TABLE 5 - ELECTRICAL DATA (COOLING / ELECTRIC HEAT)
DEB |
| COMPRESSOR | COND. | SUPPLY | ELECTRIC HEAT ACCESSORY |
| MAX. | MAX. | ||||||
|
|
|
|
|
|
|
| MINIMUM | ||||||
| POWER |
|
| FAN | AIR |
|
|
|
|
| FUSE | HACR2 | ||
MODEL | SUPPLY |
|
| MOTOR | BLOWER |
| STAGE |
|
|
| CIRCUIT | SIZE,1 | BREAKER | |
|
|
| FLA | MOTOR, |
|
|
| TOTAL | AMPACITY | AMPS | SIZE | |||
|
|
|
|
|
|
|
| |||||||
|
| RLA | LRA | FLA | MODEL NO. |
| KW |
|
| |||||
|
|
|
|
| AMPS |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
018 | 9.0 | 48.0 | 1.1 | 2.6 | 2NH04500506 | 1 | 3.8/5.0 | * | 18.1/20.8 | 25.8/29.3 | 30/30 | 30/30 | ||
2NH04500706 | 2 | 5.6/7.5 | * | 27.1/31.3 | 37.1/42.3 | 40/45 | 40/45 | |||||||
|
|
|
|
|
| |||||||||
|
|
|
|
|
| 2NH04500506 | 1 | 3.8/5.0 | * | 18.1/20.8 | 25.8/29.3 | 30/30 | 30/30 | |
024 | 11.2 | 60.0 | 1.1 | 2.6 | 2NH04500706 | 2 | 5.6/7.5 | * | 27.1/31.3 | 37.1/42.3 | 40/45 | 40/45 | ||
|
|
|
|
|
| 2NH04501006 | 2 | 7.5/10.0 | * | 36.1/41.7 | 48.4/55.3 | 50/60 | 50/60 | |
|
|
|
|
|
| 2NH04500506 | 1 | 3.8/5.0 | * | 18.1/20.8 | 25.8/29.3 | 30/30 | 30/30 | |
030 | 12.0 | 73.0 | 1.1 | 2.6 | 2NH04500706 | 2 | 5.6/7.5 | * | 27.3/31.3 | 37.1/42.3 | 40/45 | 40/45 | ||
2NH04501006 | 2 | 7.5/10.0 | * | 36.1/41.7 | 48.4/55.3 | 50/60 | 50/60 | |||||||
|
|
|
|
|
| |||||||||
|
|
|
|
|
| 2NH04501506 | 2 | 11.3/15.0 | * | 54.2/62.5 | 71.0/81.4 | 80/90 | 80/90 | |
036 | 17.3 | 94.0 | 1.1 | 3.5 | 2NH04501006 | 2 | 7.5/10.0 | * | 36.1/41.7 | 49.5/56.5 | 50/60 | 50/60 | ||
2NH04501506 | 2 | 11.3/15.0 | * | 54.2/62.5 | 72.1/82.5 | 80/90 | 80/90 | |||||||
|
|
|
|
|
| |||||||||
|
|
|
|
|
| 2NH04500506 | 1 | 3.8/5.0 | * | 18.1/20.8 | 30.2/30.4 | 40/40 | 40/40 | |
042 | 20.5 | 120.0 | 1.1 | 3.5 | 2NH04500706 | 2 | 5.6/7.5 | * | 27.1/31.3 | 38.2/43.4 | 50/50 | 50/50 | ||
2NH04501006 | 2 | 7.5/10.0 | * | 36.1/41.7 | 49.5/56.5 | 50/60 | 50/60 | |||||||
|
|
|
|
|
| |||||||||
|
|
|
|
|
| 2NH04501506 | 2 | 11.3/15.0 | * | 54.2/62.5 | 72.1/82.5 | 80/90 | 80/90 | |
|
|
|
|
|
| 2NH04501006 | 2 | 7.5/10.0 | * | 36.1/41.7 | 50.1/57.1 | 60/60 | 60/60 | |
048 | 24.4 | 140.0 | 1.3 | 4.0 | 2NH04501506 | 2 | 11.3/15.0 | * | 54.2/62.5 | 72.1/83.1 | 80/90 | 80/90 | ||
2NH04502006 | 2 | 15.0/20.0 | * | 72.2/83.3 | 95.3/109.2 | 100/110 | 100/110 | |||||||
|
|
|
|
|
| |||||||||
|
|
|
|
|
| 2NH04502506 | 2 | 18.8/25.0 | * | 90.3/104.2 | 117.8/135.2 | 125/150 | 125/150 | |
|
|
|
|
|
| 2NH04501006 | 2 | 7.5/10.0 | * | 36.1/41.7 | 53.9/60.8 | 70/70 | 70/70 | |
060 | 28.9 | 165.0 | 1.3 | 7.0 | 2NH04501506 | 2 | 11.3/15.0 | * | 54.2/62.5 | 76.5/86.9 | 80/90 | 80/90 | ||
2NH04502006 | 2 | 15.0/20.0 | * | 72.2/83.3 | 99.0/112.9 | 100/125 | 100/125 | |||||||
|
|
|
|
|
| |||||||||
|
|
|
|
|
| 2NH04502506 | 2 | 18.8/25.0 | * | 90.3/104.2 | 121.6/139.0 | 125/150 | 125/150 |
= Dual element, time delay type.
=Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.
*= KW listed is for 240 volts, use table on previous page for 208 or 230 volts. ** = KW listed is for 480 volts, use table on previous page for 460 volts.
6 | Unitary Products Group |