SETPOINTS SCREEN

OVERVIEW

This screen, accessed from the Unit screen, provides a convenient location for programming the most common setpoints involved in the chiller/condensing unit control. The setpoints depend on the type of unit.

Values on this screen are only pro- grammable if the chiller/condensing unit is in remote control mode. These values are only viewable if the unit is in local mode.

DISPLAY ONLY

None

PROGRAMMABLE

Leaving Chilled Liquid Temperature or

Return Chilled Liquid Temperature or Suction Pressure or Discharge Air Temperature Setpoint

This value allows the user to define the cooling setpoint that is to be maintained by the chiller/condensing unit. See the unit’s Installation, Operation and Maintenance Manual (IOM) for it’s programmable range.

Leaving Chilled Liquid Temperature or Return Chilled Liquid Temperature or Suction Pressure or Discharge Air Temperature - Control Range

This is the maximum allowable positive and negative deviation that is acceptable from setpoint in the system application. See the unit’s Installation, Operation and Maintenance Manual (IOM) for it’s programmable range.

Remote Chiller Run or Remote Unit Run

The chiller/condensing unit can be selected to either Run or Stop. Selecting Stop will command the chiller/condensing unit to shut down. Selecting Run will allow the chiller/condensing unit to turn on.

Current Limit Setpoint

This is the motor current limiting setpoint. The chiller will be limited from loading when the motor current equals or exceeds this value. Typically, for most instal- lations, no limiting is required and the programmed limiting will be set at or above 100%.

Load Limit Setpoint (YCAL Chillers)

Load Limiting can be programmed from 0 to 2. Load Limit 0 = no load limit

Load Limit 1 = 50% load limit - 2/4 compressor units. Load Limit 1 = 66% load limit - 3/6 compressor units. Load Limit 2 = 33 % - 3/6 compressor units only.

Change Schedule

The daily schedule is a 1 week schedule and must be programmed for the start and stop time for each week day and a holiday if desired. A box is provided to specify which days are to use the holiday schedule.

Programming the same time for both Start and Stop times will cause the display to enter 00.00 for both times which will cause the chiller to always be allowed to run.

Repeat Monday

The other days can be selected to change to the Monday schedule.

Clear Schedule

In a situation where it is required to run the chiller 24 hours a day, 7 days a week, the Chiller Control panel should first have its entire Daily Schedule zeroed (00.00) for all Start and Stop times. This puts the chiller in the run mode at all times. The OptiView Remote Control Center may now be programmed with all zeroes (00.00) for all Start and Stop times by pressing the Clear Schedule button. Since the chiller panel is already in the run mode, programming the OptiView Remote Control Center for all zeroes will keep the chiller in this mode indefinitely, allowing the chiller to run whenever demand requires.

NAVIGATION

Home

Causes an instant return to the Home Screen.

Unit Data

Causes an instant return to the Unit Screen.

