York D1EE036 Capacity Ratings Cooling / Electric Heating, Capacity Ratings Cooling / GAS Heating

Page 6

036-21411-002-A-0204

TABLE 1: CAPACITY RATINGS - COOLING / ELECTRIC HEATING

 

 

 

ARI RATINGS1

 

 

 

NOMINAL ELECTRIC HEAT CAPACITY2 (kW)

MODEL

 

COOLING CAPACITY 80 / 67-95°F

 

SOUND

 

 

 

 

 

 

MBH

 

SEER4

 

EER5

RATING3

 

240V

480V

600V

 

 

 

(dBels)

 

 

 

 

 

 

 

 

 

DEE036

42.5

 

11.5

 

10.10

86.0

 

5, 7, 10, 15 &

7, 10, 15 & 20

10, 15, & 20

 

 

 

20

 

 

 

 

 

 

 

 

 

 

DEE048

49.5

 

11.0

 

10.0

86.0

 

5, 7, 10, 15 &

7, 10, 15 & 20

10, 15, & 20

 

 

 

20

 

 

 

 

 

 

 

 

 

 

DEE060

58.5

 

11.0

 

10.05

86.0

 

5, 7, 10, 15,

7, 10, 15, 10,

10, 15, 20 &

 

 

 

20, & 30

& 30

30

 

 

 

 

 

 

 

 

1.Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2.

Heaters are available as accessories - all with single point power supply

Not ARI required

3.

Rated in accordance with ARI Standard 270.

 

4.

SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling

 

divided by the total electric power input in watt-hours during the same period.

 

5.

EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given

 

set of rating conditions, expressed in BTUH per watt (BTUH/watt).

 

TABLE 2: CAPACITY RATINGS - COOLING / GAS HEATING

 

 

ARI RATINGS1

 

 

 

GAS HEAT CAPACITY

 

 

MODEL

COOLING CAPACITY 80 /

SOUND

INPUT

OUTPUT

 

 

 

TEMP.

GASE LINE SIZE

 

67-95°F

 

RATING2

AFUE3 (%)

S.S.E.4 (%)

 

RISE

 

 

 

(MBH)

(MBH)

 

(in. O.D.)

 

MBH

SEER5

EER6

(dBels)

 

 

 

(°F)

 

 

 

 

 

 

 

DEG036N040

42.5

11.5

10.1

86

50

40

80.9

81.6

 

15-45

1/2

DEG036N079

42.5

11.5

10.1

86

100

79

80.5

80.8

 

40-70

1/2

DEG048N060

49.5

11.0

10.0

86

75

59

80.9

81.6

 

25-55

1/2

DEG048N099

49.5

11.0

 

86

125

99

80.3

80.6

 

45-75

1/2

10.0

 

DEG060N079

58.5

11.0

10.05

86

100

79

80.5

80.8

 

25-55

1/2

DEG060N099

58.5

11.0

10.05

86

125

99

80.3

80.6

 

35-65

1/2

1.

Ratings are in accordance with ARI Standard 210.

 

Not ARI required

2.

Sound ratings are in accordance with ARI Standard 270.

 

 

 

 

3.AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.

4.S.S.E. = Steady State Efficiency (Percent Output).

5.SEER =Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power input in watt-hours during the same period.

6.EER = Energy Efficiency Ratio - the cooling capacity in BTU’s per hour (BTUH) divided by the power input in watts at any given set of rating conditions, expressed in BTUH per watt (BTUH/watt).

TABLE 3: SOUND POWER RATINGS1

UNIT

 

ESP

BLOWER

 

 

 

 

SOUND POWER (dB 10-12WATTS)

 

 

SIZE

CFM

 

 

 

 

OCTAVE BAND CENTERLINE FREQUENCY (Hz)

 

SWL

dBA

 

 

 

 

 

 

 

 

 

 

 

 

 

dB(A)

@ 10Ft2

 

 

IWG

SPEED

kW

63

125

250

500

 

1000

2000

4000

8000

036

1200

0.60

LOW

0.60

84

84

74

67

 

69

62

57

52

74

41

048

1600

0.55

HIGH

0.80

85

85

75

68

 

70

63

58

53

75

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

060

2000

0.45

HIGH

1.00

86

86

76

69

 

71

64

59

54

76

43

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are to be used fro reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

