Lennox International Inc 51M32 operation manual Thermostat Output Table

Page 13

Service Reminder

The SERVICE indicator is displayed only under the follow- ing conditions:

Sif the thermostat Y1 terminal has been activated with 24VAC for at least 5 minutes, AND the L terminal is shorted to the R terminal;

OR

Sif the thermostat Y1 terminal has been activated with 24VAC for at least 5 minutes, AND the L terminal is shorted to the C terminal.

Power Loss/Recovery

Thermostat memory is retained for a minimum of 24 hours during a power loss (includes retention of programmed temperature setpoint, heat/cool and fan mode settings, fil- ter reminder status, and equipment protection timers). Af- ter 24 hours of power loss, programmed settings will be lost and replaced with default settings.

IMPORTANT

Power must be applied for at least six consecutive hours prior to a power loss in order for memory to be retained for the specified time.

LCD Backlight

Activated for 8 seconds when any key is pressed.

NOTE − During an electrical storm or similar disturbance, the backlight may activate for a few seconds. This is normal and will no longer occur after the electrical disturbance has passed.

Thermostat Operating Conditions

35°F to 105°F, 5% to 90% RH

Thermostat Storage Conditions

−40°F to 185°F, 5% to 95% RH

Thermostat Output Table

Table 3 (see page 8) provides details of the 51M33 ther- mostat output states for various input conditions.

Page 7

Image 13
Contents Initial Thermostat Power-up Table of ContentsMeritR Series Thermostat GeneralHeat Mode Disabled Heat Mode EnabledHeating Control Display − Home ScreenEnabling and Disabling Cool Mode Adjusting Temperature SetpointSetpoint Display and Adjustment Cooling ControlFilter Reminder Fan ControlThermostat Reset Service IndicatorDefault Thermostat Settings Technical SpecificationsThermostat Output Table Controls 51M33 Emergency Heat Mode Additional Thermostat Buttons Normal Heat ModeNormal Heat Mode Enabled Emergency Heat Mode EnabledCooling Control Fan Control Service Indicator Flashing Room Balance Point SettingBalance Point 51M33 Terminal Designations Backup Heat Source SelectionBalance Point Thermostat Output Table Gas Heat Backup Dual Fuel − No Outdoor Sensor Electric Heat Backup − No Outdoor SensorElectric Heat Backup − Outdoor Sensor Attached Gas Heat Backup Dual Fuel − Outdoor Sensor Attached