York R-410A manual Electric Heating Section if Equipped

Page 12

246824-YTG-G-1208

d. Flame proving controls. Unit shall have two independent stages of capacity (60% 1st stage, 100% 2nd stage).

ELECTRIC HEATING SECTION (IF EQUIPPED)

An electric heating section, with nickel chromium elements, shall be provided in a range of 9 thru 54 KW, offering two states of capacity all sizes. The heating section shall have a primary limit control(s) (automatic reset) to prevent the heating element system from operating at an excessive temperature. The Heat- ing Section assembly shall slide out of the unit for easy mainte- nance and service. Units with Electric Heating Sections shall be wired for a single point power supply with branch circuit fusing (where required).

UNIT OPERATING CHARACTERISTICS

Unit shall be capable of starting and running at 125 ºF outdoor temperature, exceeding maximum load criteria of ARI Standard 340/360. The compressor, with standard controls, shall be capable of operation down to 0 ºF outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up. (Gas heat only)

ELECTRICAL REQUIREMENTS - All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring.

STANDARD LIMITED WARRANTIES - Compressor – 5 Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years, Parts – 1 Year

maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions

regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

ADDITIONAL FACTORY INSTALLED OPTIONS

ALTERNATE INDOOR BLOWER MOTOR – For applications with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow.

CONVENIENCE OUTLET (POWERED/NON-POWERED) Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors.

ELECTRIC HEAT - Electric Heaters range from 9 kW to 54 kW and are available in all the voltage options of the base unit.

PHASE MONITOR - Designed to prevent damage in out- of-phase condition.

COIL GUARD - Designed to prevent condenser coil damage.

BAS CONTROLS - Include supply air sensor, return air sensor, dirty filter indicator and air proving switch.

FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be made available by either/or):

ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER

– Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed- air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 ºF. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief or power exhaust.

MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and return air dampers that are interlocked and positioned by a 2-position,spring-return damper actuator. The

DIRTY FILTER SWITCH – This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high- pressure drop across the filters.

BREAKER – An HACR breaker can be factory installed on gas heat units or cooling units with electric heat.

DISCONNECT SWITCH - A disconnect can be factory installed on a cooling only units sized for the largest electric heat available.

STAINLESS STEEL HEAT EXCHANGER – For applications in a corrosive environment, this option provides a full stainless steel heat exchanger assembly.

SMOKE DETECTOR – A smoke detector can be factory mounted and wired in the supply and/or return air compartments.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB - 14” and 8” high, full perimeter knockdown curb, with hinged design for quick assembly.

BAROMETRIC RELIEF DAMPER – (Unit mounted – Downflow, Duct Mounted – Horizontal) – Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit during economizer operation.

