York D2CE, D2CG300 installation instructions TROUBLESHOOTING - Cont’d

Page 22

530.18-N11Y

TROUBLESHOOTING - Cont’d.

4.The draft motor runs but the furnace does not light and the sparker does not spark.

a.The ignition control (IC1, IC2) may be locked out due to either a flame roll out or 100% shut off. These safety features are described above. If lock-out has occurred, 24V must be removed from the ignition controls. This is done at the unit or by resetting the room thermostat. After resetting 24V, check for proper furnace operation. If lock-out continues to occur, locate the source of the problem and correct.

b.Check all 24 volt connections from the relay board to and in the gas heat section. Check low voltage connec- tions to the (ETD) located in the control box.

c.If the furnace is hot, it may be out on an over-tempera- ture condition, wait for limit reset.

d.If the furnace is cold, check for 24 volts at wire 241 attached to the electronic time delay (ETD) located in the main control box. If 24 volts is not found, replace the ETD.

e.With the draft motor running, check for 24 volts at terminal 4 of (RW1-2) and (RW2-1). If 24 volts is not present, the centrifugal switch (CS) has not closed or has gone bad. Check the line voltage to the unit - if it is correct, replace the draft motor. If line voltage is low, call the power company.

f.Check for 24V at terminal 2 of (RW1-2 and RW2-1). If 24V is not present, check for 24V at (RW1 and RW2) relay coils. If these relays are pulled in, then check for a loose connection at terminal 2 and terminal 4 of each relay. If no problem is found, then replace (RW1 and/or RW2) as required.

g.If 24 volts is present at the ignitor controls, check all control wiring at the ignitor controls and the high tension wire to the ignitors. Check that the ground wires from the ignitor controls, the gas valves and pilot burners are all intact and making good electrical connection. Check to make sure that the ceramic insulator on the pilot ignitors or sensors is not broken or cracked, if all are intact, replace the ignition control IC1 or IC2.

5.The draft motor runs and the sparker sparks at the pilot burner but the pilot does not ignite and a gas odor is not detected at the draft motor outlet.

a.Check to make sure gas is being supplied to the unit. Make sure that the gas pressure to the unit is within the proper limits as described in the “POST START CHECK LIST” and that the pilot adjust screw is allowing some flow of gas as described in “PILOT CHECKOUT”.

b.Check all wiring between the ignitor control and the gas valve. Check to make sure the ground connections are intact.

c.If the wiring is intact, check for 24 volts across terminals “PV” and “COMMON” on the ignitor control. If 24 volts is not present, replace the ignitor control.

d.If 24 volts is present, remove the pilot burner and remove the pilot orifice from the pilot burner. The orifice is removed in the direction opposite the flow of gas. Inspect the orifice for obstruction. If it is clear, replace the main gas valve.

6.The sparker sparks at the pilot burner but the pilot does not ignite and a gas odor is detected at the draft motor outlet.

a.Adjust the pilot adjust screw on the gas valve as de- scribed in “PILOT CHECKOUT”.

b.Check the supply pressure as described in “POST START CHECK LIST”. Make adjustments as necessary.

c.Check the pilot orifice for obstruction as described in para. 5d. Clean as needed but the problem should not be the gas valve.

7.The pilot burner ignites but the sparker continues to spark and the main burners do not ignite.

a.Make the same checks and adjustment as described in para. 6.

b.Make sure that the pilot burner is not bent or damaged.

c.Make sure that the ground connections at the pilot burner, gas valve and ignitor control are intact. Check the high tension wire for good electrical connection. If all are intact, replace the ignitor module.

8.The pilot burner lights and the spark stops but the main burners do not light.

a.Check electrical connections between the ignitor con- trol and the gas valve. If intact, check for 24 volts across terminals “MV” and “COMMON” terminals. If no voltage detected, replace ignitor control. If voltage is present, replace gas valve.

9.Furnace lights with roll-out or one burner has delayed ignition.

a.Make sure that the pilot burner is aligned properly with the carryover as described in “PILOT CHECKOUT”.

b.Make sure that the carryovers on adjoining burners are screwed fast and are level with respect to one another.

10.Main burners light but exhibit erratic flame characteristics.

a.Adjust air shutters as described in “BURNER AIR SHUTTER ADJUSTMENT”.

b.Check the main burner orifices for obstruction and alignment. Removal procedure is described in “BURNER INSTRUCTIONS”. Clean or replace burner orifices and burners as needed.

