York D2CG300 Adjustment Of Temperature Rise, Checking Gas Input, Gas Rate - Cubic Feet Per Hour

Page 19
ADJUSTMENT OF TEMPERATURE RISE

 

530.18-N11Y

2. Insert at least 8" of 1/4 inch tubing into each of these holes

NOTE: DE-ENERGIZE THE COMPRESSORS BEFORE TAKING ANY TEST

for sufficient penetration into the air flow on both sides of

MEASUREMENTS TO ASSURE A DRY INDOOR COIL.

the indoor coil.

 

NOTE: The tubes must be inserted and held in a position perpendicular to the air flow so that velocity pres- sure will not affect the static pressure readings.

3.Using an inclined manometer, determine the pressure drop across a dry evaporator coil. Since the moisture on an

evaporator coil may vary greatly, measuring the pressure drop across a wet coil under field conditions would be inaccurate. To assure a dry coil, the compressors should

CHECKING GAS INPUT be deactivated while the test is being run.

4.Knowing the pressure drop across a dry coil, the actual CFM through the unit and clean 2" filters, can be determined from the curve in the Pressure Drop Verses Supply Air CFM figure.

WARNING: Failure to properly adjust the total system air quan-

FIG. 18 - PRESSURE DROP ACROSS A DRY INDOOR COIL VS SUPPLY AIR CFM

tity can result in extensive blower damage.

After readings have been obtained, remove the tubes and reinstall the two 5/16" dot plugs that were removed in Step 1.

CFM =

Btuh Input x 0.8

1.08 x oF Temp. Rise

 

ADJUSTMENT OF TEMPERATURE RISE

The temperature rise (or temperature difference between the return air and the heated air from the furnace) must lie within the range shown on the ETL rating plate.

After the temperature rise has been determined, the cfm can be calculated as follows:

After about 20 minutes of operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts (about six feet from the furnace) where they will not be affected by radiant heat. Increase the blower cfm to decrease the temperature rise; decrease the blower cfm to increase the rise. Refer to the Blower Motor And Drive Data table.

BELT DRIVE BLOWER

All units have belt drive single-speed blower motors. The variable pitch pulley on the blower motor can be adjusted to obtain the desired supply air CFM. Tighten belts enough to prevent slipping. but do not over tighten. Belt deflection should be between 1/4" and 1/2" per foot. Refer to the table for Blower Motor And Drive Data.

CHECKING GAS INPUT

NATURAL GAS

1.Turn off all other gas appliances connected to the gas meter.

2.With the furnace turned on, measure the time needed for one revolution of the hand on the smallest dial on the meter. A typical gas meter usually has a 1/2 or a 1 cubic foot test dial.

3.Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour from the Gas RateTable.

TABLE 11 - GAS RATE - CUBIC FEET PER HOUR

Seconds

Size of Test Dial

for One

1/2 cu. ft.

1 cu. ft.

Rev.

 

 

4

450

900

6

300

600

8

228

450

10

180

360

12

150

300

14

129

257

16

113

225

18

100

200

20

90

180

22

82

164

24

75

150

26

69

138

28

64

129

Example: By actual measurement, it takes 13 seconds for the hand on the 1-cubic foot dial to make a revolution with just a 300,000 Btuh furnace running. Read across to the column in the table above, headed “1 Cubic Foot”, where you will see that 278 cubic feet of gas per hour are consumed by the furnace at that rate. Multiply 278 x 1050 (the Btu rating of the gas obtained from the local gas company). The result is 292,425 Btuh, which is close to the 300,000 Btuh rating of the furnace.

SECURE OWNER’S APPROVAL: When the system is functioning properly, secure the owner’s approval. Show him the location of all disconnect switches and the thermostat. Teach him how to start and stop the unit and how to adjust temperature settings within the limitations of the system.

