York D1EE036, D1EG warranty FACTORY-INSTALLED Options, FIELD-INSTALLED Accessories

Page 4

voltage terminal strip. An additional set of pin connectors is also provided to simplify the field interface of external con- trols. Mate--n--lock plug connectors are used where line and low voltage wires pass through internal bulkheads. This allows for easier troubleshooting and component replace- ment. The electrical control box is not located in the compres- sor compartment so the access cover can be removed for troubleshooting without affecting the normal system operat- ing pressures.

AIR FILTERS -- Units are shipped with 1" throwaway filters. The unit filter racks can accommodate 1" or 2" filters without any modifications.

FACTORY-INSTALLED OPTIONS

ECONOMIZERS: Units equipped with a factory-installed economizer option have dampers that are positioned by a spring return, fully modulating damper actuator and are capa- ble of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is determined by a single input electronic enthalpy control or by a dual input electronic enthalpy control. Simulta- neous compressor and economizer operation is also possi- ble.

The single enthalpy system contains a sensor that monitors the outdoor air which automatically operates the damper actuator allowing the dampers to open or close.

The dual enthalpy system contains a second sensor that monitors both the temperature and the humidity of the return air in addition to the outdoor air sensor described for a single enthalpy system. The logic module compares the inputs from both sensors and switches to economizer operation when- ever the outdoor air is cooler than the return air for maximum efficiency of the economizer system.

The economizer is completely wired and installed at the fac- tory. Only the outdoor air hood, including its filters, need be assembled and installed in the field.

BELT DRIVE BLOWERS: Adjustable belt-drive blowers pro- viding maximum flexibility to handle many airflow require- ments, are available on all models.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZER - Includes a slide-in / plug-in damper assembly with fully modu- lating spring return motor actuator capable of introducing up to 100% outdoor air, one outdoor air electronic enthalpy sen- sor and a rain hood with filters. The rain hood is painted to match the basic unit and must be field-assembled before installation. Economizer dampers are 2% low leakage type.

036-21411-002-A-0204

DUAL INPUT ELECTRONIC ENTHALPY ECONOMIZER - Includes the same damper system and rain hood with filters as described for a single enthalpy economizer except this accessory contains two enthalpy sensors. It uses a differen- tial enthalpy control that compares the outdoor air versus the return air. The logic module then optimizes the economizer operation for additional savings over the single input econo- mizer.

MOTORIZED AIR DAMPER - Includes a slid-in/plug-in damper assembly with a rainhood and filters. The outdoor air dampers open when the indoor fan motor is energized. The damper is capable of providing 0% through 100% of outdoor return air opening.

MANUAL OUTDOOR DAMPER - Provides 0% through 35% or 0% through 100% of return air opening (field adjustable). Designed for duct mounted side or bottom supply/return applications. Includes rain hood assembly and filter.

ELECTRIC HEATERS - Include nickel chromium elements, a terminal block, fuses (where required by UL), all the neces- sary connectors and hardware. All heaters utilize single point power supply hookup. Capacities from 5 KW through 30 KW heating are available.

FUSE BLOCK KITS - These kits have a fuse box with a fuse block and fuses. They're available for all 460-3-60 volt heat- ers and 208/230-3-60 volt heaters 7 KW and smaller.

OUTDOOR THERMOSTAT - A 24-volt thermostat providing two stages of control for units equipped with electric heat accessories.

ROOF CURB - This 14" high full perimeter roof curb is shipped knocked down for field assembly and contains duct supports that can easily be shifted for the desired unit duct arrangement. No insulated deck is required because the unit underside is insulated.

START ASSIST KIT - Provides increased starting torque for single phase units in areas with low voltage conditions. It con- tains a 12.5 OHM PTCR temperature resistor with a support clip and hardware for mounting.

LOW AMBIENT KIT - A head pressure controller maintains stable system operation by reducing the speed of the con- denser fan motor when the outdoor temperature is between 45 and 0 ºF. Condenser fan motors with ball bearings and heavier windings are also available for these low ambient applications.

ANTI-RECYCLE TIMER - A timer to prevent the unit com- pressor from short cycling. It assures a 5-minute off-time between compressor cycles.

