2.00 |
| 12.6 |
| 2.24 | 1.65 | 7.70 |
| HD36 | 23.2 | 3.40 | 2.00 |
| 12.6 |
| 2.24 | 1.65 | 7.70 |
| FC/MC/PC37 | 28.2 | 3.40 | 2.43 |
| 16.6 |
| 2.32 | 2.10 | 7.70 |
YHJD30S41S1 | FC/MC/PC43 | 28.2 | 3.40 | 2.43 |
| 16.6 |
| 2.32 | 2.10 | 7.70 |
HC42 | 28.2 | 3.40 | 2.43 |
| 16.6 |
| 2.32 | 2.10 | 7.70 | |
|
|
| ||||||||
| HD48 | 28.2 | 3.60 | 2.30 |
| 16.6 |
| 2.32 | 2.10 | 7.70 |
| FC/MC/PC37 | 35.0 | 3.40 | 3.02 |
| 21.2 |
| 2.36 | 2.63 | 8.00 |
| FC/MC/PC43 | 35.0 | 3.42 | 3.00 |
| 21.2 |
| 2.36 | 2.63 | 8.00 |
YHJD36S41S1 | FC/MC/PC48 | 35.0 | 3.42 | 3.00 |
| 21.4 |
| 2.36 | 2.66 | 8.00 |
| HC42 | 35.0 | 3.42 | 3.00 |
| 21.2 |
| 2.36 | 2.63 | 8.00 |
| HD48 | 35.0 | 3.40 | 3.02 |
| 20.0 |
| 2.16 | 2.71 | 8.00 |
| FC/MC/PC60 | 41.0 | 3.66 | 3.28 |
| 27.8 |
| 2.56 | 3.18 | 8.00 |
YHJD42S41S1 |
|
|
|
|
|
|
|
|
|
|
HC60 | 41.0 | 3.66 | 3.28 |
| 27.8 |
| 2.56 | 3.18 | 8.00 | |
|
|
|
|
|
|
|
|
|
|
|
| HD60 | 41.0 | 3.14 | 3.83 |
| 27.6 |
| 2.26 | 3.58 | 8.00 |
|
|
|
|
|
|
|
|
|
|
|
| FC/MC/PC48 | 50.5 | 3.32 | 4.46 |
| 30.8 |
| 2.24 | 4.03 | 8.00 |
|
|
|
|
|
|
|
|
|
|
|
| FC/MC/PC60 | 51.0 | 3.50 | 4.27 |
| 30.6 |
| 2.34 | 3.83 | 8.00 |
YHJD48S41S1 |
|
|
|
|
|
|
|
|
|
|
HC60 | 51.0 | 3.50 | 4.27 |
| 30.6 |
| 2.34 | 3.83 | 8.00 | |
|
|
|
|
|
|
|
|
|
|
|
| HD60 | 50.0 | 2.98 | 4.92 |
| 30.6 |
| 2.06 | 4.35 | 8.00 |
|
|
|
|
|
|
|
|
|
|
|
| MC62 | 50.5 | 3.38 | 4.38 |
| 30.6 |
| 2.28 | 3.93 | 8.00 |
|
|
|
|
|
|
|
|
|
|
|
YHJD60S41S1 | MC62 | 56.5 | 3.48 | 4.76 |
| 35.4 |
| 2.42 | 4.29 | 8.00 |
|
|
|
|
|
|
|
|
|
|
|
1.Rated CFM same as for cooling.
2.Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no
supplemental electric heat operation.
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period.
— = Not Applicable.
Johnson Controls Unitary Products | 13 |