6

Unitary Products Group

Image 6
Contents General Flexible Easy to Install Single Package UnitsTechnical Guide Sunline Plus AIR-COOLED AIR Conditioners FeaturingTable of Contents Features DescriptionFACTORY-INSTALLED Options FIELD-INSTALLED AccessoriesSunline Plus Component Location Sound Power RATINGS1 Capacity Ratings Cooling / Electric HeatingCapacity Ratings Cooling / GAS Heating Physical Data Basic Unit Models DEE/DEGCooling Capacities 3 TON DEE / DEG036 AIR on Temperature of AIR on Condenser CoilTotal Power Evaporator Sensible CAPACITY1, MBHCooling Capacities 4 TON DEE / DEG048 Cooling Capacities 5 TON DEE / DEG060 Model AIR Available External Static Pressure IWG3 Flow CFM RPM Watts036-21411-002-A-0204 2500 1059 1560 1077 1590 1095 1630 LOW Static ResistancesMED RESISTANCE, IWG Description CFMBasic Unit W/ DIRECT-DRIVE Electrical Data MOTOR1 AdjustableMotor and Drive Data BELT-DRIVE Blower BeltBasic Unit W/ BELT-DRIVE Electrical Data Electrical Data COOLING/ELECTRIC Heat W/ Direct Drive DEE036 Nominal Voltage Fuse Block AccessoryElectric Heat Correction Factors Part Number VoltsDEE Supply Model Stages SIZE1 Motor Ampacity Amps Breaker FLAElectrical Data COOLING/ELECTRIC Heat W/ Belt Drive DEE036 Electrical Data COOLING/ELECTRIC Heat W/ Belt Drive DEE060 DEE Supply Model StagesMotor Ampacity Comprssorr Elayand COOLING/HEATINGELECTRONICTHERMOSTAT Singlestage Hole Knockout Size DIAUnit Dimensions DEG 3, 4, & 5 TON DEE/DEG Unit Clearances DEE/DEG Dimensions Rear View 3, 4, & 5 TON Detail B Unit Dimensions with DAMPER/RAINHOOD Roof Curb Dimensions DEE & DEG 3, 4, & 5 TON Unit Weights Unit Corner WeightsTypical Applications Mechanical Specifications Electric Heating Section DEE Models Unit Operating CharacteristicsGAS Heating Section DEG Models Electrical RequirementsOther PRE-ENGINEERED Accessories AVAIL- Able Other Factory Installed OptionsOptional Outdoor AIR

D1EG, D1EE036 specifications

The York D1EE036 and D1EG are two models of high-performance direct expansion (DX) rooftop air conditioning units designed for commercial applications. These units are known for their efficiency, reliability, and advanced technology.

The D1EE036 model is particularly recognized for its energy efficiency, featuring a high-efficiency scroll compressor. This compressor operates at lower energy consumption levels while providing consistent cooling performance. The unit is equipped with variable speed technology, which adjusts the compressor's speed according to the cooling demand. This feature not only optimizes energy use but also minimizes the sound levels during operation, making it suitable for noise-sensitive environments such as hospitals and schools.

On the other hand, the D1EG model is designed for versatility and offers a range of custom configuration options. It incorporates advanced controls that allow for integration with building management systems, enabling users to monitor and manage their HVAC systems remotely. The D1EG is also notable for its robust construction, with weather-resistant enclosures that ensure durability and longevity in various environmental conditions.

Both models feature an advanced microprocessor control system that provides precise temperature control and enhances overall system efficiency. These controls allow for multiple unit configurations, including staged cooling, which further contributes to energy savings. Additionally, both units come equipped with high-efficiency filters that improve indoor air quality by trapping dust, pollen, and other airborne particles.

From a technological standpoint, the York D1EE036 and D1EG models support environmentally friendly refrigerants, which comply with the latest regulations for reducing ozone depletion potential. The use of these refrigerants not only helps in meeting regulatory requirements but also aligns with global sustainability goals.

In summary, the York D1EE036 and D1EG rooftop units are engineered to deliver excellent performance, adaptability, and energy efficiency for commercial settings. Their combination of innovative technologies, environmentally conscious design, and advanced control features make them a compelling choice for businesses looking to enhance their HVAC systems while reducing operational costs. Whether requiring quiet operation or robust configurability, these units offer solutions that cater to diverse commercial needs.