Toshiba RAV-SP180AT2-UL installation manual Electrical Connections, „ Field wiring, „ Wiring

Page 15

Outdoor Unit

Installation Manual

7 ELECTRICAL CONNECTIONS

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

The unit cabinet must have an uninterrupted or unbroken ground to minimize personal injury if an electrical fault should occur. The ground may consist of electrical wire or metal conduit when installed in accordance with existing electrical codes.

Before performing service or maintenance, be sure main power switch is turned OFF.

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in damage or improper operation.

Unit failure as a result of operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components.

Wrong wiring may cause a burn-out of some electrical parts.

Do not damage or scratch the conductive core or inner insulator of the power and inter-connecting wires when peeling them.

Valve cover

Field power supply wires

System

 

interconnection wires

Conduit

 

„Field wiring

The dashed lines show field wiring.

 

(Main circuit)

(Indoor/outdoor

 

 

connecting wires)

 

Input

L1

L1

L1

 

power

L2

L2

L2

 

208/230 V~,

Remote

 

S

S

60 Hz

 

controller

circuit breaker

Outdoor unit

Indoor unit

 

ground

Connect the indoor/outdoor connecting wires to the identical terminal numbers on the terminal block of each unit.

Incorrect connection may cause a failure.

1.With the valve cover removed the electrical control box is exposed the side of the unit.

2.Terminate the field wiring conduit (if used) at the conduit connection holes provided.

3.Route the field power wires and the system interconnection wires (indoor to outdoor). Terminate the wires at field wiring terminal blocks.

Field wiring terminal blocks

L1 L2 S L1 L2

L1 L2 S

L1 L2

Ground screw

 

System interconnection

Field power

wires

supply wires

„Wiring

All wiring and connections must comply with NEC, CEC, local codes.

1.

Connect all wires to the correct terminal on the

 

 

wiring terminal blocks.

 

2.

Make sure that all connectors are secure.

 

3.

Size connectors per the ratings listed in the system

 

 

requirement section.

 

 

 

4.

System interconnections should be minimum, 16

EN

 

AWG.

 

 

 

– 14 –

14-EN

Image 15
Contents Installation manual Contents Ø0.26 hole DimensionAccessory Parts „ Piping Field supplied System RequirementsBe sure to ground the equipment Precautions for SafetyEquipment Damage Hazard Installation of NEW Refrigerant AIR Conditioner „ Required Tools/Equipment and Precautions for UseNew Refrigerant Air Conditioner Installation „ Installation Location Do not install the outdoor unit in the following locationExample Upper side is free Above unit is free „Required ClearancesUnit in mm Barrier at rear side Barrier in front„ Installation of Outdoor Unit Standard installationBarriers in front and back of unit „ For Reference Installation ManualProjection margin in flaring B Unit in mm Rigid Clutch type Refrigerant Piping„ Tightening of Flare Connections FlaringDo not apply refrigerant oil to the flared surface „ Field wiring „ WiringElectrical Connections Triple Evacuation Method Using Vacuum PumpEvacuate and Dehydrate the System Deep Vacuum MethodLiquid and gas side Open service valvesValve handling precautions Final Tubing Check11PERIODIC Maintenance Finishing10TEST RUN 13POWER Save Procedure12UNIT Pump Down EH99865301

RAV-SP180AT2-UL specifications

The Toshiba RAV-SP180AT2-UL is an innovative ducted air conditioning unit designed to deliver exceptional cooling and heating capabilities for both residential and commercial applications. Known for its efficiency and performance, this model integrates advanced technology that ensures optimal indoor climate control.

One of the primary features of the RAV-SP180AT2-UL is its energy efficiency. It operates with a high Energy Efficiency Ratio (EER) and Seasonal Energy Efficiency Ratio (SEER) ratings, allowing it to consume less electricity while providing maximum comfort. This efficiency not only contributes to lowering energy bills but also promotes environmentally friendly practices by reducing carbon emissions.

The air conditioning unit is equipped with Toshiba’s advanced inverter technology. This technology allows for precise temperature control and significant energy savings by continuously adjusting the compressor speed based on the desired temperature. With this capability, the system can operate quietly and maintain a stable climate, avoiding the sharp temperature fluctuations characteristic of traditional fixed-speed units.

Another significant feature of the RAV-SP180AT2-UL is its compact design, making it suitable for installation in various settings, including small apartments and larger commercial spaces. Its ducted system enables seamless air distribution, reducing visible components and maintaining the aesthetic of the interior space.

The unit also incorporates innovative filtration systems that improve indoor air quality. With advanced air purifying filters, it effectively minimizes allergens, dust, and pollutants, ensuring that the air circulated in the space is clean and healthy.

In terms of control, the RAV-SP180AT2-UL is compatible with a range of smart control options. Users can manage settings remotely via applications or programmable timers, allowing for convenience and the possibility of scheduling cooling and heating cycles according to personal routines.

Overall, the Toshiba RAV-SP180AT2-UL combines efficiency, compact design, and advanced technology, making it a strong contender in the ducted air conditioning market. Its ability to provide comfortable air conditioning solutions while being mindful of energy consumption is a testament to Toshiba's commitment to innovation in climate control technology.