INSTALLATION

530.18-N11Y

INSTALLATION

LIMITATIONS

These units must be installed in accordance with the following applicable national and local safety codes:

In U.S.A.:

1.National Electrical Code ANSI/NFPA No. 70.

2.National Fuel Gas Code Z223.1.

3.Gas-Fired Central Furnace Standard ANSI Z21.47a.

4.Local gas and electric utility requirements.

In Canada:

1.Current Canadian Electrical Code C22.1.

2.Current Gas Installation Codes CAN/CGA-B149.1 and .2

3.Local plumbing and waste water codes.

4.Other applicable local codes.

Refer to the Unit Application Data Table and to the Gas Heat Application Data Table.

After installation, units with gas heat must be adjusted to obtain a temperature rise within the range specified on the unit rating plate.

If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or the customer’s expense.

Size of unit for proposed installation should be based on heat loss/heat gain calculation made according to the methods of the Air Conditioning Contractors of America (ACCA).

This furnace is not to be used for temporary heating of buildings or structures under construction.

TABLE 1 - UNIT APPLICATION DATA

Voltage Variation,

208/230-3-60

187

/ 253

460-3-60

414

/ 506

Min. / Max.1

575-3-60

518

/ 630

 

Supply Air CFM, Min. / Max.

8,000 / 12,000

Wet Bulb Temperature (° F) of Air on

57

/ 72

Evaporator Coil, Min. / Max.

 

 

Dry Bulb Temperature (° F) of Air on

25 / 120

Condenser Coil, Min.2 / Max.

1Utilization range “A” in accordance with ARI Standard 110.

2A low ambient accessory is available for applications down to 0° F.

LOCATION

Use the following guidelines to select a suitable location for these units.

1.Unit is designed for outdoor installation only.

2.Condenser coils must have an unlimited supply of air. Where a choice of location is possible, position the unit on either north or east side of building.

3.For ground level installation, use a level concrete slab with a minimum thickness of 4 inches. The length and width should be at least 6 inches greater than the unit base rails. Do not tie slab to the building foundation.

WARNING: Excessive exposure of this furnace to contami- nated combustion air may result in equipment dam- age or personal injury. Typical contaminates in- clude: permanent wave solutions, chlorinated waxes and cleaners, chlorine based swimming pool chemicals, water softening chemicals, carbon tetrachloride, Halogen type refrigerants, cleaning solvents (e.g. perchloroethylene), printing inks, paint removers, varnishes, hydrochloric acid, ce- ments and glues, antistatic fabric softeners for clothes dryers, masonry acid washing materials.

4.Roof structures must be able to support the weight of the unit and its options and/or accessories. Unit must be in- stalled on a solid level roof curb or appropriate angle iron frame.

CAUTION: If a unit is to be installed on a roof curb or special frame, gasketing must be applied to all surfaces that come in contact with the unit underside.

5.Maintain level tolerance to 1/2" maximum across the entire length or width of the unit.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the round lifting holes provided in the base rails. Spreaders, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit.

Units may also be moved or lifted with a forklift, from the front or rear only, providing that an accessory skid is used.

LENGTH OF FORKS MUST BE A MINIMUM OF 90".

CAUTION: On gas heating units, an adhesive backed label is provided over the outside of the combustion air inlet opening to prevent moisture from entering the unit w hich could cause damage to electr ical components. Allow this closure label to remain in place until the combustion air hood is to be installed.

FIG. 1 - TYPICAL RIGGING

5

4

136-1/4"

FIG. 2 - CENTER OF GRAVITY

CLEARANCES

All units require certain clearances for proper operation and service. Installer must make provisions for adequate combustion and ventilation air in accordance with Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 (in U.S.A.) or Sections 7.2, 7.3 or 7.4 of Gas Installation Codes CAN/CGA-B149.1 and .2 (in Canada) and/or applicable provisions of the local building codes. Refer to Dimensions and Clearances table for the clearances required for combustible construction, servicing, and proper unit operation.

WARNING: Do not permit overhanging structures or shrubs to obstruct outdoor air discharge outlet, combustion air inlet or vent outlets.