4

Unitary Products Group

Image 4
Contents Flexible Easy to Install Single Package Units Technical Guide Sunline Plus AIR-COOLED AIR ConditionersGeneral FeaturingTable of Contents Features DescriptionFACTORY-INSTALLED Options FIELD-INSTALLED AccessoriesSunline Plus Component Location Capacity Ratings Cooling / Electric Heating Sound Power RATINGS1Capacity Ratings Cooling / GAS Heating Physical Data Basic Unit Models DEE/DEGAIR on Temperature of AIR on Condenser Coil Total PowerCooling Capacities 3 TON DEE / DEG036 Evaporator Sensible CAPACITY1, MBHCooling Capacities 4 TON DEE / DEG048 Cooling Capacities 5 TON DEE / DEG060 Model AIR Available External Static Pressure IWG3 Flow CFM RPM Watts036-21411-002-A-0204 2500 1059 1560 1077 1590 1095 1630 Static Resistances MEDLOW RESISTANCE, IWG Description CFMMOTOR1 Adjustable Motor and Drive Data BELT-DRIVE BlowerBasic Unit W/ DIRECT-DRIVE Electrical Data BeltBasic Unit W/ BELT-DRIVE Electrical Data Electrical Data COOLING/ELECTRIC Heat W/ Direct Drive DEE036 Fuse Block Accessory Electric Heat Correction FactorsNominal Voltage Part Number VoltsDEE Supply Model Stages SIZE1 Motor Ampacity Amps Breaker FLAElectrical Data COOLING/ELECTRIC Heat W/ Belt Drive DEE036 DEE Supply Model Stages Electrical Data COOLING/ELECTRIC Heat W/ Belt Drive DEE060Motor Ampacity Comprssorr Elayand COOLING/HEATINGELECTRONICTHERMOSTAT Singlestage Hole Knockout Size DIAUnit Dimensions DEG 3, 4, & 5 TON DEE/DEG Unit Clearances DEE/DEG Dimensions Rear View 3, 4, & 5 TON Detail B Unit Dimensions with DAMPER/RAINHOOD Roof Curb Dimensions DEE & DEG 3, 4, & 5 TON Unit Weights Unit Corner WeightsTypical Applications Mechanical Specifications Unit Operating Characteristics GAS Heating Section DEG ModelsElectric Heating Section DEE Models Electrical RequirementsOther Factory Installed Options Other PRE-ENGINEERED Accessories AVAIL- AbleOptional Outdoor AIR

D1EG, D1EE036 specifications

The York D1EE036 and D1EG are two models of high-performance direct expansion (DX) rooftop air conditioning units designed for commercial applications. These units are known for their efficiency, reliability, and advanced technology.

The D1EE036 model is particularly recognized for its energy efficiency, featuring a high-efficiency scroll compressor. This compressor operates at lower energy consumption levels while providing consistent cooling performance. The unit is equipped with variable speed technology, which adjusts the compressor's speed according to the cooling demand. This feature not only optimizes energy use but also minimizes the sound levels during operation, making it suitable for noise-sensitive environments such as hospitals and schools.

On the other hand, the D1EG model is designed for versatility and offers a range of custom configuration options. It incorporates advanced controls that allow for integration with building management systems, enabling users to monitor and manage their HVAC systems remotely. The D1EG is also notable for its robust construction, with weather-resistant enclosures that ensure durability and longevity in various environmental conditions.

Both models feature an advanced microprocessor control system that provides precise temperature control and enhances overall system efficiency. These controls allow for multiple unit configurations, including staged cooling, which further contributes to energy savings. Additionally, both units come equipped with high-efficiency filters that improve indoor air quality by trapping dust, pollen, and other airborne particles.

From a technological standpoint, the York D1EE036 and D1EG models support environmentally friendly refrigerants, which comply with the latest regulations for reducing ozone depletion potential. The use of these refrigerants not only helps in meeting regulatory requirements but also aligns with global sustainability goals.

In summary, the York D1EE036 and D1EG rooftop units are engineered to deliver excellent performance, adaptability, and energy efficiency for commercial settings. Their combination of innovative technologies, environmentally conscious design, and advanced control features make them a compelling choice for businesses looking to enhance their HVAC systems while reducing operational costs. Whether requiring quiet operation or robust configurability, these units offer solutions that cater to diverse commercial needs.