22

Unitary Products Group

Image 22
Contents FOR YOUR SAFETY If you smell gas 1.Open windows INSTALLATION INSTRUCTIONSAFETY CONSIDERATIONS FOR YOUR SAFETYMAINTENANCE & TROUBLESHOOTING TABLE OF CONTENTSINSTALLATION OPERATIONTABLE 1 - UNIT APPLICATION DATA INSTALLATIONLIMITATIONS LOCATIONFIXED OUTDOOR AIR INTAKE DAMPER SERVICE ACCESSDUCTWORK FIG. 3 - FIXED OUTDOOR AIR DAMPERCONTROL WIRE SIZES FIG. 5 - TYPICAL FIELD WIRINGOPTIONAL ELECTRIC HEATERS DCE Models POWER AND CONTROL WIRINGTHERMOSTAT TABLE 2 - GAS HEAT APPLICATION DATAEXTERNAL SHUT-OFF FIG. 7 - BOTTOM SUPPLY CONNECTIONL.P. UNITS, TANKS AND PIPING DCG Models FIG. 8 - VENT AND COMBUSTION AIR HOODS VENT AND COMBUSTION AIR HOODS DCG ModelsOPTIONAL ECONOMIZER/MOTORIZED DAMPER RAIN HOOD 530.18-N11Y FIG. 9 - ENTHALPY SETPOINT ADJUSTMENTUnitary Products Group TABLE 5 - ELECTRICAL DATA - BASIC UNITS TABLE 4 - PHYSICAL DATATABLE 6 - ELECTRICAL DATA - UNITS w/ELECTRIC HEAT UTILITIES ENTRY DATA FIG. 10 - DIMENSIONS & CLEARANCES - DCE & DCGCont’d DETAIL “X” ACCESSORY SIDE SUPPLY AND RETURN AIR OPENINGSREAR VIEW DETAIL “Y” UNIT WITH RAIN HOODSFIG. 11- FOUR AND SIX POINT LOADS 4 POINT LOADS6 POINT LOADS TABLE 7 - FOUR AND SIX POINT LOADSTABLE 10 - STATIC RESISTANCES TABLE 11 - POWER EXHAUST PERFORMANCETABLE 12 - BLOWER MOTOR AND DRIVE DATA COOLING SYSTEM SAFETY CONTROLSOPERATION PRELIMINARY OPERATION COOLINGGAS HEATING SEQUENCE OF OPERATION TABLE 9 - HEAT ANTICIPATOR SETTINGHEAT ANTICIPATOR SETPOINTS FIG. 12 - GAS VALVE PIPINGSTART-UP TABLE 10 - LIMIT CONTROL SETTINGMANIFOLD GAS PRESSURE ADJUSTMENT PRE-STARTCHECK LISTFIG.17 - BELT ADJUSTMENT FIG. 15 - PROPER FLAME ADJUSTMENTBURNER AIR SHUTTER ADJUSTMENT PILOT CHECKOUTCHECKING GAS INPUT ADJUSTMENT OF TEMPERATURE RISETABLE 11 - GAS RATE - CUBIC FEET PER HOUR NORMAL MAINTENANCE MAINTENANCEFIG. 19 - TYPICAL FLUE BAFFLE INSTALLATION TROUBLESHOOTING TROUBLESHOOTING - Cont’d REPLACEMENT PARTS Code SBY Unitary Products Group530.18-N11Y
Related manuals
Manual 24 pages 39.3 Kb

D2CG300, D2CE specifications

The York D2CE and D2CG series represent cutting-edge advancements in energy-efficient chiller technology, specifically designed to optimize performance in a variety of commercial and industrial applications. These chillers are known for their ability to deliver reliable cooling while minimizing energy consumption, making them a preferred choice for businesses aiming to reduce their carbon footprint and operational costs.

One of the standout features of the York D2CE and D2CG chillers is their utilization of advanced scroll compressor technology. This technology not only enhances the reliability of the systems but also significantly improves energy efficiency, allowing for lower operational costs. The chillers are built to provide high efficiency across a diverse range of operating conditions, ensuring consistent performance during peak loads.

The D2CE series, designed primarily for air-cooled applications, benefits from a compact and modular design, allowing for flexible installation in tight spaces. Additionally, its quiet operation makes it suitable for use in noise-sensitive environments, such as healthcare facilities and educational institutions. The model is equipped with microprocessor controls that facilitate precise temperature regulation and system diagnostics, ensuring optimal operation.

Conversely, the D2CG series focuses on water-cooled applications, featuring robust construction that accommodates higher cooling capacities. This model also includes advanced heat exchanger technology, which maximizes heat transfer efficiency. The D2CG’s intelligent controls not only help in energy management but also provide remote monitoring capabilities, allowing facility managers to analyze performance and troubleshoot issues from anywhere.

Both models utilize environmentally friendly refrigerants, aligning with global regulations and promoting sustainability. Enhanced filtration options are available, enabling the units to maintain high indoor air quality by minimizing dust and other pollutants.

In addition to their energy-saving attributes, the York D2CE and D2CG chillers are designed for ease of maintenance, with accessible components and modular parts that simplify service procedures. This, coupled with their durable construction, leads to greater longevity and reliability in operation.

In summary, the York D2CE and D2CG chillers are leading examples of modern HVAC engineering, combining efficiency, flexibility, and sustainability. Their innovative technologies and thoughtful design make them an excellent addition to any facility looking to enhance its cooling systems while adhering to environmental standards.