397855-YTG-G-0509

Physical and Electrical Data

MODEL

 

YHJD18

YHJD24

YHJD30

 

YHJD36

 

YHJD42

YHJD48

YHJD60

 

S41S1

S41S1

S41S1

 

S41S1

 

S41S1

S41S1

S41S2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Supply Voltage

 

 

 

 

208-230V, 1 60Hz

 

 

 

 

 

 

 

 

 

 

 

 

Normal Voltage Range 1

 

 

 

 

187 to 252

 

 

 

Minimum Circuit Ampacity

9.6

12.0

15.4

 

19.6

 

28.6

30.9

37.4

 

 

 

 

 

 

 

 

 

 

Max. Overcurrent Device Amps 2

15

20

25

 

30

 

50

50

60

Min. Overcurrent Device Amps 3

15

15

20

 

20

 

30

35

40

Compressor Type

 

Recip

Recip

Recip

 

Recip

 

Scroll

Scroll

Scroll

 

 

 

 

 

 

 

 

 

 

 

Compressor Amps

Rated Load

7.12

8.9

11.65

 

14.72

 

21.76

23.61

28.8

Locked Rotor

47.0

48.0

60.0

 

83.0

 

105.0

150.0

150.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

Yes

Yes

Yes

 

Yes

 

No

No

No

 

 

 

 

 

 

 

 

 

 

 

Fan Motor Amps

Rated Load

0.70

0.80

0.80

 

1.5

 

1.5

1.5

1.5

 

 

 

 

 

 

 

 

 

 

 

Fan Diameter Inches

24

24

24

 

24

 

24

24

24

 

 

 

 

 

 

 

 

 

 

 

 

Rated HP

1/10

1/8

1/8

 

1/4

 

1/4

1/4

1/4

Fan Motor

 

 

 

 

 

 

 

 

 

 

Nominal RPM

825

1075

1075

 

850

 

850

850

850

 

 

 

 

 

 

 

 

 

 

 

 

Nominal CFM

2200

2900

3100

 

3800

 

3800

3600

3600

 

 

 

 

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

15.7

18.3

21.0

 

23.58

 

23.58

23.58

23.6

Coil

 

 

 

 

 

 

 

 

 

 

Rows Deep

1

1

1

 

1

 

1

2

2

 

 

 

 

 

 

 

 

 

 

 

 

Fin / Inches

22

22

22

 

22

 

22

18

18

 

 

 

 

 

 

 

 

 

 

 

Liquid Line Set OD (Field Installed)

3/8

3/8

3/8

 

3/8

 

3/8

3/8

3/8

 

 

 

 

 

 

 

 

 

 

Vapor Line Set OD (Field Installed)

3/4

3/4

3/4

 

3/4

 

7/8

7/8

7/8

 

 

 

 

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 4

6 - 5

8 - 7

9 - 12

 

9 - 15

 

9 - 12

13 - 9

13 - 6

Charge Per Foot, Oz.

.62

.62

.62

 

.62

 

.67

.67

0.67

 

 

 

 

 

 

 

 

 

 

Operating Weight Lbs.

172

184

196

 

208

 

208

275

290

 

 

 

 

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

All dimensions are in inches. They are subject to change with- out notice. Certified dimensions will be provided upon request.

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit

 

Dimensions

 

Refrigerant Connection

 

 

 

 

 

(Inches)

 

Service Valve Size

 

 

 

Model

 

 

 

 

 

 

 

 

 

 

A1

 

B

 

C

Liquid

Vapor

 

 

 

 

 

 

 

 

 

18

28

 

34

 

34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24

32

 

34

 

34

 

3/4”

A

 

30

36

 

34

 

34

 

 

 

 

 

 

 

 

 

36

40

 

34

 

34

3/8”

 

 

 

 

 

 

 

42

40

 

34

 

34

 

 

 

 

 

48

40

 

34

 

34

 

7/8”

 

 

 

60

40

 

34

 

34

 

 

1. Including Fan Guard.

B

2

Johnson Controls Unitary Products

Image 2
Contents Listed Physical and Electrical Data ModelProcedures FootnotesSens Unit AIR HandlerCooling Model MODEL1 Rated NET MBH Seer EER CFM Seer HP withSeer HP with AHP / SHP / AHX / F*FP YHJD60S41S1 AHX60FC/MC/PC18 Unit Model Furnace Coil MODEL1 Cooling CFM Total Sens Seer HP with Variable Speed FURNACES2UC48C UC48D Unit Furnace Coil Cooling Model MODEL1 Rated Seer EER CFMMBH COP STD Seer HP With MA Unit AIR COIL1 ARI HEATING2 Model HandlerHspf Seer HP with MVMBH COP STD Seer HP with AHP SHP / AHX / F*FPUnit COIL1 ARI HEATING2 Model MBH COP STDModel Furnace COIL1 ARI HEATING2 MBH COP STD Seer HP With Variable Speed FURNACES3Model MBH COP STD 41.0 27.6 9X*C16 47.5 32.6 9X*C20 Accessories Typical Installation Entering AIR TemperatureCondensing FC/MC/PC24 FC/MC/PC30 FC/MC/PC32 FC/MC/PC35 FC/MC/PC32 FC/MC/PC35 FC/MC/PC37 FC/MC/PC43 FC/MC/PC37 FC/MC/PC43 FC/MC/PC48 On next UC48D FC/MC/PC48 FC/MC/PC60 MA20D MC62D MV20D MBH COP EnteringOutdoor Unit Indoor Coil 600 800 1000 38.5 31.4 1000 1200 1400 AHP/SHP48 AHX42 AHX48 UC48D 57.0 Johnson Controls Unitary Products Johnson Controls Unitary Products York Drive Norman, OK