Default Thermostat Settings
Default Thermostat settings are in table 1.
Table 1
Default Thermostat Settings
Mode | Heat |
|
|
Setpoint | 70°F (or 21°C) |
|
|
Fan | Auto |
|
|
Filter Reminder | OFF (reminder setting = 0) |
|
|
Equipment Protection | reset back to zero |
Timers |
|
|
|
Technical Specifications
Thermostat Type
Electronic nonprogrammable thermostat for 1H/1C, heat pump with electric or gas backup heat source, non−power robbing applications.
Power Supply Range
18VAC − 30VAC (24VAC nominal), 60Hz
Temperature Display
Display Scale: Fahrenheit or Celsius user selectable (via DIP switches)
Display range: 35°F (2°C) to 99°F (37°C)
Display resolution: 1°F (1°C)
Display Accuracy: +/−1°F
Temperature Measurement Range
Measurement Scale: Fahrenheit
Measurement Range: 35°F to 99°F
Measurement Resolution: 0.5°F
Measurement Accuracy: +/−1°F
Field Offset: via DIP switches to +/−3°F
Sampling Method: temperature measurements sampled every 15 seconds. Displayed temperature is the average of the last four measurements.
Temperature Setpoint Range
Setting range: 50°F (10°C) to 90°F (32°C)
Setting resolution: 1°F (1°C)
Fan Control
AUTO or ON modes.
Backup Heat Source Selection
Electric or gas furnace, selectable via DIP switch #5 (Aux or Dual, respectively). See also Thermostat Output section.
I/O Relays
All thermostat relays are latching type to minimize power consumption. See table 2.
| Table 2 |
51M33 Terminal Designations | |
|
|
Connections | Description |
|
|
O | Reversing valve, cool active |
|
|
B | Reversing valve, heat active |
|
|
R | 24VAC |
|
|
G | Fan control |
|
|
Y1 | First stage cooling/heating, compres- |
| sor generated |
|
|
W1 | Auxiliary heating, furnace generated |
|
|
L | Service Indicator |
|
|
C | 24VAC common |
|
|
E | Emergency heat |
|
|
T | Outdoor temperature sensor |
| connection 1 |
|
|
T | Outdoor temperature sensor |
| connection 2 |
|
|
Equipment Protection Timers
Minimum Compressor OFF time: 5 minutes
Minimum Compressor ON time: 4 minutes
Minimum Furnace ON time: 3 minutes
Minimum backup furnace cycle time (elapsed time be- tween any furnace activation and the next furnace activa- tion): 6 minutes.
Minimum elapsed time between any compressor activation and the next compressor activation: 6 minutes.
NOTE − All protection timers (except the compressor OFF timer) can be over−ridden if a heating or cooling demand is initiated or terminated using the UP, DOWN, HEAT, or COOL buttons.
Equipment Protection Override
Both the minimum compressor OFF timer and the mini- mum equipment cycle timer can be over−ridden by press- ing and holding either the HEAT or COOL button down for 4 seconds.
Over−Temperature Protection
Thermal mechanical switch opens W1 at 93°F+/−6°F.
Filter Reminder
Settings of 0 (Off), 1, 3, 6 or 12 months are available. When programmed time has elapsed, a FILTER indicator is dis- played.
Balance Point
0°F (OFF) to 55°F, user selectable.