QuickSpecs
HP ProLiant DL160 Generation 5
Standard Features
Server Power Cords | One 6' Highline | |
| NOTE: HP ProLiant DL servers no longer ship standard with NEMA power cords | |
| that allow connection to 110V US wall outlets in a home or office. ProLiant DL servers are | |
| primarily connected to PDU's in data center racks so they now ship standard with only a PDU | |
| power cord | |
| ||
| If customers require a local power cord, they can check the power cord matrix for the appropriate | |
| cord. Please see the following power cord matrix: http://www.hp.com/go/powercordmatrix. | |
|
|
|
UPS and PDU Power | Please see the UPS and PDU cable matrix that lists cable descriptions, requirements, and | |
Cord Matrix | specifications for UPS and PDU units: | |
| ||
|
|
|
Power Supply | 650 Watts, | |
| NOTE: Factory upgradeable to | |
|
|
|
System Fans | 6 system fans ship standard; | |
|
|
|
OS Support | Microsoft Windows Server 2003 R2 | |
| Microsoft Windows Server 2008 | |
| Microsoft Windows Small Business Server 2008 | |
| Microsoft Windows Essential Server 2008 | |
| Red Hat Enterprise Linux | |
| SUSE Linux Enterprise Server | |
| Sun Solaris for | |
| NOTE: For more information on HP's Certified and Supported ProLiant Servers for OS and | |
| Virtualization Software and latest listing of software drivers available for your server, please visit | |
| our Support Matrix at: http://www.hp.com/go/supportos and our driver download page | |
| http://www.hp.com/support/DL160G5. | |
|
|
|
Rack Airflow | Rack 10000 series Cabinets | |
Requirements | The increasing power of new | |
| efficiency for | |
| maximum cooling, allowing these racks to be fully loaded with servers using the latest processors. | |
| CAUTION: If a | |
| adequate airflow and to prevent damage to the equipment: | |
| Front and rear doors: If your 42U server rack includes closing front and rear doors, you must allow | |
| 5,350 sq cm (830 square inches) of hole evenly distributed from top to bottom to permit adequate | |
| airflow (equivalent to the required 64 percent open area for ventilation). | |
| Side: The clearance between the installed rack component and the side panels of the rack must | |
| be a minimum of 7 cm (2.75 inches) | |
| CAUTION: Always use blanking panels to fill all remaining empty front panel | |
| This arrangement ensures proper airflow. Using a rack without blanking panels results in improper | |
| cooling that can lead to thermal damage. |
DA - 12902 Worldwide QuickSpecs — Version 19 — 1/26/2009 | Page 9 |