York YHJD18 warranty FC/MC/PC24 FC/MC/PC30 FC/MC/PC32 FC/MC/PC35

Page 21

COOLING PERFORMANCE DATA

CONDENSING UNIT MODEL NO. YHJD24S41S1

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

AHP30

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSING

IDCFM

 

 

600

 

 

 

 

800

 

 

 

 

1000

 

 

ENTERING AIR

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

 

T.C.

22.9

26.4

25.6

29.2

31.5

25.8

28.0

27.2

30.7

33.2

28.8

29.6

28.8

32.2

35.0

65

S.C.

21.8

20.2

17.3

17.7

15.1

24.6

23.7

19.4

19.6

16.2

27.4

27.2

21.5

21.6

17.4

 

KW

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

1.5

 

T.C.

21.9

24.6

24.1

27.3

29.5

24.5

26.0

25.5

28.6

31.1

27.0

27.4

26.9

30.0

32.6

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

20.8

19.4

16.5

16.8

14.3

23.3

22.4

18.6

18.8

15.4

25.7

25.4

20.7

20.8

16.5

 

KW

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

 

T.C.

20.9

22.9

22.6

25.3

27.6

23.1

24.1

23.7

26.5

28.9

25.3

25.3

24.9

27.8

30.3

85

S.C.

19.9

18.6

15.8

16.0

13.4

22.0

21.2

17.9

18.0

14.5

24.1

23.7

20.0

20.0

15.6

 

KW

1.7

1.7

1.7

1.7

1.8

1.7

1.7

1.7

1.8

1.8

1.8

1.7

1.7

1.8

1.8

 

T.C.

19.8

21.1

21.0

23.4

25.6

21.7

22.1

22.0

24.5

26.8

23.5

23.1

23.0

25.6

27.9

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

18.9

17.8

15.0

15.1

12.6

20.6

19.9

17.1

17.2

13.7

22.4

22.0

19.2

19.2

14.8

 

KW

1.8

1.8

1.8

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

1.9

 

T.C.

18.4

19.1

19.2

21.5

23.5

20.1

20.3

20.0

22.3

24.5

21.8

21.5

20.8

23.2

25.5

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

17.6

16.7

14.3

14.4

11.7

19.2

18.6

16.2

16.4

12.8

20.8

20.5

18.1

18.4

13.9

 

KW

1.9

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.0

2.1

 

T.C.

17.1

17.3

17.4

19.6

21.5

18.6

18.6

18.0

20.2

22.3

20.1

20.0

18.7

20.9

23.1

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

16.3

15.7

13.5

13.6

10.8

17.7

17.4

15.2

15.6

12.0

19.2

19.1

16.9

17.6

13.1

 

KW

2.1

2.1

2.1

2.1

2.2

2.1

2.1

2.1

2.1

2.2

2.2

2.2

2.1

2.2

2.2

 

T.C.

15.8

15.4

15.6

17.7

19.5

17.1

17.0

16.1

18.2

20.1

18.5

18.5

16.6

18.6

20.7

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

15.0

14.7

12.7

12.9

10.0

16.3

16.1

14.3

14.9

11.1

17.6

17.6

15.8

16.9

12.2

 

KW

2.2

2.2

2.2

2.2

2.3

2.2

2.2

2.2

2.3

2.3

2.3

2.3

2.2

2.3

2.3

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

Air Handlers

Coils

T.C.

S.C.

KW

FC/MC/PC24

0.98

0.98

1.00

FC/MC/PC30

0.98

0.98

1.00

FC/MC/PC32

1.00

1.00

1.00

FC/MC/PC35

1.00

1.00

1.00

HC30

0.98

0.99

1.00

HC36

1.00

1.00

1.00

HD36

0.98

0.94

1.00

AHP30

0.99

0.98

1.00

AHX30

1.02

1.06

0.93

AHX36

1.04

1.08

0.91

AV*24

0.99

0.98

1.00

AV*36

1.02

1.01

0.91

F4FP030

0.99

0.97

1.00

F6FP030

1.03

1.06

0.95

F6FP036

1.02

1.07

0.94

MA08B

FC/MC/PC24B

0.98

0.98

1.00

MV12B

FC/MC/PC24B

1.01

1.00

1.00

MA08B

FC/MC/PC30B

0.98

0.98

1.00

MV12B

FC/MC/PC30B

1.01

1.01

1.00

MA08B

FC/MC/PC35B

1.00

1.00

1.00

MV12B

FC/MC/PC35B

1.02

1.02

1.00

MV16C

FC/MC/PC35C

1.02

1.02

1.00

Furnaces

Coils

T.C.

