York 300 warranty General, Description

Page 50

GUIDE SPECIFICATIONS

GENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility.

York's Sunline Magnum™ units are convertible single pack- age units. All models have dual independent refrigerant cir- cuits for efficient part load operation and maximum comfort control. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, replace the supply and return air panels on the rear of the unit with a side duct flange accessory. All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job.

Each unit shall have 4 condenser fan motors. A high speed drive accessory is available for applications with a higher CFM and/or static pressure requirement. All compressors include crankcase heat and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line fil- ter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch. The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with two compressor lockout circuits, a terminal strip for thermostat wiring, plus an addi- tional set of pin connectors to simplify the interface of addi- tional field controls. All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM- B117 procedures. All 208/230 and 460-volt models are ETL approved. All 208/230 and 575-volt models are CGA approved. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry an additional 4-year warranty. Aluminized steel tubular heat exchangers carry an additional 9-year warranty.

DESCRIPTION

Units shall be factory-assembled, single packaged, DJ***N Electric Cooling/Gas Heat, DJ***C/E Electric Cooling/ Optional Electric Heat, designed for outdoor mounted instal- lation. The 15,17.5, and 20 ton units shall have minimum EER ratings of 11.1. The 25 ton unit shall have a minimum EER rating of 10.5.

036-21410-001-A-0502

They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/ return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to ship- ment. All unit wiring shall be both numbered and color coded. All units shall be manufactured in a facility certified to ISO 9001 standards and the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be ETL & CGA listed, classified to ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236-M90 conditions.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 750 hours salt spray test per ASTM- B117 standards. Indoor blower section shall be insulated with a minimum 1/2" thick insulation, coated on the airside. Alumi- num foil faced insulation shall be used in the furnace com- partment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be "large" size, easily removable for servicing and mainte- nance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 2" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1" or 2" filters. Fan performance mea- suring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan perfor- mance without removing panels or creating air by-pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate con- nection shall be a minimum of 1" I.D. female and be a ridged mount connection. Unit shall incorporate a fixed outdoor air damper with an outdoor air intake opening covered with a bird screen and a rain hood painted to match the exterior of the unit.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be a belt drive assembly and include an adjustable- pitch motor pulley. Job site selected (B.H.P.) brake horse- power shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fans shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to cor- rosion resistant steel spider brackets and shall be dynami- cally balanced for smooth operation. The 4 outdoor fan motors shall be totally enclosed with permanently lubricated

50

Unitary Products Group

Image 50
Contents Technical Guide Table of Contents Sng Product Nomenclature Panels Johnson UNT Controller, DFS, APS & Phase Monitor Technicoat Condenser Coil, Phase Monitor, & Coil Guard Features FACTORY-INSTALLED Options FIELD-INSTALLED Accessories 036-21410-001-A-0502 GAS Heat Ratiings Sound Power RATING1Capacity Ratings ARI Cooling Capacities for DJ180 AT 85F Cooling Capacities for DJ180 AT 95F Cooling Capacities for DJ180 AT 105F Cooling Capacities for DJ180 AT 115F Cooling Capacities for DJ180 AT 125F 7000 Cooling Capacities for DJ210 AT 85F6500 7875Cooling Capacities for DJ210 AT 95F Cooling Capacities for DJ210 AT 105F Cooling Capacities for DJ210 AT 115F Cooling Capacities for DJ210 AT 125F 8700 Cooling Capacities for DJ240 AT 85F8000 9400Cooling Capacities for DJ240 AT 95F Cooling Capacities for DJ240 AT 105F Cooling Capacities for DJ240 AT 115F Cooling Capacities for DJ240 AT 125F 12500 Cooling Capacities for DJ300 AT 85F10000 Cooling Capacities for DJ300 AT 95F Cooling Capacities for DJ300 AT 105F Cooling Capacities for DJ300 AT 115F Cooling Capacities for DJ300 AT 125F Volt and Standard Drive Volt Standard Drive 6000 7000 8000 9000 9400 965 980 1025 1065 1125 1170 870 900 930 950 980 995 1015 6000 7000 8000 9000 9400 7500 8750 10000 11250 12500 Static RESISTANCES1 Power Exhaust PerformanceBlower Motor and Drive Data DJ Electrical Data DJ Voltage LIMITATIONS1 Physical DataElectric Heat Correction Factors KW CAP. MultiplierUtilities Entry BackUnit Dimensions Rear View Unit Dimensions DJ180, 210, 240 & 300 Rainhood Four and SIX Point Loads Unit Roof Curb Dimensions DimensionOCC General DescriptionRefrigerant Components Other Factory Installed Options 036-21410-001-A-0502 036-21410-001-A-0502 036-21410-001-A-0502 Unitary 5005 Norman Products York Group Drive 73069