COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJD60S41S1 |
|
|
|
|
|
|
|
|
|
|
|
| ||||
INDOOR COIL MODEL NO. | FC/MC62 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CONDENSING | IDCFM |
|
| 1600 |
|
|
|
| 1800 |
|
|
|
| 2000 |
|
|
ENTERING AIR | ID DB (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 |
TEMPERATURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID WB (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
| T.C. | 54.0 | 57.1 | 56.9 | 62.3 | 67.6 | 56.0 | 57.9 | 57.8 | 63.4 | 69.1 | 58.0 | 58.7 | 58.7 | 64.4 | 70.5 |
65 | S.C. | 54.0 | 51.0 | 43.4 | 42.9 | 34.8 | 56.0 | 54.4 | 45.4 | 45.0 | 36.2 | 58.0 | 57.7 | 47.4 | 47.1 | 37.6 |
| KW | 2.8 | 2.8 | 2.8 | 2.9 | 2.9 | 2.8 | 2.8 | 2.8 | 2.9 | 2.9 | 2.8 | 2.8 | 2.8 | 2.9 | 2.9 |
| T.C. | 51.9 | 54.1 | 53.9 | 59.2 | 64.5 | 53.7 | 54.9 | 54.8 | 60.2 | 65.7 | 55.5 | 55.7 | 55.6 | 61.2 | 66.9 |
75 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 51.9 | 49.8 | 42.0 | 41.7 | 33.5 | 53.7 | 52.7 | 44.1 | 43.8 | 34.8 | 55.5 | 55.6 | 46.1 | 45.8 | 36.2 | |
| KW | 3.2 | 3.2 | 3.2 | 3.3 | 3.3 | 3.2 | 3.2 | 3.2 | 3.3 | 3.3 | 3.2 | 3.2 | 3.2 | 3.3 | 3.3 |
| T.C. | 49.7 | 51.1 | 51.0 | 56.2 | 61.4 | 51.3 | 51.9 | 51.8 | 57.1 | 62.4 | 53.0 | 52.7 | 52.6 | 58.0 | 63.4 |
85 | S.C. | 49.7 | 48.6 | 40.7 | 40.5 | 32.2 | 51.3 | 51.1 | 42.8 | 42.5 | 33.4 | 53.0 | 52.7 | 44.9 | 44.6 | 34.7 |
| KW | 3.6 | 3.6 | 3.6 | 3.6 | 3.7 | 3.6 | 3.6 | 3.6 | 3.7 | 3.7 | 3.6 | 3.6 | 3.6 | 3.7 | 3.7 |
| T.C. | 47.6 | 48.1 | 48.1 | 53.1 | 58.3 | 49.0 | 48.9 | 48.8 | 54.0 | 59.0 | 50.4 | 49.7 | 49.5 | 54.8 | 59.8 |
95 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 47.6 | 47.4 | 39.3 | 39.2 | 30.9 | 49.0 | 48.9 | 41.5 | 41.3 | 32.0 | 50.4 | 49.7 | 43.6 | 43.3 | 33.2 | |
| KW | 4.0 | 4.0 | 4.0 | 4.0 | 4.1 | 4.0 | 4.0 | 4.0 | 4.1 | 4.1 | 4.0 | 4.0 | 4.0 | 4.1 | 4.1 |
| T.C. | 44.3 | 44.6 | 44.1 | 48.7 | 53.5 | 45.6 | 45.5 | 44.6 | 49.3 | 54.1 | 46.8 | 46.3 | 45.2 | 50.0 | 54.7 |
105 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 44.3 | 44.6 | 37.6 | 37.4 | 29.0 | 45.6 | 45.5 | 39.7 | 39.4 | 30.2 | 46.8 | 46.3 | 41.8 | 41.5 | 31.3 | |
| KW | 4.5 | 4.5 | 4.5 | 4.5 | 4.6 | 4.5 | 4.5 | 4.5 | 4.5 | 4.6 | 4.5 | 4.5 | 4.5 | 4.5 | 4.6 |
| T.C. | 41.1 | 41.3 | 40.2 | 44.4 | 48.9 | 42.2 | 42.2 | 40.6 | 44.9 | 49.4 | 43.3 | 43.1 | 41.0 | 45.3 | 49.9 |
115 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 41.1 | 41.3 | 35.9 | 35.7 | 27.3 | 42.2 | 42.2 | 37.9 | 37.7 | 28.4 | 43.3 | 43.1 | 40.0 | 39.7 | 29.5 | |
| KW | 4.9 | 5.0 | 4.9 | 5.0 | 5.0 | 5.0 | 5.0 | 4.9 | 5.0 | 5.0 | 5.0 | 5.0 | 5.0 | 5.0 | 5.0 |
| T.C. | 37.9 | 37.9 | 36.2 | 40.1 | 44.3 | 38.8 | 38.8 | 36.5 | 40.4 | 44.6 | 39.8 | 39.8 | 36.8 | 40.7 | 45.0 |
125 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
S.C. | 37.9 | 37.9 | 34.2 | 33.9 | 25.5 | 38.8 | 38.8 | 36.2 | 35.9 | 26.6 | 39.8 | 39.8 | 36.8 | 37.9 | 27.7 | |
| KW | 5.4 | 5.4 | 5.4 | 5.4 | 5.5 | 5.4 | 5.4 | 5.4 | 5.4 | 5.5 | 5.4 | 5.4 | 5.4 | 5.4 | 5.5 |
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between
Air Handlers | Coils | T.C. | S.C. | KW |
AHX60 | – | 1.06 | 1.13 | 1.05 |
F6FP060 | – | 1.06 | 1.09 | 1.01 |
MA20D | MC62D | 1.00 | 1.00 | 1.00 |
MV20D | MC62D | 1.01 | 1.01 | 1.00 |
Furnaces | Coils | T.C. | S.C. | KW |
T*(8,L)X*C20 | FC/MC62D | 1.05 | 1.08 | 0.99 |
T*9X*D20 | FC/MC62D | 1.02 | 1.02 | 1.02 |
(Y*9C/T*9V)*D20 | FC/MC/PC60D | 0.99 | 0.96 | 0.97 |
Y*(8,L)C*C20 | FC/MC62D | 1.00 | 0.97 | 0.96 |
(Y*9C/T*9V)*C20 | FC/MC62D | 0.99 | 0.96 | 0.98 |
Johnson Controls Unitary Products | 27 |