York 00497VIP manual Keypad, Refer to Figures 45

Page 91

FORM 50.40-OM2

KEYPAD

(REFER TO FIGURES 45 & 46)

The Keypad contains touch-sensitive keys that allow the Operator to interface with the Control Center. The Operator presses the keys to request the desired screens of information and enter System Setpoints.

The top layer of the Keypad contains embossed areas identifying the keys. Under each embossed key area are two conductors, one on top of the other, separated by an air space. The conductors are arranged in a matrix of rows and columns and connected to the Keypad connector as shown in Fig. 46. The embossed area of each key is located directly over the intersection point of the conductors. Pressing the embossed key area causes contact and electrical continuity between the two conductors. For example, pressing the “1” key creates continuity between the Keypad connector pin 5 (column 3) and pin 13 (row 4). Since this connector is interfaced to the Microboard (J18), the Microboard senses this continuity as described below and concludes the “1” key is pressed.

The Microboard Program continuously scans the Keypad to determine if a key is pressed. Beginning with row 1 and proceeding through all rows, the Program places a “logic low” (<1VDC) on a row, a “logic high” (>4VDC) on the remaining rows and reads the columns. A logic low in any column indicates a key in that column and row is pressed. For example, if at the time row 4 is being driven low, if column 3 is low, then the Micro

concludes the key at coordinate of row 4 and column 3 is pressed. Since the coordinates of all keys are stored in the Microboard’s Program, it can identify which key is at this coordinate and responds accordingly. In this example the “1” key is pressed.

In order for the Microboard to reliably detect closed and open keys, each key must meet a closed circuit and open circuit resistance requirement. When a key is pressed, the contact resistance must be < 100 Ohms. When a key is not pressed, the contact resistance must be > 1 Meg Ohm. If the Microboard is not responding to a pressed key, or if it’s detecting a closed key when none are pressed, it could be because the contact resistance requirements are not being met. The operation of each key can be checked with an Ohmmeter. To check the open and closed contact resistance of any key, refer to the “Diagnostics and Troubleshooting” description in this book.

The Keypad is attached to the front of the Remote Control Center door with an adhesive backing. If service replacement is required, start at one corner and slowly peel the Keypad from the door. The rear side of the replacement Keypad is coated with an adhesive covered with a paper backing. Remove the paper backing, align the Display opening and apply the Keypad to the door.

