Lenox XC14 Operating Gauge Set and Service Valves, Torque Requirements, Using Manifold Gauge SET

Page 4

WARNING

Electric Shock Hazard. Can cause injury or death. Unit must be grounded in accordance with national and local codes.

Line voltage is present at all components when unit is not in operation on units with single-pole contactors. Disconnect all remote electric power supplies before opening access panel. Unit may have multiple power supplies.

CAUTION

Physical contact with metal edges and corners while applying excessive force or rapid motion can result in personal injury. Be aware of, and use caution when working near these areas during installation or while servicing this equipment.

Operating Gauge Set and Service Valves

These instructions are intended as a general guide and do not supersede local codes in any way. Consult authorities who have jurisdiction before installation.

TORQUE REQUIREMENTS

When servicing or repairing heating, ventilating, and air conditioning components, ensure the fasteners are appropriately tightened. Table 1 lists torque values for fasteners.

IMPORTANT

Only use Allen wrenches of sufficient hardness (50Rc − Rockwell Harness Scale minimum). Fully insert the wrench into the valve stem recess.

Service valve stems are factory−torqued (from 9 ft−lbs for small valves, to 25 ft−lbs for large valves) to prevent refrigerant loss during shipping and handling. Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench, or stripping the valve stem recess.

See the Lennox Service and Application Notes #C−08−1 for further details and information.

IMPORTANT

To prevent stripping of the various caps used, the appropriately sized wrench should be used and fitted snugly over the cap before tightening.

Table 1. Torque Requirements

Parts

Recommended Torque

 

 

 

Service valve cap

8 ft.− lb.

11 NM

 

 

 

Sheet metal screws

16 in.− lb.

2 NM

 

 

 

Machine screws #10

28 in.− lb.

3 NM

 

 

 

Compressor bolts

90 in.− lb.

10 NM

 

 

 

Gauge port seal cap

8 ft.− lb.

11 NM

 

 

 

USING MANIFOLD GAUGE SET

When checking the system charge, only use a manifold gauge set that features low loss anti−blow back fittings.

Manifold gauge set used with HFC−410A refrigerant systems must be capable of handling the higher system operating pressures. The gauges should be rated for use with pressures of 0 − 800 psig on the high side and a low side of 30" vacuum to 250 psig with dampened speed to 500 psi. Gauge hoses must be rated for use at up to 800 psig of pressure with a 4000 psig burst rating.

OPERATING SERVICE VALVES

The liquid and vapor line service valves are used for removing refrigerant, flushing, leak testing, evacuating, checking charge and charging.

Each valve is equipped with a service port which has a factory−installed valve stem. Figure 2 provides information on how to access and operating both angle and ball service valves.

Page 4

506636−01

Image 4
Contents Table of Contents GeneralShipping and Packing List AIR ConditionerModel Number Identification Unit Dimensions − Inches mm230 Typical Unit Parts Arrangement Plumbing and Switches ComponentsControl Panel Operating Gauge Set and Service Valves Using Manifold Gauge SETOperating Service Valves Torque RequirementsOperating Angle Type Service Valve Operating Ball Type Service ValveTo Access Service Port Reinstall Stem CapRecovering Refrigerant from Existing System 1DISCONNECT PowerRecovering Refrigerant 2CONNECT Manifold Gauge SETUnit Placement Clearance on ALL SidesPositioning Considerations Placing Unit on SlabDetail a Outside Unit Placement Detail C Elevated Slab Mounting using Feet ExtendersDetail D Slab Side Mounting Detail E Deck Top MountingRemoving and Installing Panels Louvered Panel InstallationRoof Mounting Louvered Panel RemovalRefrigerant Line SET New or Replacement Line SetRefrigerant Line Set Refrigerant Line SET From Vertical to Horizontal Refrigerant Line SET Alling Horizontal RunsBrazing Connections Brazing Procedures 1CUT and DeburWrap Service Valves Flow Nitrogen6BRAZE Line SET 7PREPARATION for Next StepInstalling Indoor Expansion Valve Flushing Line Set and Indoor CoilInstalling Indoor Metering Device Indoor Expansion Valve InstallationSensing Bulb Installation Equalizer Line InstallationLeak Test Line Set and Indoor Coil Leak TestEvacuating Line Set and Indoor Coil Evacuating SystemSize Circuit and Install Disconnect 2INSTALL ThermostatElectrical 24VAC TransformerVAC Control Wiring Diagrams Field Installed Typical Factory Wiring Diagram Interlink Compressor Typical Unit Wiring Diagram Connections for Testing and Charging Servicing Units Delivered Void of ChargeUnit Start−Up System RefrigerantDetermining Charge Method Which indoorMetering Device?Checking AIR Flow AT Indoor Coil Calculating System Charge for Outdoor Unit Void of ChargeAbove Below40ºF SHº Superheat Values +/−5ºFNormal Operating Pressures Liquid +10 and Suction +5 psig System OperationUnit Components Maintenance Indoor UnitIndoor Coil Unit Nameplate ActualStart−Up and Performance Checklist Installer CityJob Name Job no Date Job Location City State

Elite Series, XC14 specifications

The Lenox Elite Series XC14 is a remarkable tool designed for superior cutting performance in various applications. This saw blade stands out due to its innovative technologies and features, which cater to the needs of professionals in woodworking, metalworking, and general cutting tasks.

One of the key features of the XC14 is its carbide-tipped teeth. These teeth are engineered for longevity and efficiency, allowing for extended use without performance degradation. The unique geometry of the teeth enhances cutting speed while minimizing resistance, making it ideal for a range of materials including hardwoods, softwoods, and metals.

The blade’s construction is another significant aspect of its design. Made from high-quality steel, the XC14 ensures durability and resistance to bending or warping under stress. This robust construction contributes to the blade's overall stability, resulting in smoother cuts and reduced vibration during operation.

Another noteworthy technology embedded in the XC14 is its advanced tooth design. The combination of alternate top bevel (ATB) and flat (F) configurations allows for precision cutting and a cleaner finish. This feature is particularly beneficial when working on intricate projects that require a high level of accuracy.

To enhance performance further, the XC14 incorporates a unique thin kerf design. This design reduces the width of the cut, which not only conserves material but also requires less power from the saw. This energy efficiency translates to less wear on the saw, extending the lifecycle of both the blade and the tool itself.

The blade is also designed with heat dissipation in mind. Specially engineered cooling vents help in maintaining optimal temperature during operation. This technology reduces the risk of overheating, which can compromise the integrity of the blade and the quality of the cut.

Versatility is another standout feature of the Lenox Elite Series XC14. It is suitable for table saws, miter saws, and portable saws, making it a valuable tool for professionals and DIY enthusiasts alike. Whether tackling large construction projects, meticulous cabinetry, or small home repairs, the XC14 adapts efficiently to diverse cutting needs.

In conclusion, the Lenox Elite Series XC14 combines advanced technologies, premium materials, and thoughtful design to deliver exceptional cutting performance. Its carbide-tipped teeth, innovative geometry, stable construction, thin kerf, heat dissipation features, and versatility make it a top choice for those seeking reliable and efficient cutting solutions in various applications.