Unitary Products Group

3

Image 3
Contents FOR YOUR SAFETY INSTALLATION INSTRUCTIONSAFETY CONSIDERATIONS FOR YOUR SAFETY If you smell gas 1.Open windowsOPERATION TABLE OF CONTENTSINSTALLATION MAINTENANCE & TROUBLESHOOTINGLOCATION INSTALLATIONLIMITATIONS TABLE 1 - UNIT APPLICATION DATAFIG. 3 - FIXED OUTDOOR AIR DAMPER SERVICE ACCESSDUCTWORK FIXED OUTDOOR AIR INTAKE DAMPERFIG. 5 - TYPICAL FIELD WIRING CONTROL WIRE SIZESTABLE 2 - GAS HEAT APPLICATION DATA POWER AND CONTROL WIRINGTHERMOSTAT OPTIONAL ELECTRIC HEATERS DCE ModelsFIG. 7 - BOTTOM SUPPLY CONNECTION EXTERNAL SHUT-OFFL.P. UNITS, TANKS AND PIPING DCG Models VENT AND COMBUSTION AIR HOODS DCG Models FIG. 8 - VENT AND COMBUSTION AIR HOODSOPTIONAL ECONOMIZER/MOTORIZED DAMPER RAIN HOOD FIG. 9 - ENTHALPY SETPOINT ADJUSTMENT 530.18-N11YUnitary Products Group TABLE 4 - PHYSICAL DATA TABLE 5 - ELECTRICAL DATA - BASIC UNITSTABLE 6 - ELECTRICAL DATA - UNITS w/ELECTRIC HEAT FIG. 10 - DIMENSIONS & CLEARANCES - DCE & DCG UTILITIES ENTRY DATACont’d DETAIL “Y” UNIT WITH RAIN HOODS ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGSREAR VIEW DETAIL “X”TABLE 7 - FOUR AND SIX POINT LOADS 4 POINT LOADS6 POINT LOADS FIG. 11- FOUR AND SIX POINT LOADSTABLE 11 - POWER EXHAUST PERFORMANCE TABLE 10 - STATIC RESISTANCESTABLE 12 - BLOWER MOTOR AND DRIVE DATA PRELIMINARY OPERATION COOLING SAFETY CONTROLSOPERATION COOLING SYSTEMFIG. 12 - GAS VALVE PIPING TABLE 9 - HEAT ANTICIPATOR SETTINGHEAT ANTICIPATOR SETPOINTS GAS HEATING SEQUENCE OF OPERATIONPRE-STARTCHECK LIST TABLE 10 - LIMIT CONTROL SETTINGMANIFOLD GAS PRESSURE ADJUSTMENT START-UPPILOT CHECKOUT FIG. 15 - PROPER FLAME ADJUSTMENTBURNER AIR SHUTTER ADJUSTMENT FIG.17 - BELT ADJUSTMENTADJUSTMENT OF TEMPERATURE RISE CHECKING GAS INPUTTABLE 11 - GAS RATE - CUBIC FEET PER HOUR MAINTENANCE NORMAL MAINTENANCEFIG. 19 - TYPICAL FLUE BAFFLE INSTALLATION TROUBLESHOOTING TROUBLESHOOTING - Cont’d REPLACEMENT PARTS Unitary Products Group Code SBY530.18-N11Y
Related manuals
Manual 24 pages 39.3 Kb

D2CG300, D2CE specifications

The York D2CE and D2CG series represent cutting-edge advancements in energy-efficient chiller technology, specifically designed to optimize performance in a variety of commercial and industrial applications. These chillers are known for their ability to deliver reliable cooling while minimizing energy consumption, making them a preferred choice for businesses aiming to reduce their carbon footprint and operational costs.

One of the standout features of the York D2CE and D2CG chillers is their utilization of advanced scroll compressor technology. This technology not only enhances the reliability of the systems but also significantly improves energy efficiency, allowing for lower operational costs. The chillers are built to provide high efficiency across a diverse range of operating conditions, ensuring consistent performance during peak loads.

The D2CE series, designed primarily for air-cooled applications, benefits from a compact and modular design, allowing for flexible installation in tight spaces. Additionally, its quiet operation makes it suitable for use in noise-sensitive environments, such as healthcare facilities and educational institutions. The model is equipped with microprocessor controls that facilitate precise temperature regulation and system diagnostics, ensuring optimal operation.

Conversely, the D2CG series focuses on water-cooled applications, featuring robust construction that accommodates higher cooling capacities. This model also includes advanced heat exchanger technology, which maximizes heat transfer efficiency. The D2CG’s intelligent controls not only help in energy management but also provide remote monitoring capabilities, allowing facility managers to analyze performance and troubleshoot issues from anywhere.

Both models utilize environmentally friendly refrigerants, aligning with global regulations and promoting sustainability. Enhanced filtration options are available, enabling the units to maintain high indoor air quality by minimizing dust and other pollutants.

In addition to their energy-saving attributes, the York D2CE and D2CG chillers are designed for ease of maintenance, with accessible components and modular parts that simplify service procedures. This, coupled with their durable construction, leads to greater longevity and reliability in operation.

In summary, the York D2CE and D2CG chillers are leading examples of modern HVAC engineering, combining efficiency, flexibility, and sustainability. Their innovative technologies and thoughtful design make them an excellent addition to any facility looking to enhance its cooling systems while adhering to environmental standards.