TABLE 10 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB042

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,400 CFM/TON

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

75

 

 

 

65

20.3

21.9

 

23.5

25.0

26.6

28.1

29.7

30.6

31.6

 

32.6

33.6

70

16.7

18.5

 

20.3

22.1

23.9

25.7

27.5

28.6

29.7

 

30.8

32.0

75

13.0

15.1

 

17.1

19.2

21.2

23.2

25.3

26.6

27.8

 

29.1

30.4

80

9.4

11.7

 

13.9

16.2

18.5

20.8

23.1

24.5

25.9

 

27.3

28.7

85

5.7

8.2

 

10.8

13.3

15.8

18.4

20.9

22.5

24.0

 

25.6

27.1

90

-

6.5

 

9.1

11.7

14.2

16.8

19.4

21.0

22.6

 

24.1

25.7

95

-

-

 

7.4

10.0

12.7

15.3

17.9

19.5

21.1

 

22.7

24.3

100

-

-

 

5.8

7.9

10.0

12.0

14.1

16.3

18.4

 

20.6

22.8

105

-

-

 

-

5.8

7.3

8.7

10.2

13.0

15.8

 

18.6

21.4

110

-

-

 

-

-

-

5.5

6.4

9.8

13.2

 

16.5

19.9

115

-

-

 

-

-

-

-

-

6.5

10.5

 

14.5

18.5

TABLE 11 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB048

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 1,600 CFM/TON

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

75

 

 

 

65

13.5

15.4

 

17.3

19.1

21.0

22.8

24.7

26.1

27.6

 

29.0

30.5

70

10.7

12.7

 

14.7

16.8

18.8

20.9

22.9

24.7

26.5

 

28.2

30.0

75

7.8

10.0

 

12.2

14.5

16.7

18.9

21.2

23.3

25.4

 

27.5

29.6

80

-

7.3

 

9.7

12.1

14.5

17.0

19.4

21.8

24.2

 

26.7

29.1

85

-

-

 

7.2

9.8

12.4

15.0

17.6

20.4

23.1

 

25.9

28.6

90

-

-

 

6.1

7.7

9.4

11.0

12.7

16.6

20.5

 

24.4

28.3

95

-

-

 

-

5.7

6.3

7.0

7.7

12.7

17.8

 

22.8

27.9

100

-

-

 

-

5.3

5.9

6.5

7.1

11.1

15.1

 

19.1

23.0

105

-

-

 

-

-

5.5

6.0

6.6

9.5

12.4

 

15.3

18.2

110

-

-

 

-

-

5.0

5.5

6.0

7.8

9.7

 

11.6

13.4

115

-

-

 

-

-

-

-

5.4

6.2

7.0

 

7.8

8.6

TABLE 12 - SUPERHEAT CHARGING TABLE FOR MODEL D2EB060

OUTDOOR

 

 

SUPERHEAT AT COMPRESSOR SUCTION (F), AIRFLOW = 2,000 CFM/TON

 

 

TEMPERATURE

 

 

 

 

 

INDOOR WB TEMPERATURE (F)

 

 

 

 

 

(F)

55

57

 

59

61

63

65

67

69

71

 

73

75

 

 

 

65

25.3

25.8

 

26.3

26.8

27.3

27.8

28.3

28.7

29.1

 

29.6

30.0

70

22.2

23.0

 

23.7

24.4

25.1

25.9

26.6

27.4

28.2

 

28.9

29.7

75

19.2

20.1

 

21.1

22.1

23.0

24.0

24.9

26.1

27.2

 

28.3

29.4

80

16.1

17.3

 

18.5

19.7

20.9

22.1

23.3

24.7

26.2

 

27.7

29.1

85

13.1

14.5

 

15.9

17.3

18.8

20.2

21.6

23.4

25.2

 

27.0

28.9

90

10.3

11.7

 

13.1

14.5

15.9

17.3

18.6

21.1

23.5

 

25.9

28.3

95

7.6

8.9

 

10.3

11.6

13.0

14.3

15.7

18.7

21.8

 

24.8

27.8

100

6.6

7.7

 

8.9

10.1

11.3

12.5

13.6

16.7

19.7

 

22.7

25.8

105

5.6

6.6

 

7.6

8.6

9.6

10.6

11.6

14.6

17.6

 

20.7

23.7

110

-

5.4

 

6.2

7.0

7.9

8.7

9.5

12.5

15.6

 

18.6

21.6

115

-

-

 

-

5.5

6.2

6.8

7.5

10.5

13.5

 

16.5

19.5

Unitary Products Group

9

Image 9
Contents REPLACEMENT PARTS INSTALLATION INSTRUCTIONGENERAL REFERENCELIMITATIONS INSTALLATIONTABLE 1 - UNIT APPLICATION DATA LOCATIONCLEARANCES SERVICE ACCESSDUCT WORK FILTERSFIG. 2 - TYPICAL FIELD WIRING DIAGRAM POWER AND CONTROL WIRINGCONTROL WIRING POWER WIRINGTABLE 4 - ELECTRICAL DATA BASIC UNIT TABLE 5 - ELECTRICAL DATA COOLING / ELECTRIC HEAT DEB Coil Delta P vs Airflow Checking Supply Air CFM174065-YIM-A-0206 174065-YIM-A-0206 FRONT FIG. 3 - DIMENSIONS AND CLEARANCESFRONT 14 BACKSEQUENCE OF OPERATION CoolingHeating NORMAL MAINTENANCE MAINTENANCESEE DETAIL B DETAIL ATYPICAL WIRING DIAGRAM NOTES TYPICAL WIRING DIAGRAM LEGEND174065-YIM-A-0206 Unitary Products GroupUnitary Products Group 174065-YIM-A-02065005 York Drive, Norman Oklahoma Unitary Products GroupSupersedes Nothing 174065-YIM-A-0206