GUIDE SPECIFICATIONS

PREDATOR®

DH 078, 090, 102, 120 & 150, 11.5 EER

GENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK® Predator® units are convertible single packages with a com- mon footprint cabinet and common roof curb for all 6-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial appli- cations and can be easily installed on a roof curb, slab, or frame. All Predator® units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow. Independent economizer designs are used on side and down discharge applications, as well as all tonnage sizes. Predator® units are available in the following configurations: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory-installed options or field-installed accessories.

of the coils. Condensate pan shall be slide out design, con- structed of a non corrosive material, internally sloped and conforming to ASHRAE 62-B9 standards. Condensate con- nection shall be a minimum of ¾” I.D. female and be rigid mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with for- ward curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no mainte- nance. Entire blower assembly and motor shall be slide out design.

OUTDOOR (CONDENSER) FAN ASSEMBLY

DESCRIPTION

Units shall be factory assembled, single package, (Elec/Elec, Gas/Elec), designed for outdoor installation. Units shall have a minimum EER of 9.0. They shall have built in field convert- ible duct connections for down discharge supply/return or horizontal discharge supply/return and be available with fac- tory installed options or field installed accessories. The units shall be factory wired, piped and charged with R-22 refriger- ant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and ARI test proce- dures. Units shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel with exterior surfaces coated with a non-chalking, powder paint finish, certified at 1000 hour salt spray test per ASTM-B117 standards. Indoor blower sections shall be insulated with up to 1” thick insulation coated on the airside. Aluminum foil faced insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with toolless access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2” filters shall be furnished and be accessible through hinged access door. Fan perfor- mance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating bypass

The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically bal- anced for smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and staged independently. A cleaning window shall be provided on two sides of the units for coil cleaning.

REFRIGERANT COMPONENTS

Compressors:

A.Shall be fully hermetic type, direct drive, internally pro- tected with internal high-pressure relief and over temper- ature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or – 10% of the unit nameplate voltage.

B.Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.

Coils:

A.Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.

B.Evaporator and condenser coils shall be of the direct expansion, draw-thru design.

46

Unitary Products Group

Image 46 Contents
Technical Guide Ashrae 90.1 CompliantTable of Contents Features All units are shipped with 2 throw-away filters installed Factory Installed Options Field Installed Accessories Low Limit / Compressor Lockout Kit Accessories Part Number Description WeightYTG-C-0606 Ton York Model Number Nomenclature 078 DH Physical Data102 CFM DH Capacity RatingsUnit Voltage Limitations MBH EER IplvCooling Capacity DH078 6-1/2 TON Unit Cooling Capacity DH090 7-1/2 TON Unit Cooling Capacity DH102 8-1/2 TON Unit Cooling Capacity DH120 10 TON Unit 4375 Cooling Capacity DH150 12-1/2 TON UnitReturn Dry Bulb F 5625MCA RLA LRA FLA RLA LRA FLA MCA 240 Electric Heat MultipliersKW Cap. Multiplier 480DH078 6-1/2 Side Shot Blower Performance DH090 7-1/2 TON Side Shot Blower Performance CFMDH102 8-1/2 TON Side Shot Blower Performance DH120 10 TON Side Shot Blower Performance DH150 12-1/2 TON Side Shot Blower Performance DH078 6-1/2 TON Down Shot Blower Performance DH090 7-1/2 TON Down Shot Blower Performance DH102 8-1/2 TON Down Shot Blower Performance DH120 10 TON Down Shot Blower Performance DH150 12-1/2 TON Down Shot Blower Performance Additional Static Resistance DH120 Additional Static Resistance DH078, 090Power Exhaust Specifications Indoor Blower SpecificationsElectric Heat Minimum Supply AIR CFM Unit Model Number DH078 DH090 DH102 DH120 Unit WeightModel Shipping Operating Unit Clearances Detail aDetail C DH078 DH090 DH102 DH120Predator Roof Curb Dimensions Rear Duct Dimensions Bottom Duct Openings from AboveDownflow Economizer Hood Detail Economizer Usage Factory Installed Downflow Economizer Field Installed Horizontal Economizer W/POWER Exhaust Slab Economizer END Return W/POWER Exhaust Cooling Unit with GAS Heat Wiring 230 Volt Diagram Cooling Unit WITH/WITHOUT Electric Heat Wiring Diagram YTG-C-0606 General PredatorDescription GAS Heating Section if Equipped Unit Operating CharacteristicsElectric Heating Section if Equipped Additional Factory Installed Options Other PRE-ENGINEERED Accessories Available