12

Johnson Controls Unitary Products

Image 12
Contents Technical Guide Table of Contents Component LocationHeat Pump Ton York Model Number Nomenclature NomenclatureFeatures and Benefits Standard FeaturesFactory Installed Options Control Options Field Installed Accessories Accessories Part Number DescriptionGuide Specifications GeneralIndoor Evaporator FAN Assembly Electric Heating Section if Equipped Reheat Mode Sequence of Operation Reheat Control Board Physical Data ZH078-150 Physical DataFilters ZR078-150 Physical Data Reheat Coil Data XP078-150 Physical Data ZH/ZR/XP078-150 Unit Limitations MinYTG-G-1208 Capacity Performance ZH078-150 Cooling CapacitiesZH078 6.5 Ton 115F ZH090 7.5 Ton ZH090 7.5 Ton ZH102 8.5 Ton ZH102 8.5 Ton ZH120 10 Ton 115F 125F ZH150 12.5 Ton ZH150 12.5 Ton ZR078-150 Cooling and Reheat Capacities ZR078 6.5 Ton Cooling115F ZR078 6.5 Ton Reheat 35F 45FCapacity Input ZR090 7.5 Ton Cooling 115F ZR090 7.5 Ton Reheat 75F 85F ZR102 8.5 Ton Cooling 115F ZR102 8.5 Ton Reheat 75F 85F ZR120 10 Ton Cooling 115F ZR120 10 Ton Reheat 75F 85F ZR150 12.5 Ton Cooling 115F 125F ZR150 12.5 Ton Reheat 75F 85F XP078-150 Cooling Capacities XP078 6.5 Ton115F XP090 7.5 Ton 95F 105F115F 125F XP102 8.5 Ton 115F XP120 10 Ton XP120 10 Ton XP150 12.5 Ton 115F 125F XP078-150 Heating Capacities XP078-150Capacity Outdoor Temperature F @ 72% RH Airflow Performance ZH078-150 Side Duct ApplicationZH078 6.5 Ton Side Duct ZH090 7.5 Ton Side DuctZH120 10 Ton Side Duct ZH150 12.5 Ton Side DuctZH078-150 Bottom Duct Application ZH078 6.5 Ton Bottom DuctZH090 7.5 Ton Bottom Duct ZH102 8.5 Ton Bottom DuctZH120 10 Ton Bottom Duct ZH150 12.5 Ton Bottom DuctZR078-150 Side Duct Application ZR078 6.5 Ton Side DuctZR090 7.5 Ton Side Duct ZR102 8.5 Ton Side DuctZR120 10 Ton Side Duct ZR150 12.5 Ton Side DuctZR078-150 Bottom Duct Application ZR078 6.5 Ton Bottom DuctZR090 7.5 Ton Bottom Duct ZR102 8.5 Ton Bottom DuctZR120 10 Ton Bottom Duct ZR150 12.5 Ton Bottom DuctXP078-150 Side Duct Application XP078 6.5 Ton Side DuctXP090 7.5 Ton Side Duct XP102 8.5 Ton Side DuctXP120 10 Ton Side Duct XP150 12.5 Ton Side DuctXP078-150 Bottom Duct Application XP078 6.5 Ton Bottom DuctXP090 7.5 Ton Bottom Duct XP102 8.5 Ton Bottom DuctXP120 10 Ton Bottom Duct XP150 12.5 Ton Bottom DuctRPM Selection Additional Static Resistance TonsAirflow Performance Drive SelectionAltitude/Temperature Correction Factors Air Temperature ºFFactor CorrectionIndoor Blower Specifications Power Exhaust SpecificationsGas Heat Minimum Supply Air Electric Heat Minimum Supply AirIndoor Sound Power Levels Outdoor Sound Power Levels ZH/ZR/XP078-150Sound Performance Electric Heat MultipliersZH078-150 Standard Motor Without Powered Convenience Outlet Electrical DataZH078-150 Standard Motor Without Powered Convenience Outlet ZH078-150 Hi Static Motor Without Powered Convenience Outlet ZH078-150 Hi Static Motor Without Powered Convenience Outlet ZH078-150 Standard Motor With Powered Convenience Outlet ZH078-150 Standard Motor With Powered Convenience Outlet ZH078-150 Hi Static Motor With Powered Convenience Outlet ZH078-150 Hi Static Motor With Powered Convenience Outlet ZR078-150 Standard Motor Without Powered Convenience Outlet ZR078-150 Standard Motor Without Powered Convenience Outlet ZR078-150 Hi Static Motor Without Powered Convenience Outlet ZR078-150 Hi Static Motor Without Powered Convenience Outlet ZR078-150 Standard Motor With Powered Convenience Outlet ZR078-150 Standard Motor With Powered Convenience Outlet ZR078-150 Hi Static Motor With Powered Convenience Outlet ZR078-150 Hi Static Motor With Powered Convenience Outlet XP078-150 Standard Motor Without Powered Convenience Outlet XP078-150 Standard Motor Without Powered Convenience Outlet XP078-150 Hi Static Motor Without Powered Convenience Outlet Johnson Controls Unitary Products 101 XP078-150 Standard Motor With Powered Convenience Outlet Johnson Controls Unitary Products 103 XP078-150 Hi Static Motor With Powered Convenience Outlet Johnson Controls Unitary Products 105 Typical Wiring Diagrams ZH/ZR078-150 Typical Wiring DiagramsJohnson Controls Unitary Products 107 108 Johnson Controls Unitary Products Johnson Controls Unitary Products 109 110 Johnson Controls Unitary Products Johnson Controls Unitary Products 111 Typical ZR078-120 Reheat Wiring Diagram Typical ZR150 Reheat Wiring Diagram XP078-150 Typical Wiring Diagrams Johnson Controls Unitary Products 115 Weights and Dimensions ZH/ZR/XP078-150 Unit WeightsUnit 4 Point Load Weight Unit 6 Point Load Weight ZH/ZR/XP078-150 Unit Dimensions ZH/ZR/XP078-150 Unit Accessory WeightsZH/ZR/XP078-120 ZH/ZR/XP078-150 Unit Physical Dimensions Detail aZH/ZR/XP078-150 Unit Clearances ZH/ZR/XP078-150 Unit Bottom Duct OpeningsZH/ZR/XP078-150 Unit Electrical Entry ZH/ZR/XP078-120 Unit Side Duct OpeningsSide Duct Dimensions ZH/ZR/XP150 Unit Side Duct OpeningsZH/ZR/XP078-150 Unit Left Duct Opening ZH/ZR/XP078-150 Unit Accessory Dimensions ZH/ZR/XP078-150 Roof CurbZH/ZR/XP078-150 Transition Roof Curb ZH/ZR/XP078-150 Economizer Assembly Factory Installed Downflow Economizer Field Installed Downflow Economizer W/Power ExhaustEconomizer Options Economizer UsageField Installed Horizontal Economizer W/Power Exhaust Slab Economizer Downflow W/Power ExhaustSlab Economizer End Return W/Power Exhaust 126 Johnson Controls Unitary Products YTG-G-1208 Johnson Controls Unitary Products 127 Johnson Controls Unitary Products York Drive Norman, OK
Related manuals
Manual 24 pages 22.74 Kb Manual 68 pages 3.65 Kb Manual 104 pages 7.39 Kb Manual 36 pages 24.83 Kb