S.C.

KW

T*9X*B12

FC/MC/PC35B

1.02

1.04

0.91

T*(8,L)X*A12

FC/MC/PC37A

1.05

1.10

0.91

T*(8,L)X*B12

FC/MC/PC43B

1.06

1.12

0.91

T*9X*B12

FC/MC/PC43B

1.04

1.07

0.91

T*(8,L)X*B12

FC/MC/PC35B

1.04

1.09

0.91

T*9X*C16

FC/MC/PC35C

1.00

1.00

0.90

T*(8,L)X*A12

FC/MC/PC32A

1.02

1.05

0.91

Y*(8,L)C*A12

FC/MC/PC32A

1.01

1.01

0.94

Y*(8,L)C*B12

FC/MC/PC35B

1.02

1.01

0.93

(Y*9C/T*9V)*B12

FC/MC/PC35B

1.03

1.03

0.94

Y*(8,L)C*A12

FC/MC/PC37A

1.03

1.04

0.95

Y*(8,L)C*B12

FC/MC/PC43B

1.03

1.02

0.93

(Y*9C/T*9V)*B12

FC/MC/PC43B

1.04

1.04

0.94

Y*(8,L)C*B12

HC36

1.02

1.00

0.93

(Y*9C/T*9V)*B12

HC36

1.03

1.03

0.94

Y*(8,L)C*A12

HD36

1.00

0.99

0.93

Y*(8,L)C*B12

HD36

1.00

0.96

0.93

Y*(8,L)C*C16

HD36

1.02

1.02

0.92

Y*(8,L)C*C20

HD36

1.00

0.96

0.91

(Y*9C/T*9V)*B12

HD36

1.00

0.99

0.93

(Y*9C/T*9V)*C16

HD36

1.00

1.00

0.92

(Y*9C/T*9V)*C20

HD36

1.00

0.96

0.92

Johnson Controls Unitary Products

21

Image 21
Contents Listed Model Physical and Electrical DataFootnotes ProceduresCooling Model MODEL1 Rated NET MBH Seer EER CFM Unit AIR HandlerSens Seer HP withYHJD60S41S1 AHX60 Seer HP with AHP / SHP / AHX / F*FPFC/MC/PC18 CFM Total Sens Seer HP with Variable Speed FURNACES2 Unit Model Furnace Coil MODEL1 CoolingUC48C UC48D Seer EER CFM Unit Furnace Coil Cooling Model MODEL1 RatedHspf Unit AIR COIL1 ARI HEATING2 Model HandlerMBH COP STD Seer HP With MA Seer HP with MVSHP / AHX / F*FP MBH COP STD Seer HP with AHPMBH COP STD Unit COIL1 ARI HEATING2 ModelMBH COP STD Seer HP With Variable Speed FURNACES3 Model Furnace COIL1 ARI HEATING2Model MBH COP STD 41.0 27.6 9X*C16 47.5 32.6 9X*C20 Accessories Typical Installation Temperature CondensingEntering AIR FC/MC/PC24 FC/MC/PC30 FC/MC/PC32 FC/MC/PC35 FC/MC/PC32 FC/MC/PC35 FC/MC/PC37 FC/MC/PC43 FC/MC/PC37 FC/MC/PC43 FC/MC/PC48 On next UC48D FC/MC/PC48 FC/MC/PC60 MA20D MC62D MV20D Entering Outdoor Unit Indoor CoilMBH COP 600 800 1000 38.5 31.4 1000 1200 1400 AHP/SHP48 AHX42 AHX48 UC48D 57.0 Johnson Controls Unitary Products Johnson Controls Unitary Products York Drive Norman, OK