TABLE 14: ELECTRICAL DATA DH102 (8-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET

 

 

 

 

 

 

 

Pwr

 

 

 

Min. Circuit

MCA w/Power

 

 

Max Fuse Size

 

 

 

OD Fan

Supply Blower

Pwr Exh

 

 

 

Max Fuse*

w/Power

 

Compressors

Conv

 

 

 

Ampacity

Exhaust

Voltage

 

 

Motors

Motor FLA

Motor

Outlet

Electric Heater

Actual

Heater

(Amps)

(Amps)

Size (Amps)

Exhaust

 

 

 

 

 

 

Model No.

KW

Amps

 

 

(Amps)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RLA

LRA

FLA

3 HP

3 HP

FLA

FLA

 

 

 

3 HP

3 HP

3 HP

3 HP

3 HP

3 HP

3 HP

3 HP

 

ea.

ea.

ea.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

44.2

44.2

49.7

49.7

50

50

60

60

 

 

 

 

 

 

 

 

2TP04540925

6.8

18.9

44.2

44.2

49.7

49.7

50

50

60

60

208

11.7

88.0

3.5

10.9

10.9

5.5

0.0

2TP04541825

13.5

37.5

60.5

60.5

67.3

67.3

70

70

70

70

 

 

 

 

 

 

 

 

2TP04542425

18

50.0

76.1

76.1

83.0

83.0

80

80

90

90

 

 

 

 

 

 

 

 

2TP04543625

25.5

70.8

102.1

102.1

109.0

109.0

110

110

110

110

 

 

 

 

 

 

 

 

None

--

--

44.2

44.2

50.4

50.4

50

50

60

60

 

 

 

 

 

 

 

 

2TP04540925

9

21.7

44.2

44.2

50.4

50.4

50

50

60

60

230

11.7

88.0

3.5

10.9

10.9

5.5

0.0

2TP04541825

18

43.3

67.8

67.8

74.6

74.6

70

70

80

80

 

 

 

 

 

 

 

 

2TP04542425

24

57.7

85.8

85.8

92.7

92.7

90

90

100

100

 

 

 

 

 

 

 

 

2TP04543625

34

81.8

115.9

115.9

122.7

122.7

125

125

125

125

 

 

 

 

 

 

 

 

None

--

--

22.9

22.9

25.1

25.1

25

25

30

30

 

 

 

 

 

 

 

 

2TP04540946

9

11.3

22.9

22.9

25.1

25.1

25

25

30

30

460

6.4

42.0

1.6

5.3

5.3

2.2

0.0

2TP04541846

18

22.6

33.7

33.7

36.4

36.4

35

35

40

40

 

 

 

 

 

 

 

 

2TP04542446

24

30.1

42.7

42.7

45.5

45.5

45

45

50

50

 

 

 

 

 

 

 

 

2TP04543646

34

42.7

57.7

57.7

60.5

60.5

60

60

70

70

 

 

 

 

 

 

 

 

None

--

--

18.2

18.2

20

20

20

20

25

25

 

 

 

 

 

 

 

 

2TP04540958

9

9.0

18.2

18.2

20

20

20

20

25

25

575

5.1

36.0

1.3

4.1

4.1

1.8

0.0

2TP04541858

18

18.1

26.8

26.8

29

29

30

30

30

30

 

 

 

 

 

 

 

 

2TP04542458

24

24.1

34

34

36.2

36.2

35

35

40

40

 

 

 

 

 

 

 

 

2TP04543658

34

34.1

46

46

48.3

48.3

50

50

50

50

TABLE 15: ELECTRICAL DATA DH102 (8-1/2 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET

 

 

 

 

 

 

 

Pwr

 

 

 

Min. Circuit

MCA w/Power

 

 

Max Fuse Size

 

 

 

OD Fan

Supply Blower

Pwr Exh

 

 

 

Max Fuse*

w/Power

 

Compressors

Conv

 

 

 

Ampacity

Exhaust

 

 

 

Motors

Motor FLA

Motor

Outlet

Electric Heater

Actual

Heater

(Amps)

(Amps)

Size (Amps)

Exhaust

Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Amps)

 

 

 

 

 

 

 

Model No.