5

YORK INTERNATIONAL

91

Image 91
Contents Optiview Remote Control Center Remote Control CenterSafety Symbols General Safety GuidelinesChangeability of this Document Table of Contents List of Tables List of Figures EU Declaration of Conformity Product Description CHILLER/CONDENSING Control Panels Installation Required Software Version Chiller / Condensing Unit Eproms Optiview Remote Control Center From Optiview RCC Unit Microboard Unit Microboard 031-01314-000 031-02050-001Voltage Source Figure Wire SizingWiring Practices Figure Ground Wire Size FigureGrounding Sides or bottom of the panel and use a conduit drain Do not drill a control panel to locate conduit conOperation Manual Controls Screen Descriptions and UsageSetpoint / Change Schedule SetpointsScreen Navigation Layout This page intentionally left blank to maintain formatting Unit Status Unit Control TemperatureHome Screen Unit TypeAverage Ambient Temperature Unit Run Indicator LEDUnit # Ycal Chiller Unit Screen ExamplesYcas Chiller Ycws Chiller Unit Screen This page intentionally left blank Systems Screen Examples 00507VIPC Systems Screen Individual System Screen None Hours and Starts Screen Operating Hours Total StartsYcas Chiller / Ycar Chiller Options ScreenLanguage Display Mode Units Display ModeAmbient Control Mode Local/Remote Control ModeTrending Trending ScreenAxis Trend SetupStart StopChart Type Trend Setup ScreenCollection Interval Data Point Max SelectData Point Slot # Data Point MinThis page intentionally left blank This page intentionally left blank Setpoints Screen Examples 00517VIPC Setpoints Screen Print All Histories Last FaultsHistory Screen Print HistoryHistory Printout History Details ScreenDown RCC Setpoints Screen SetupNumber of Units Connected Set Time RCC Setup ScreenClock Enabled / Disabled Set DatePrinter DiagnosticsUnits CommsRS-485 Baud Rate Comms ScreenRCC Poll Time 5-30 sec Printer Screen Software Versions Diagnostics ScreenRCC Comms Digital Inputs Diagnostics I/O ScreenDiagnostics RCC Comms Screen Clear Counters Timeout CountStatus Messages Display MessagesPrinters PrintersOkidata 182, 182 turbo, 184 turbo Equipped with an RS-232 Serial interface OkidataWeigh-Tronix Models 2600 SeikoModel ConnectorsHardware required WEIGH-TRONIX PrinterAutomatic Data Logging Printer SetupLocal/Remote Control Mode Suction Temperature = 42.9 F Discharge Temperature Introduction ServiceRefer to FIG System ArchitectureControl Center Refer to MicroboardMini-card checksum Fpga configurationFirst initiate table complete Mini-card signature testService York International Bios Eprom U45 Flash Memory Card Bram Bios Eprom Flash Memory Card From Microboard Program Jumpers Pins 1-2 RS-232 Pins 2-3 RS-485 JP10 JP26 Not usedWatchdog protection as follows JP39, JP40, JP41, JP42 Not used JP34, JP35, JP36, JP37 Not UsedTion! Severe compressor or chiller Microboard Program SwitchesMicroboard Serial Data Communications Ports Configurable Analog Inputs Ment Displays or supporting components cannot be Liquid Crystal DisplayDisplay Replacement Kit Sharp LQ10D367 Display Refer to Removal InstallationLG Semicon LP104V2 Display refer to Removal DISPLAY, Mounting Liquid Crystal Display Assembly LG Semicon LP104V2 Display Sharp LQ10D367 Lamp Replacement 031-01765-001 Display Interface Board031-01765-002 Display Interface Board Display Backlight Inverter Board Inverter Refer to Figures 45 KeypadKeypad LD04075 Power Supply Power Supply Refer to Offline Diagnostics & TroubleshootingMain Diagnostics Screen Keypad Test Display Test ProcedureBIT Patterns Test Screen From COM 4b Serial Inputs / Outputs TestsFrom RS-485 From102 Digital Inputs / Outputs Tests Analog Inputs Tests System Commissioning Checklist Part Number and Renewal Parts 107 108 109 110 SI Metric ConversionPage ALL Rights Reserved

00497VIP specifications

York 00497VIP is an innovative system designed to enhance efficiency and comfort in residential and light commercial environments. Central to its appeal is its commitment to energy efficiency and environmentally friendly operation, making it a popular choice for those looking to reduce their carbon footprint.

One of the standout features of the York 00497VIP is its advanced variable speed compressor technology. This technology allows the system to adjust its cooling and heating output based on real-time demand, leading to significant energy savings. Unlike traditional systems that often operate at a single speed, the variable speed compressor modulates its output to maintain a consistent indoor climate, ensuring optimal comfort while minimizing energy consumption.

The system is equipped with a high-efficiency air handler that enhances airflow, ensuring that every corner of the space benefits from consistent temperature control. Its unique design facilitates quiet operation, making it ideal for residential spaces where noise levels need to be kept to a minimum. This whisper-quiet functioning doesn’t compromise power, as the air handler is designed to work collaboratively with the compressor to deliver efficient cooling or heating throughout the home.

York has integrated smart technology into the 00497VIP, allowing homeowners to control the system remotely via smartphone applications. This feature not only adds convenience but also enables users to monitor energy usage and adjust settings from anywhere, enhancing the possibility of energy savings.

The system also boasts advanced filtration capabilities, utilizing a multi-stage filtration system to capture dust, allergens, and other airborne particles. This technology improves indoor air quality, promoting a healthier living environment.

In terms of adaptability, the York 00497VIP is compatible with a range of smart home systems, seamlessly integrating into existing setups. This flexibility extends to its installation, as it can be tailored to fit various spaces without significant modifications to the existing infrastructure.

Built to withstand diverse environmental conditions, the York 00497VIP is constructed with durable materials, ensuring longevity and reliable performance. This combination of efficiency, smart features, and adaptability makes it an ideal choice for consumers seeking a sustainable and effective heating and cooling solution for their home or light commercial space.