R-410A specifications

York R-410A is a widely recognized and highly efficient refrigerant used in modern air conditioning systems. Developed as an environmentally friendly alternative to R-22, R-410A has gained popularity in the HVAC industry due to its numerous advantageous features and characteristics.

One of the main features of York R-410A is its ability to provide superior cooling performance. This refrigerant operates efficiently at both high and low temperatures, allowing systems using it to maintain optimal indoor climates even during extreme weather conditions. Its high energy efficiency ratio (EER) and seasonal energy efficiency ratio (SEER) ratings make it a preferred choice for energy-conscious consumers, resulting in lower energy bills and a reduced carbon footprint.

Technologically, York R-410A systems feature advanced compressor designs that enhance their overall reliability and performance. These compressors are often equipped with variable-speed technology, enabling them to adjust their output to match the cooling demands of the space. This not only improves comfort levels but also leads to efficient energy consumption, reducing wear and tear on the equipment over time.

Another significant characteristic of York R-410A is its non-ozone-depleting properties. Unlike its predecessor R-22, which is being phased out due to its damaging effects on the ozone layer, R-410A is designed to minimize environmental impact. Its lower global warming potential (GWP) further underscores its role in promoting sustainability within the HVAC sector.

Furthermore, York R-410A systems are engineered with enhanced safety features. The refrigerant is non-toxic and non-flammable, which makes it safer for use in both residential and commercial applications. Additionally, its high thermal stability reduces the risk of breakdown or leakage, contributing to longer system lifespans and lower maintenance costs.

In conclusion, York R-410A stands out as a cutting-edge refrigerant that combines efficiency, safety, and environmental responsibility. With its advanced technologies and remarkable characteristics, it meets the demands of modern air conditioning requirements while paving the way for a sustainable future in HVAC systems. Adopting York R-410A not only benefits individual users through improved comfort and lower energy bills but also plays a vital role in protecting our planet's ozone layer and mitigating climate change.