KW

Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RLA

LRA

FLA

3 HP

3 HP

FLA

FLA

 

 

 

3 HP

3 HP

3 HP

3 HP

3 HP

3 HP

3 HP

3 HP

 

 

 

 

 

 

 

 

ea.

ea.

ea.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

None

--

--

54.2

54.2

59.7

59.7

60

60

70

70

 

 

 

 

 

 

 

 

2TP04540925

6.8

18.9

54.2

54.2

59.7

59.7

60

60

70

70

208

11.7

88.0

3.5

10.9

10.9

5.5

10.0

2TP04541825

13.5

37.5

73.0

73.0

79.8

79.8

80

80

80

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2TP04542425

18

50.0

88.6

88.6

95.5

95.5

90

90

100

100

 

 

 

 

 

 

 

 

2TP04543625

25.5

70.8

114.6

114.6

121.5

121.5

125

125

125

125

 

 

 

 

 

 

 

 

None

--

--

54.2

54.2

59.7

59.7

60

60

70

70

 

 

 

 

 

 

 

 

2TP04540925

9

21.7

54.2

54.2

59.7

59.7

60

60

70

70

230

11.7

88.0

3.5

10.9

10.9

5.5

10.0

2TP04541825

18

43.3

80.3

80.3

87.1

87.1

90

90

90

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2TP04542425

24

57.7

98.3

98.3

105.2

105.2

100

100

110

110

 

 

 

 

 

 

 

 

2TP04543625

34

81.8

128.4

128.4

135.2

135.2

150

150

150

150

 

 

 

 

 

 

 

 

None

--

--

27.9

27.9

30.1

30.1

30

30

35

35

 

 

 

 

 

 

 

 

2TP04540946

9

11.3

27.9

27.9

30.1

30.1

30

30

35

35

460

6.4

42.0

1.6

5.3

5.3

2.2

10.0

2TP04541846

18

22.6

39.9

39.9

42.7

42.7

40

40

45

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2TP04542446

24

30.1

49

49

51.7

51.7

50

50

60

60

 

 

 

 

 

 

 

 

2TP04543646

34

42.7

64

64

66.7

66.7

70

70

70

70

 

 

 

 

 

 

 

 

None

--

--

22.2

22.2

24

24

25

25

25

25

 

 

 

 

 

 

 

 

2TP04540958

9

9.0

22.2

22.2

24

24

25

25

25

25

575

5.1

36.0

1.3

4.1

4.1

1.8

10.0

2TP04541858

18

18.1

31.8

31.8

34

34

35

35

35

35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2TP04542458

24

24.1

39

39

41.2

41.2

40

40

45

45

 

 

 

 

 

 

 

 

2TP04543658

34

34.1

51

51

53.3

53.3

60

60

60

60

20

Unitary Products Group

Image 20 Contents
Technical Guide Ashrae 90.1 CompliantTable of Contents Features All units are shipped with 2 throw-away filters installed Factory Installed Options Field Installed Accessories Low Limit / Compressor Lockout Kit Accessories Part Number Description WeightYTG-C-0606 Ton York Model Number Nomenclature 102 DH Physical Data078 DH Capacity Ratings Unit Voltage LimitationsCFM MBH EER IplvCooling Capacity DH078 6-1/2 TON Unit Cooling Capacity DH090 7-1/2 TON Unit Cooling Capacity DH102 8-1/2 TON Unit Cooling Capacity DH120 10 TON Unit Cooling Capacity DH150 12-1/2 TON Unit Return Dry Bulb F4375 5625MCA RLA LRA FLA RLA LRA FLA MCA Electric Heat Multipliers KW Cap. Multiplier240 480DH078 6-1/2 Side Shot Blower Performance DH090 7-1/2 TON Side Shot Blower Performance CFMDH102 8-1/2 TON Side Shot Blower Performance DH120 10 TON Side Shot Blower Performance DH150 12-1/2 TON Side Shot Blower Performance DH078 6-1/2 TON Down Shot Blower Performance DH090 7-1/2 TON Down Shot Blower Performance DH102 8-1/2 TON Down Shot Blower Performance DH120 10 TON Down Shot Blower Performance DH150 12-1/2 TON Down Shot Blower Performance Additional Static Resistance DH120 Additional Static Resistance DH078, 090Electric Heat Minimum Supply AIR CFM Indoor Blower SpecificationsPower Exhaust Specifications Model Shipping Operating Unit WeightUnit Model Number DH078 DH090 DH102 DH120 Detail a Detail CUnit Clearances DH078 DH090 DH102 DH120Predator Roof Curb Dimensions Rear Duct Dimensions Bottom Duct Openings from AboveDownflow Economizer Hood Detail Economizer Usage Factory Installed Downflow Economizer Field Installed Horizontal Economizer W/POWER Exhaust Slab Economizer END Return W/POWER Exhaust Cooling Unit with GAS Heat Wiring 230 Volt Diagram Cooling Unit WITH/WITHOUT Electric Heat Wiring Diagram YTG-C-0606 Description PredatorGeneral Electric Heating Section if Equipped Unit Operating CharacteristicsGAS Heating Section if Equipped Additional Factory Installed Options Other PRE-ENGINEERED Accessories Available