46

YORK INTERNATIONAL

Image 46
Contents Remote Control Center Optiview Remote Control CenterGeneral Safety Guidelines Safety SymbolsChangeability of this Document Table of Contents List of Tables List of Figures EU Declaration of Conformity Product Description CHILLER/CONDENSING Control Panels Installation Required Software Version Chiller / Condensing Unit Eproms Optiview Remote Control Center From Optiview RCC Unit Microboard 031-01314-000 031-02050-001 Unit MicroboardWire Sizing Voltage Source FigureWiring Practices Figure Ground Wire Size FigureGrounding Do not drill a control panel to locate conduit con Sides or bottom of the panel and use a conduit drainOperation Setpoints Screen Descriptions and UsageSetpoint / Change Schedule Manual ControlsScreen Navigation Layout This page intentionally left blank to maintain formatting Unit Type Unit Control TemperatureHome Screen Unit StatusAverage Ambient Temperature Unit Run Indicator LEDUnit # Unit Screen Examples Ycal ChillerYcas Chiller Ycws Chiller Unit Screen This page intentionally left blank Systems Screen Examples 00507VIPC Systems Screen Individual System Screen None Hours and Starts Screen Total Starts Operating HoursOptions Screen Ycas Chiller / Ycar ChillerLocal/Remote Control Mode Units Display ModeAmbient Control Mode Language Display ModeTrending Screen TrendingStop Trend SetupStart AxisChart Type Trend Setup ScreenCollection Interval Data Point Min SelectData Point Slot # Data Point MaxThis page intentionally left blank This page intentionally left blank Setpoints Screen Examples 00517VIPC Setpoints Screen Print History Last FaultsHistory Screen Print All HistoriesHistory Printout History Details ScreenDown RCC Setpoints Screen SetupNumber of Units Connected Set Date RCC Setup ScreenClock Enabled / Disabled Set TimeComms DiagnosticsUnits PrinterRS-485 Baud Rate Comms ScreenRCC Poll Time 5-30 sec Printer Screen Software Versions Diagnostics ScreenRCC Comms Diagnostics I/O Screen Digital InputsDiagnostics RCC Comms Screen Timeout Count Clear CountersDisplay Messages Status MessagesPrinters PrintersSeiko Equipped with an RS-232 Serial interface OkidataWeigh-Tronix Models 2600 Okidata 182, 182 turbo, 184 turboWEIGH-TRONIX Printer ConnectorsHardware required ModelPrinter Setup Automatic Data LoggingLocal/Remote Control Mode Suction Temperature = 42.9 F Discharge Temperature Service IntroductionSystem Architecture Refer to FIGControl Center Microboard Refer toMini-card signature test Fpga configurationFirst initiate table complete Mini-card checksumService York International Bios Eprom U45 Flash Memory Card Bram Bios Eprom Flash Memory Card From Microboard Program Jumpers Pins 1-2 RS-232 Pins 2-3 RS-485 JP10 JP26 Not usedWatchdog protection as follows JP34, JP35, JP36, JP37 Not Used JP39, JP40, JP41, JP42 Not usedMicroboard Program Switches Tion! Severe compressor or chillerMicroboard Serial Data Communications Ports Configurable Analog Inputs Liquid Crystal Display Ment Displays or supporting components cannot beDisplay Replacement Kit Sharp LQ10D367 Display Refer to Removal InstallationLG Semicon LP104V2 Display refer to Removal DISPLAY, Mounting Liquid Crystal Display Assembly LG Semicon LP104V2 Display Sharp LQ10D367 Lamp Replacement 031-01765-001 Display Interface Board031-01765-002 Display Interface Board Display Backlight Inverter Board Inverter Keypad Refer to Figures 45Keypad LD04075 Power Supply Power Supply Offline Diagnostics & Troubleshooting Refer toMain Diagnostics Screen Keypad Test Procedure Display TestBIT Patterns Test Screen RS-485 From Serial Inputs / Outputs TestsFrom From COM 4b102 Digital Inputs / Outputs Tests Analog Inputs Tests System Commissioning Checklist Part Number and Renewal Parts 107 108 109 SI Metric Conversion 110Page ALL Rights Reserved

00497VIP specifications

York 00497VIP is an innovative system designed to enhance efficiency and comfort in residential and light commercial environments. Central to its appeal is its commitment to energy efficiency and environmentally friendly operation, making it a popular choice for those looking to reduce their carbon footprint.

One of the standout features of the York 00497VIP is its advanced variable speed compressor technology. This technology allows the system to adjust its cooling and heating output based on real-time demand, leading to significant energy savings. Unlike traditional systems that often operate at a single speed, the variable speed compressor modulates its output to maintain a consistent indoor climate, ensuring optimal comfort while minimizing energy consumption.

The system is equipped with a high-efficiency air handler that enhances airflow, ensuring that every corner of the space benefits from consistent temperature control. Its unique design facilitates quiet operation, making it ideal for residential spaces where noise levels need to be kept to a minimum. This whisper-quiet functioning doesn’t compromise power, as the air handler is designed to work collaboratively with the compressor to deliver efficient cooling or heating throughout the home.

York has integrated smart technology into the 00497VIP, allowing homeowners to control the system remotely via smartphone applications. This feature not only adds convenience but also enables users to monitor energy usage and adjust settings from anywhere, enhancing the possibility of energy savings.

The system also boasts advanced filtration capabilities, utilizing a multi-stage filtration system to capture dust, allergens, and other airborne particles. This technology improves indoor air quality, promoting a healthier living environment.

In terms of adaptability, the York 00497VIP is compatible with a range of smart home systems, seamlessly integrating into existing setups. This flexibility extends to its installation, as it can be tailored to fit various spaces without significant modifications to the existing infrastructure.

Built to withstand diverse environmental conditions, the York 00497VIP is constructed with durable materials, ensuring longevity and reliable performance. This combination of efficiency, smart features, and adaptability makes it an ideal choice for consumers seeking a sustainable and effective heating and cooling solution for their home or light commercial space.