Unitary Products Group

19

Image 19
Contents FOR YOUR SAFETY INSTALLATION INSTRUCTIONSAFETY CONSIDERATIONS FOR YOUR SAFETY If you smell gas 1.Open windowsOPERATION TABLE OF CONTENTSINSTALLATION MAINTENANCE & TROUBLESHOOTINGLOCATION INSTALLATIONLIMITATIONS TABLE 1 - UNIT APPLICATION DATAFIG. 3 - FIXED OUTDOOR AIR DAMPER SERVICE ACCESSDUCTWORK FIXED OUTDOOR AIR INTAKE DAMPERFIG. 5 - TYPICAL FIELD WIRING CONTROL WIRE SIZESTABLE 2 - GAS HEAT APPLICATION DATA POWER AND CONTROL WIRINGTHERMOSTAT OPTIONAL ELECTRIC HEATERS DCE ModelsEXTERNAL SHUT-OFF FIG. 7 - BOTTOM SUPPLY CONNECTIONL.P. UNITS, TANKS AND PIPING DCG Models FIG. 8 - VENT AND COMBUSTION AIR HOODS VENT AND COMBUSTION AIR HOODS DCG ModelsOPTIONAL ECONOMIZER/MOTORIZED DAMPER RAIN HOOD 530.18-N11Y FIG. 9 - ENTHALPY SETPOINT ADJUSTMENTUnitary Products Group TABLE 5 - ELECTRICAL DATA - BASIC UNITS TABLE 4 - PHYSICAL DATATABLE 6 - ELECTRICAL DATA - UNITS w/ELECTRIC HEAT UTILITIES ENTRY DATA FIG. 10 - DIMENSIONS & CLEARANCES - DCE & DCGCont’d DETAIL “Y” UNIT WITH RAIN HOODS ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGSREAR VIEW DETAIL “X”TABLE 7 - FOUR AND SIX POINT LOADS 4 POINT LOADS6 POINT LOADS FIG. 11- FOUR AND SIX POINT LOADSTABLE 10 - STATIC RESISTANCES TABLE 11 - POWER EXHAUST PERFORMANCETABLE 12 - BLOWER MOTOR AND DRIVE DATA PRELIMINARY OPERATION COOLING SAFETY CONTROLSOPERATION COOLING SYSTEMFIG. 12 - GAS VALVE PIPING TABLE 9 - HEAT ANTICIPATOR SETTINGHEAT ANTICIPATOR SETPOINTS GAS HEATING SEQUENCE OF OPERATIONPRE-STARTCHECK LIST TABLE 10 - LIMIT CONTROL SETTINGMANIFOLD GAS PRESSURE ADJUSTMENT START-UPPILOT CHECKOUT FIG. 15 - PROPER FLAME ADJUSTMENTBURNER AIR SHUTTER ADJUSTMENT FIG.17 - BELT ADJUSTMENTCHECKING GAS INPUT ADJUSTMENT OF TEMPERATURE RISETABLE 11 - GAS RATE - CUBIC FEET PER HOUR NORMAL MAINTENANCE MAINTENANCEFIG. 19 - TYPICAL FLUE BAFFLE INSTALLATION TROUBLESHOOTING TROUBLESHOOTING - Cont’d REPLACEMENT PARTS Code SBY Unitary Products Group530.18-N11Y
Related manuals
Manual 24 pages 39.3 Kb

D2CG300, D2CE specifications

The York D2CE and D2CG series represent cutting-edge advancements in energy-efficient chiller technology, specifically designed to optimize performance in a variety of commercial and industrial applications. These chillers are known for their ability to deliver reliable cooling while minimizing energy consumption, making them a preferred choice for businesses aiming to reduce their carbon footprint and operational costs.

One of the standout features of the York D2CE and D2CG chillers is their utilization of advanced scroll compressor technology. This technology not only enhances the reliability of the systems but also significantly improves energy efficiency, allowing for lower operational costs. The chillers are built to provide high efficiency across a diverse range of operating conditions, ensuring consistent performance during peak loads.

The D2CE series, designed primarily for air-cooled applications, benefits from a compact and modular design, allowing for flexible installation in tight spaces. Additionally, its quiet operation makes it suitable for use in noise-sensitive environments, such as healthcare facilities and educational institutions. The model is equipped with microprocessor controls that facilitate precise temperature regulation and system diagnostics, ensuring optimal operation.

Conversely, the D2CG series focuses on water-cooled applications, featuring robust construction that accommodates higher cooling capacities. This model also includes advanced heat exchanger technology, which maximizes heat transfer efficiency. The D2CG’s intelligent controls not only help in energy management but also provide remote monitoring capabilities, allowing facility managers to analyze performance and troubleshoot issues from anywhere.

Both models utilize environmentally friendly refrigerants, aligning with global regulations and promoting sustainability. Enhanced filtration options are available, enabling the units to maintain high indoor air quality by minimizing dust and other pollutants.

In addition to their energy-saving attributes, the York D2CE and D2CG chillers are designed for ease of maintenance, with accessible components and modular parts that simplify service procedures. This, coupled with their durable construction, leads to greater longevity and reliability in operation.

In summary, the York D2CE and D2CG chillers are leading examples of modern HVAC engineering, combining efficiency, flexibility, and sustainability. Their innovative technologies and thoughtful design make them an excellent addition to any facility looking to enhance its cooling systems while adhering to environmental standards.